1、12-05M 27 05 33 - 1 SECTION 27 05 33 RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS SPEC WRITER NOTE: Delete between /-/if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION A. This section spe
2、cifies the furnishing, installation, and connection of conduit, fittings, and boxes to form complete, coordinated, raceway systems. Raceways are required for all communications cabling unless shown or specified otherwise. B. Definitions: The term conduit, as used in this specification, shall mean an
3、y or all of the raceway types specified. 1.2 RELATED WORK A. Bedding of conduits: Section 31 20 00, EARTH MOVING. B. Mounting board for communication closets: Section 06 10 00, ROUGH CARPENTRY. C. Sealing around penetrations to maintain the integrity of fire rated construction: Section 07 84 00, FIR
4、ESTOPPING. D. Fabrications for the deflection of water away from the building envelope at penetrations: Section 07 60 00, FLASHING AND SHEET METAL. E. Sealing around conduit penetrations through the building envelope to prevent moisture migration into the building: Section 07 92 00, JOINT SEALANTS.
5、F. Identification and painting of conduit and other devices: Section 09 91 00, PAINTING. G. General electrical requirements and items that is common to more than one section of Division 27: Section 27 05 11, REQUIREMENTS FOR COMMUNICATIONS INSTALLATIONS. H. Requirements for personnel safety and to p
6、rovide a low impedance path for possible ground fault currents: Section 27 05 26, GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS. 1.3 SUBMITTALS In accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES, furnish the following: A. Shop Drawings: 1. Size and location of panels an
7、d pull boxes 2. Layout of required conduit penetrations through structural elements. 3. The specific item proposed and its area of application shall be identified on the catalog cuts. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-12-05M 27 05 33 -
8、2 B. Certification: Prior to final inspection, deliver to the / Resident Engineer / COTR / four copies of the certification that the material is in accordance with the drawings and specifications and has been properly installed. 1.4 APPLICABLE PUBLICATIONS A. Publications listed below (including ame
9、ndments, addenda, revisions, supplements and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by the basic designation only. B. National Fire Protection Association (NFPA): 70-05 National Electrical Code (NEC) C. Underwriters Laboratories, I
10、nc. (UL): 1-03. Flexible Metal Conduit 5-01. Surface Metal Raceway and Fittings 6-03. Rigid Metal Conduit 50-03 Enclosures for Electrical Equipment 360-03. Liquid-Tight Flexible Steel Conduit 467-01. Grounding and Bonding Equipment 514A-01 Metallic Outlet Boxes 514B-02 Fittings for Cable and Conduit
11、 514C-05 Nonmetallic Outlet Boxes, Flush-Device Boxes and Covers 651-02. Schedule 40 and 80 Rigid PVC Conduit 651A-03 Type EB and A Rigid PVC Conduit and HDPE Conduit 797-03. Electrical Metallic Tubing 1242-00 Intermediate Metal Conduit D. National Electrical Manufacturers Association (NEMA): TC-3-0
12、4 PVC Fittings for Use with Rigid PVC Conduit and Tubing FB1-03. Fittings, Cast Metal Boxes and Conduit Bodies for Conduit, Electrical Metallic Tubing and Cable PART 2 - PRODUCTS 2.1 MATERIAL SPEC WRITER NOTE: Coordinate with Section 27 10 00, STRUCTURED CABLING to insure that type THW insulation is
13、 not specified for use in 13 mm (1/2 inch) conduit. A. Conduit Size: In accordance with the NEC, but not less than 13 mm (1/2 inch) unless otherwise shown. Where permitted by the NEC, 13 mm Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-12-05M 27 05
14、 33 - 3 (1/2 inch) flexible conduit may be used for tap connections to recessed lighting fixtures. B. Conduit: 1. Rigid galvanized steel: Shall Conform to UL 6, ANSI C80.1. 2. Rigid aluminum: Shall Conform to UL 6A, ANSI C80.5. 3. Rigid intermediate steel conduit (IMC): Shall Conform to UL 1242, ANS
15、I C80.6. 4. Electrical metallic tubing (EMT): Shall Conform to UL 797, ANSI C80.3. Maximum size not to exceed 105 mm (4 inch) and shall be permitted only with cable rated 600 volts or less. 5. Flexible galvanized steel conduit: Shall Conform to UL 1. 6. Liquid-tight flexible metal conduit: Shall Con
16、form to UL 360. 7. Direct burial plastic conduit: Shall conform to UL 651 and UL 651A, heavy wall PVC or high density polyethylene (PE). 8. Surface metal raceway: Shall Conform to UL 5. C. Conduit Fittings: 1. Rigid steel and IMC conduit fittings: a. Fittings shall meet the requirements of UL 514B a
17、nd ANSI/ NEMA FB1. a. Standard threaded couplings, locknuts, bushings, and elbows: Only steel or malleable iron materials are acceptable. Integral retractable type IMC couplings are also acceptable. b. Locknuts: Bonding type with sharp edges for digging into the metal wall of an enclosure. c. Bushin
18、gs: Metallic insulating type, consisting of an insulating insert molded or locked into the metallic body of the fitting. Bushings made entirely of metal or nonmetallic material are not permitted. d. Erickson (union-type) and set screw type couplings: Approved for use in concrete are permitted for us
19、e to complete a conduit run where conduit is installed in concrete. Use set screws of case hardened steel with hex head and cup point to firmly seat in conduit wall for positive ground. Tightening of set screws with pliers is prohibited. e. Sealing fittings: Threaded cast iron type. Use continuous d
20、rain type sealing fittings to prevent passage of water vapor. In concealed work, install fittings in flush steel boxes with blank cover plates having the same finishes as that of other electrical plates in the room. Provided by IHSNot for ResaleNo reproduction or networking permitted without license
21、 from IHS-,-,-12-05M 27 05 33 - 4 2. Rigid aluminum conduit fittings: a. Standard threaded couplings, locknuts, bushings, and elbows: Malleable iron, steel or aluminum alloy materials; Zinc or cadmium plate iron or steel fittings. Aluminum fittings containing more than 0.4 percent copper are prohibi
22、ted. b. Locknuts and bushings: As specified for rigid steel and IMC conduit. c. Set screw fittings: Not permitted for use with aluminum conduit. 3. Electrical metallic tubing fittings: a. Fittings shall meet the requirements of UL 514B and ANSI/ NEMA FB1. b. Only steel or malleable iron materials ar
23、e acceptable. c. Couplings and connectors: Concrete tight and rain tight, with connectors having insulated throats. Use gland and ring compression type couplings and connectors for conduit sizes 50 mm (2 inches) and smaller. Use set screw type couplings with four set screws each for conduit sizes ov
24、er 50 mm (2 inches). Use set screws of case-hardened steel with hex head and cup point to firmly seat in wall of conduit for positive grounding. d. Indent type connectors or couplings are prohibited. e. Die-cast or pressure-cast zinc-alloy fittings or fittings made of “pot metal“ are prohibited. 4.
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2705332005RACEWAYSANDBOXESFORCOMMUNICATIONSSYSTEMSPDF

链接地址:http://www.mydoc123.com/p-1074981.html