API PUBL 937-1996 Evaluation of Design Criteria for Storage Tanks with Frangible Roof Joints《对带有脆性顶连接储罐设计准则的评估》.pdf
《API PUBL 937-1996 Evaluation of Design Criteria for Storage Tanks with Frangible Roof Joints《对带有脆性顶连接储罐设计准则的评估》.pdf》由会员分享,可在线阅读,更多相关《API PUBL 937-1996 Evaluation of Design Criteria for Storage Tanks with Frangible Roof Joints《对带有脆性顶连接储罐设计准则的评估》.pdf(82页珍藏版)》请在麦多课文档分享上搜索。
1、Evaluation of Design Criteria for Storage Tanks With Frangible Roof Joints API PUBLICATION 937 APRIL 1996 American Petroleum Institute 1220 L Street, Northwest Washington, D.C. 20005 11 (1) API publications necessarily address problems of a general nature. With respect to particular circumstances, l
2、ocal, state, and federal laws and regulations should be reviewed. (2) API is not undertaking to meet the duties of employers, manufacturers, or suppliers to warn and properly train and equip their employees, and others exposed, concerning health and safety risks and precautions, nor undertaking thei
3、r obligations under local, state, or federal laws. (3) Information concerning safety and health risks and proper precautions with respect to particular materials and conditions should be obtained from the employer, the manufacturer or supplier of that material, or the material safety data sheet. (4)
4、 Nothing contained in any API publication is to be construed as granting any right, by implication or otherwise, for the manufacture, sale, or use of any method, apparatus, or product covered by letters patent. Neither should anything contained in the publication be construed as insuring anyone agai
5、nst liability for infringement of letters patent. (5) Generally, API standards are reviewed and revised, reaffirmed, or withdrawn at least every five years. Sometimes a one-time extension of up to two years will be added to this review cycle. This publication will no longer be in effect five years a
6、fter its publication date as an operative API standard or, where an extension has been granted, upon republication. Status of the publication can be ascertained from the API Authoring Department telephone (202) 682-8000. A catalog of API publications and materials is published annually and updated q
7、uarterly by API, 1220 L Street, N.W., Washington, D.C. 20005. Copyright s 1996 Welding Research Council Inc. American Petroleum Institute EVALUATION OF DESIGN CRITERIA FOR STORAGE TANKS WITH FRANGIBLE ROOF JOINTS Daniel Swenson, Co-Investigator Don Fenton, Co-Investigator Zhi Lu, Graduate Research A
8、ssistant Asif Ghori, Graduate Research Assistant Joe Baalman, Graduate Research Assistant Mechanical Engineering Department Kansas State University Manhattan, KS 66506 API PUBLICATION 937-APRIL 1996 American Petroleum Institute 1220 L Street, Northwest Washington, D.C. 20005 Q FOREWORD American Petr
9、oleum Institute (API) provides standards for the design, construction and inspection of storage tanks. One of the family of design standards, API 650-Welded Steel Tanks for Oil Storis the target of the research addressed by this Bulletin. API 650 includes, among other important design provisions, cr
10、iteria governing the design of frangible rooIjoi#s for w for tanks with diameters of 35 to 60 feet, 2 by 2 by 1/4 inches; for larger tanks 3 by 3 by % inches. Section 3.10.2.2: Roof plates shall have a minimum nominal thickness of 3/16 inch (permissible ordering basis-7.65 pounds per square fool of
11、plate, 0.180- inch plate, or 7-gauge sheet). Section 3.10.2.3: Roof plates of supported cone roofs shall not be attached to the supporting mem- bers. Section 3.10.2.5: Basic criteria for frangible roof joints are given in this section. Section 3.10.2.5 states that for a frangible joint, the top angl
12、e may be smaller than that specified in Section 3.1.5.9. 2 Frangible Roof Joints CONCRETE FWNOATION 114 ItK SlNGlE LAP 25 -0 NOM OIAMETER Fig. 2.2-Overall layout of typical tank Section 3.10.2.5.1: The continuous fillet weld be- tween the roof plates and the top angle can not exceed %s inch. The slo
