ANSI IEEE C62 34-1996 Standard for Performance of Low-Voltage Surge-Protective Devices (Secondary Arresters)《低压电涌保护设备的性能(二次避雷器)》.pdf
《ANSI IEEE C62 34-1996 Standard for Performance of Low-Voltage Surge-Protective Devices (Secondary Arresters)《低压电涌保护设备的性能(二次避雷器)》.pdf》由会员分享,可在线阅读,更多相关《ANSI IEEE C62 34-1996 Standard for Performance of Low-Voltage Surge-Protective Devices (Secondary Arresters)《低压电涌保护设备的性能(二次避雷器)》.pdf(21页珍藏版)》请在麦多课文档分享上搜索。
1、 Copyright 1999 IEEE All Rights Reserved1IEEE Std C62.34-1996 (R2001)IEEE Standard for Performance of Low-Voltage Surge-Protective Devices (Secondary Arresters)SponsorSurge Protective Devices Committeeof thePower Engineering SocietyReaffirmed 30 January 2002Approved 5 June 1997American National Stan
2、dards InstituteReaffirmed 10 October 2001Approved 10 December 1996IEEE Standards BoardAbstract: Surge-protective devices designed for application on the low-voltage ac supply mains (1000 Vrms and less, frequency between 48 Hz and 62 Hz) are covered.Keywords: low voltage, secondary arresters, surge-p
3、rotective devicesThe Institute of Electrical and Electronics Engineers, Inc.345 East 47th Street, New York, NY 10017-2394, USACopyright 1997 by the Institute of Electrical and Electronics Engineers, Inc.All rights reserved. Published 1997. Printed in the United States of America.ISBN 1-55937-874-3No
4、 part of this publication may be reproduced in any form, in an electronic retrieval system or otherwise, without theprior written permission of the publisher.IEEE Standardsdocuments are developed within the IEEE Societies and the Standards Coordinat-ing Committees of the IEEE Standards Board. Member
5、s of the committees serve voluntarily andwithout compensation. They are not necessarily members of the Institute. The standards developedwithin IEEE represent a consensus of the broad expertise on the subject within the Institute as wellas those activities outside of IEEE that have expressed an inte
6、rest in participating in the develop-ment of the standard.Use of an IEEE Standard is wholly voluntary. The existence of an IEEE Standard does not implythat there are no other ways to produce, test, measure, purchase, market, or provide other goods andservices related to the scope of the IEEE Standar
7、d. Furthermore, the viewpoint expressed at thetime a standard is approved and issued is subject to change brought about through developments inthe state of the art and comments received from users of the standard. Every IEEE Standard is sub-jected to review at least every five years for revision or
8、reaffirmation. When a document is morethan five years old and has not been reaffirmed, it is reasonable to conclude that its contents,although still of some value, do not wholly reflect the present state of the art. Users are cautioned tocheck to determine that they have the latest edition of any IE
9、EE Standard.Comments for revision of IEEE Standards are welcome from any interested party, regardless ofmembership affiliation with IEEE. Suggestions for changes in documents should be in the form of aproposed change of text, together with appropriate supporting comments.Interpretations: Occasionall
10、y questions may arise regarding the meaning of portions of standards asthey relate to specific applications. When the need for interpretations is brought to the attention ofIEEE, the Institute will initiate action to prepare appropriate responses. Since IEEE Standards rep-resent a consensus of all c
11、oncerned interests, it is important to ensure that any interpretation hasalso received the concurrence of a balance of interests. For this reason, IEEE and the members of itssocieties and Standards Coordinating Committees are not able to provide an instant response tointerpretation requests except i
12、n those cases where the matter has previously received formalconsideration. Comments on standards and requests for interpretations should be addressed to:Secretary, IEEE Standards Board445 Hoes LaneP.O. Box 1331Piscataway, NJ 08855-1331USAAuthorization to photocopy portions of any individual standar
13、d for internal or personal use isgranted by the Institute of Electrical and Electronics Engineers, Inc., provided that the appropriatefee is paid to Copyright Clearance Center. To arrange for payment of licensing fee, please contactCopyright Clearance Center, Customer Service, 222 Rosewood Drive, Da
14、nvers, MA 01923 USA;(508) 750-8400. Permission to photocopy portions of any individual standard for educational class-room use can also be obtained through the Copyright Clearance Center.Note: Attention is called to the possibility that implementation of this standard mayrequire use of subject matte
15、r covered by patent rights. By publication of this standard,no position is taken with respect to the existence or validity of any patent rights inconnection therewith. The IEEE shall not be responsible for identifying all patents forwhich a license may be required by an IEEE standard or for conducti
16、ng inquiries intothe legal validity or scope of those patents that are brought to its attention.iiiIntroductionThis introduction is not a part of IEEE Std C62.34-1996, IEEE Standard for Performance of Low-Voltage Surge-Protec-tive Devices (Secondary Arresters).Secondary arresters have been used sinc
17、e 1940 to protect the secondary winding of distribution transform-ers, kilowatt hour meters, and power equipment loads downstream from breakdown of insulation duringlightning strikes. Performance criteria for secondary arresters are included in standards for performance ofhigh-voltage arresters in I
18、EEE Std C62.1-1989 and IEEE Std C62.11-1993.With the proliferation of electronic equipment installed inside buildings, the emphasis has shifted away fromprotection of insulation on wiring devices to vulnerable electronic equipment.The standards developers have attempted, as far as possible, to harmo
19、nize with relevant internationalstandards.The Accredited Standards Committee on Surge Arresters, C62, that reviewed and approved this standard,had the following members at the time of approval:Joseph L. Koepfinger, ChairJohn A. Gauthier, SecretaryOrganization Represented Name of RepresentativeAssoci
20、ation of American Railroads .Wayne EtterBonneville Power Administration G. E. LeeCanadian Standards Association. D. M. SmithElectric Light and Power. J. W. WilsonR. A. JonesW. A. MaguireG. N. Miller(Alt.)T. A. WolfeInstitute of Electrical and Electronics Engineers.J. L. KoepfingerJ. J. BurkeG. L. Ga
21、ibroisW. H. KappRichard OdenbergKeith StumpEdgar Taylor (Alt.)Members-at-Large J. OsterhoutB. PensarSteven G. WhisenantNational Electrical Manufacturers Association .Dennis W. LenkLarry Bock (Alt.)Andi HaaPaul JeffriesHans SteinhoffJonathan J. WoodworthRural Electrification Administration.(vacant)Un
22、derwriters Laboratories . George MauroivAt the time this standard was completed, the Working Group on Performance of Low-Voltage Surge-Protec-tive Devices (Secondary Arresters) had the following membership:Joe Osterhout,Chair Other individuals who have contributed written review and comments are the
23、 following:The following persons were on the balloting committee:When the IEEE Standards Board approved this standard on 10 December 1996, it had the followingmembership:Donald C. Loughry,ChairRichard J. Holleman,Vice ChairAndrew G. Salem,Secretary*Member EmeritusAlso included are the following nonv
24、oting IEEE Standards Board liaisons:Satish K. AggarwalAlan H. CooksonChester C. TaylorRochelle L. SternIEEE Standards Project EditorEd FoelkerGary GoeddeJeff MackevichFrancois MartzloffGeorge MauroKurt MeindorferHans SteinhoffMike StringfellowJonathan WoodworthChris ChrysanthouJ. David ClaytonFranci
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIIEEEC62341996STANDARDFORPERFORMANCEOFLOWVOLTAGESURGEPROTECTIVEDEVICESSECONDARYARRESTERS 压电 保护 设备

链接地址:http://www.mydoc123.com/p-1242481.html