1、IEEE Std C57.147-2008IEEE Guide for Acceptance andMaintenance of Natural Ester Fluids inTransformersIEEE3 Park Avenue New York, NY 10016-5997, USA11 July 2008 IEEE Power +1 978 750 8400. Permission to photocopy portions of any individual standard for educational classroom use can also be obtained th
2、rough the Copyright Clearance Center. iv Copyright 2008 IEEE. All rights reserved. Introduction This introduction is not part of IEEE Std C57.147-2008, IEEE Guide for Acceptance and Maintenance of Natural Ester Fluids in Transformers. This guide was prepared by the Insulating Fluids Subcommittee of
3、the Transformers Committee of the IEEE Power Non-Transportation-Related Onshore and Offshore Facilities (Final Rule).6IEEE Std 62, IEEE Guide for Diagnostic Field Testing of Electric Power ApparatusPart 1: Oil Filled Power Transformers, Regulators, and Reactors.7, 8IEEE Std 637-1985 (Reaff 2007), IE
4、EE Guide for the Reclamation of Insulating Oil and Criteria for Its Use. IEEE Std 980, IEEE Guide for Containment and Control of Oil Spills in Substations. IEEE Std C57.104-1991, IEEE Guide for the Interpretation of Gases Generated in Oil-Immersed Transformers.9NFPA 70, National Electrical Code(NEC)
5、.10Official Methods and Recommended Practices of the AOCS, American Oil Chemists Society.116CFR publications are available from the Superintendent of Documents, U.S. Government Printing Office, P.O. Box 37082, Washington, DC 20013-7082, USA (http:/www.access.gpo.gov/). 7IEEE publications are availab
6、le from the Institute of Electrical and Electronics Engineers, 445 Hoes Lane, Piscataway, NJ 08854, USA (http:/standards.ieee.org/). 8The IEEE standards or products referred to in Clause 2 are trademarks owned by the Institute of Electrical and Electronics Engineers, Incorporated. 9IEEE Std C57.104-
7、1991 has been withdrawn; however, copies can be obtained from Global Engineering, 15 Inverness Way East, Englewood, CO 80112-5704, USA, tel. (303) 792-2181 (http:/ 10The NEC is published by the National Fire Protection Association, Batterymarch Park, Quincy, MA 02269, USA (http:/www.nfpa.org/). Copi
8、es are also available from the Institute of Electrical and Electronics Engineers, 445 Hoes Lane, Piscataway, NJ 08854, USA (http:/standards.ieee.org/). 11AOCS publications are available from The American Oil Chemists Society, 2710 S. Boulder, Urbana, IL 61802-6996, USA (http:/www.aocs.org). IEEE Std
9、 C57.147-2008 IEEE Guide for Acceptance and Maintenance of Natural Ester Fluids in Transformers 5 Copyright 2008 IEEE. All rights reserved. 3. Acronyms and abbreviations CFR Code of Federal Regulations cSt centistokes, units of measurement for kinematic viscosity DGA dissolved gas analysis EPA Envir
10、onmental Protection Agency HMWH high molecular weight hydrocarbon MSDS material safety data sheet NEC National Electrical CodePCB polychlorinated biphenyl SIC specific inductive capacity 4. Fluid tests and the significance of each test 4.1 General Many established ASTM tests of practical significanc
11、e can be applied to insulating fluids. The list of tests (see Table 1) and the significance of each test (see 4.3 through 4.18) are offered for classification purposes. (See Clause 2 for ASTM standards referenced in this clause.) Table 1 Insulating fluid tests suitable for natural ester-based dielec
12、tric fluids Significance (subclause) Test ASTM method number 4.2 Practices for sampling D923, D3305 4.3 Neutralization number D664, D974 4.4 Dielectric breakdown voltage D1816 4.5 Dielectric breakdown voltage, impulse conditions D3300 4.6 AC loss characteristicsdissipation factor and relative permit
13、tivity D924 4.7 Interfacial tension D971 4.8 Color D1500 4.9 Kinematic viscosity D445 4.10 Flash point and fire pointCleveland Open Cup Method D92 4.11 Relative density (specific gravity) D1298 4.12 Pour point D97 4.13 Volume resistivity (specific resistance) D1169 4.14 Gas analysis D2945, D3284, D3
14、612 4.15 Oxidation stability TBD 4.16 Water contentKarl Fischer Method aD1533 4.17 Visual examination field test (and color) D1500, D1524 4.18 Gassing of insulating oils under electrical stress and ionization D2300 4.19 Corrosive sulfur test D1275 4.20 Polychlorinated biphenyls (PCBs) D4059 aAlterna
15、te reagents as listed in ASTM D1533. IEEE Std C57.147-2008 IEEE Guide for Acceptance and Maintenance of Natural Ester Fluids in Transformers 6 Copyright 2008 IEEE. All rights reserved. 4.2 Practices for sampling (ASTM D923 and ASTM D3305) ASTM sampling practices are as follows: Practices for samplin
16、g electrical insulating fluids (ASTM D923) Practice for sampling small gas volume in a transformer (ASTM D3305) Accurate sampling, whether of the complete contents or only part thereof, is extremely important from the standpoint of evaluation of the quality of the product sampled. Careless sampling
17、procedures or contamination in the sampling equipment will result in a sample that is not truly representative, leading to erroneous conclusions concerning quality. The appropriate procedures and precautions outlined in ASTM D923 should be followed. 4.3 Acid number (ASTM D664 and ASTM D974) The acid
18、 (neutralization) number for service-aged fluids is, in general, a measure of the acidic constituents of the fluid. It may be useful, if compared to the value for the new product, to detect contamination by substances with which the fluid has been in contact. It may also reveal a tendency toward che
19、mical change or deterioration or to indicate chemical changes in additives. Natural ester fluids have naturally higher acid numbers than hydrocarbon-based fluids, even when new. The acid number may be used as a general guide for determining when oil should be replaced or reclaimed, provided suitable
20、 rejection limits have been established and confirmation is received from other tests. ASTM D664 is the preferred method when testing dielectric fluids that have become discolored, because it uses a potentiometric endpoint rather than a colorimetric endpoint used in ASTM D974. Although the acid numb
21、er indicates relative acid content, the cited methods do not indicate the chemical activity of the acids. Long-chain fatty acids produced by natural ester fluids are less reactive than short-chain organic acids produced by mineral oils. 4.4 Dielectric breakdown voltage (ASTM D1816) The dielectric br
22、eakdown voltage of an insulating fluid is of importance as a measure of its ability to withstand electric stress. It is the voltage at which breakdown occurs between two electrodes under prescribed test conditions. ASTM D1816 prescribes the use of spherically capped electrodes of the VDE type (see V
23、DE 0370-1978 B14).12It serves primarily to indicate the presence of contaminating agents (e.g., water, dirt, conducting particles in the liquid), one or more of which may be present when low dielectric breakdown values are found by test. Care must be taken when filling the test cell with natural est
24、er fluids to guard against trapping air bubbles, which can lead to misleading, low breakdown voltages. Due to their higher viscosity, a longer sample rest time (equal to or greater than 15 min at room temperature) is recommended for natural ester fluids than for mineral oils to allow air bubbles to
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- IEEEC571472008ENGUIDEFORACCEPTANCEANDMAINTENANCEOFNATURALESTERFLUIDSINTRANSFORMERS 变压器 天然 液体 验收 维护 指南

链接地址:http://www.mydoc123.com/p-1249209.html