13、pe of the roof at the top-angle attachment can not exceed 2 inches in 12 inches. Section 3.10.2.5.3: The cross-sectional area at the roof-to-shell junction should not exceed: 0.153 W A = 30,800 tan 0 where, A = Area resisting the compressive force, in square inches, W = Total weight of the shell and
14、 any framing (but not roof plates) supported by the shell and roof, in pounds, 8 = Angle between the roof and a horizontal plane at the roof-to-shell junction, in degrees. Section 3.10.4.1: Roof plates shall be welded on the top side with continuous full-fillet welds on all seams. The size of the ro
15、of-to-top angle weld shall be inch or smaller if so specified on the purchase order. Section 3.10.4.2: The slope of the roof shall be 3/4 inch in 12 inches, or greater if specified by purchaser. (Note: Section 3.10.2.5 limits maximum slope to 2 inches in 12 inches.) Section 3.10.4.5: Rafters shall b
16、e spaced so that at the outer edges their center shall be not more than 6.28 feet apart. Spacing on inner rings shall not be less than 5% feet. Appendix F.2.2.1: When the construction of the compression ring conforms to but does not exceed the minimum requirements of Item e of 3.1.5.9, 3.10.2, and 3
17、.10.4, the frangible characteristic of the ring is retained, and additional emergency venting devices are not required. (Note: The Appendix F requirement to conform to 3.1.5.9 (Item e) is not consistent with Section 10.3.2.5 which allows compression ring area to be reduced for frangible joints.) App
18、endix F.4.1: Maximum design pressure is given by: where, P = internal design pressure, in inches of water, D = tank diameter, in feet, th = nominal roof thickness, in inches. Appendix F.4.2: The maximum design pressure, limited by uplift at the base of the shell, shall not exceed: 0.245W 0.735M P, =
19、 - D2 + 8th - D3 (2.2.3) where, M = wind moment, in foot-pounds. Note: the wind moment term was not in the Eighth Edition of API 650 (API, 1988). Appendix F.5.1: Where the maximum design pres- sure has already been established (not higher than Frangible Roof Joints 3 Frangible Roof Joints that permi
20、tted by F.4.2 or F.4.3), the total required given in Appendix F and are shown in Figure 2.4. As compression area at the roof-to-shell junction may be the roof lifts due to internal pressure, it applies an calculated from the following: inward radial force on the compression area. The compression are
21、a calculations in Figure 2.4 allow the D2(P - 8th) A = (2.2.4) designer to calculate the area available to resist this 30,80O(tan 0) compressive force. Appendix F.5.6: Failure can be expected to occur when the stress in the compression ring area reaches the yield point, as given by: Pf = 1.6P - 4.8t
22、h (2.2.5) where Pf = calculated failure pressure, in inches of water. In addition to the rules given above, only certain configurations of joint design are allowed. These are 2.3 Derivation of API 650 Rules In the above section, the rules that govern frangible joint design were listed as facts. To t
23、ruly understand the rules, it is necessary to understand the intent and derivation of the rules. In this section, we re-derived the API 650 rules to make clear the assumptions on which they are based. The intent is stated in Section 3.10.2.5.1, where, if Neutral axis of amgle , Detail a Detail b Det
24、ell o Detall d Detail e Detail f Detall g max max Detall h Detail I r, = thickness of angle leg. wh = maximum width of participating roof. rb = thickness of bar. = 0.3(Rr). or I2 inches, whichever is less. r, = thickness of shell plate. R, = inside radius of tank shell. rh = thickness of roof plate.
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- APIPUBL9371996EVALUATIONOFDESIGNCRITERIAFORSTORAGETANKSWITHFRANGIBLEROOFJOINTS 带有 脆性 连接 设计 准则 评估 PDF

链接地址:http://www.mydoc123.com/p-399901.html