BS ISO TR 5925-2-1998 Fire tests - Smoke control door and shutter assemblies - Commentary on test method and test data application《防火试验 烟雾防护门和防护屏组件 试验方法和试验数据的应用说明》.pdf
《BS ISO TR 5925-2-1998 Fire tests - Smoke control door and shutter assemblies - Commentary on test method and test data application《防火试验 烟雾防护门和防护屏组件 试验方法和试验数据的应用说明》.pdf》由会员分享,可在线阅读,更多相关《BS ISO TR 5925-2-1998 Fire tests - Smoke control door and shutter assemblies - Commentary on test method and test data application《防火试验 烟雾防护门和防护屏组件 试验方法和试验数据的应用说明》.pdf(16页珍藏版)》请在麦多课文档分享上搜索。
1、BRITISH STANDARD BS ISO TR 5925-2:1997 Fire tests Smoke control door and shutter assemblies Part 2: Commentary on test method and test data application ICS 13.220.50; 91.060.50BSISO TR 5925-2:1997 This British Standard, having been prepared under the directionof the Health and Environment Sector Boa
2、rd, waspublished under the authorityof the Standards Boardand comes into effect on 15 February 1998 BSI 04-1999 ISBN 0 580 29228 2 National foreword This British Standard reproduces verbatimISOTR5925-2:1997 and implements it as the UK national standard. The UK participation in its preparation was en
3、trusted by Technical CommitteeFSH/22, Fire resistance tests, to SubcommitteeFSH/22/5, Test procedures for doors, which has the responsibility to: aid enquirers to understand the text; present to the responsible international/European committee any enquiries on the interpretation, or proposals for ch
4、ange, and keep the UK interests informed; monitor related international and European developments and promulgate them in the UK. A list of organizations represented on this subcommittee can be obtained on request to its secretary. Cross-references The British Standards which implement international
5、or European publications referred to in this document may be found in the BSI Standards Catalogue under the section entitled “International Standards Correspondence Index”, or by using the “Find” facility of the BSI Standards Electronic Catalogue. A British Standard does not purport to include all t
6、he necessary provisions of a contract. Users of British Standards are responsible for their correct application. Compliance with a British Standard does not of itself confer immunity from legal obligations. Summary of pages This document comprises a front cover, an inside front cover, pages i and ii
7、, theISO/TRtitle page, pageii, pages1to8 and a back cover. This standard has been updated (see copyright date) and may have had amendments incorporated. This will be indicated in the amendment table on the inside front cover. Amendments issued since publication Amd. No. Date CommentsBSISO TR 5925-2:
8、1997 BSI 04-1999 i Contents Page National foreword Inside front cover Foreword ii Introduction 1 1 Scope 1 2 References 1 3 Definitions 1 4 Fire and smoke 2 5 The role of doors in fire 2 6 Selection of test conditions 3 7 Test package 5 8 Some points relevant to tests 5 9 Practical application of te
9、st results 6 Annex A Estimation of smoke concentration 8 Figure 1 Examples of different doors 6 Figure 2 Different fire scenarios 7 Table 1 Time (minutes) to reach 1% type2, when the subject is still under technical development or where for any other reason there is the future but not immediate poss
10、ibility of an agreement on an International Standard; type3, when a technical committee has collected data of a different kind from that which is normally published as an International Standard (“state of the art”, for example). Technical Reports of types1and2are subject to review within three years
11、 of publication, to decide whether they can be transformed into International Standards. Technical Reports of type3do not necessarily have to be reviewed until the data they provide are considered to be no longer valid or useful. ISO/TR5925-2, which is a Technical Report of type3, was prepared joint
12、ly by Technical CommitteeISO/TC92, Fire safety, SubcommitteeSC2, Fire resistance. ISO/TR5925consists of the following parts, under the general title Fire tests Smoke control door and shutter assemblies: Part 1: Ambient and medium temperature leakage test procedure; Part 2: Commentary on test method
13、and test data application. Descriptors: Buildings, fire protection, smoke control, doors, fire doors, tests, fire tests, test results.BSISO TR 5925-2:1997 BSI 04-1999 1 Introduction Technical CommitteeISO/TC92 Fire safety, has prepared a test specification for smoke control doors as follows: ISO5925
14、-1, Fire tests Smoke control door and shutter assemblies Part1: Ambient and medium temperature leakage test procedure. In a fire the decomposition of materials results in the production of heat and fire gases containing smoke particles. The consequent expansion of gases leads to the creation of pres
15、sure differential across door faces often assisted by wind pressures, mechanical or extract systems, stack effect or a combination of these. This pressure differential induces the movement of smoke past any openings or gaps including those in a door assembly. Schemes to keep building areas free of s
16、moke use various techniques using obstructions to its movement, exhausting, dilution, pressurization either singly or in some suitable combination. Standard tests have been designed to measure the leakage of smoke when such conditions exist. They do not deal specifically with doors installed in conj
17、unction with smoke control methods based on pressurization but, nevertheless, information obtained from these tests is likely to be helpful in assessing the suitability of such doors. 1 Scope This Technical Report establishes a commentary which explains the general philosophy and factors on which th
18、e test specified inISO/DIS 5925-1 has been designed, to describe the limitations of its scope, to provide some general guidance for those who use the results of the test and to emphasize certain practical aspects of the procedure for those who carry out the test. All concerned with testing fire door
19、s should read this commentary before initiating the test and before making use of the test results. 2 References ISO834:1975, Fire-resistance tests Elements of building construction. ISO/DIS834-1, Fire-resistance tests Elements of building constructionPart 1: General requirements. ISO3008:1976, Fire
20、-resistance tests Door and shutter assemblies. ISO/TR3956:1975, Principles of structural fire-engineering design with special regard to the connection between real fire exposure and the heating conditions of the standard fire-resistance test (ISO834). ISO/DIS5925-1, Fire tests Smoke control door and
21、 shutter assemblies Ambient and medium temperature leakage test procedure. 3 Definitions For the purposes of this Technical Report, the definitions given inISO/DIS5925-1, together with the following, apply. 3.1 door and shutter assembly a door and shutter assembly is an assembly comprising a fixed p
22、art (the door frame), one or more movable parts (the door leaves) and its hardware. The purpose of the door assembly is to allow or prevent access of persons and/or goods. The term hardware includes such items as hinges, latches, door handles, locks, keyholes (excluding keys), letter plates, sliding
23、 gear, closing devices, electrical wiring and any other items which may influence the performance of the assembly being tested 3.2 fire control door a door assembly capable of maintaining for a specified period the fire resistance criteria defined inISO3008 3.3 smoke control door a door assembly who
24、se primary function is to restrict the passage of smoke as determined byISO5925 tests 3.4 fire and smoke control door a door assembly meeting the criteria appropriate for fire control and smoke control door assemblies 3.5 ambient temperature for the purpose of this standard ambient temperature is an
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- BSISOTR592521998FIRETESTSSMOKECONTROLDOORANDSHUTTERASSEMBLIESCOMMENTARYONTESTMETHODANDTESTDATAAPPLICATION

链接地址:http://www.mydoc123.com/p-397012.html