IEEE C62 92 1 ERTA-2017 en Errata to Guide for the Application of Neutral Grounding in Electrical Utility Systems-Part I Introduction.pdf
《IEEE C62 92 1 ERTA-2017 en Errata to Guide for the Application of Neutral Grounding in Electrical Utility Systems-Part I Introduction.pdf》由会员分享,可在线阅读,更多相关《IEEE C62 92 1 ERTA-2017 en Errata to Guide for the Application of Neutral Grounding in Electrical Utility Systems-Part I Introduction.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、30 November 2017 Product STD22421E IEEE Std C62.92.1 -2016 (Revision of IEEE Std C62.92.1-2000) Errata to IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems Part I: Introduction Sponsor Surge Protective Devices Committee of the IEEE Power and Energy Society Correction
2、Sheet Issued 30 November 2017 Copyright 2017 by The Institute of Electrical and Electronics Engineers. Inc. All rights reserved. Published 2017 Printed in the United States of America. This correction sheet may be freely reproduced and distributed in order to maintain the utility and currency of the
3、 underlying Standard. This correction sheet may not be sold, licensed or otherwise distributed for any commercial purposes whatsoever. The content of this correction sheet may not be modified. 30 November 2017 Product STD22421E Page 11, change the definition of coefficient of grounding (COG) to read
4、 as follows: coefficient of grounding (COG): The ratio, ELG/ELL (expressed as a percentage), of the highest root-mean-square (rms) line-to-ground power-frequency voltage ELG on a sound phase, at a selected location, during a fault to ground affecting one or more phases to the line-to-line power-freq
5、uency voltage ELL that would be obtained at the selected location with the fault removed. Page 13, change the Notes below Figure 1 to read as follows: NOTE 1 Va , Vb , and Vc are the respective source voltages (line-to-neutral). NOTE 2 RS and XS are the equivalent source resistance and reactance, pe
6、r phase. NOTE 3 Rn and Xn are the neutral resistance and reactance of the system as seen at the source. NOTE 4 Cg is the total system capacitance to ground and is obtained by connecting all three phases together and measuring the capacitance with the neutral grounding branch open-circuited. NOTE 5 C
7、g /3 is the grounded-wye partial, or zero-sequence, capacitance of the system. NOTE 6 CS is the ungrounded wye equivalent of the interphase partial capacitances of the system, obtained by subtracting the zero-sequence capacitance Cg/3 from the positive sequence capacitance C1. NOTE 7 f is frequency
8、in hertz. NOTE 8 The switch S, simulates a single-line-to-ground fault on a-phase. NOTE 9 Vf is the prefault line-to-ground voltage at the fault, the energization voltage. Page 15, the first paragraph under subclause 6.2 should read as follows: Various classes of grounding are available to the syste
9、m designer, each having a unique set of attributes. The response characteristics of the various classes of grounding may be defined or classified in terms of the ratios of symmetrical component parameters, such as the positive-sequence reactance X1, the negative-sequence reactance X2, the zero-seque
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- IEEEC62921ERTA2017ENERRATATOGUIDEFORTHEAPPLICATIONOFNEUTRALGROUNDINGINELECTRICALUTILITYSYSTEMSPARTIINTRODUCTIONPDF

链接地址:http://www.mydoc123.com/p-1249273.html