VA 26 56 00-2010 EXTERIOR LIGHTING.pdf
《VA 26 56 00-2010 EXTERIOR LIGHTING.pdf》由会员分享,可在线阅读,更多相关《VA 26 56 00-2010 EXTERIOR LIGHTING.pdf(13页珍藏版)》请在麦多课文档分享上搜索。
1、09-10 26 56 00 - 1 SECTION 26 56 00 EXTERIOR LIGHTING SPEC WRITER NOTE: Delete between / _ / if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. Use this section for low voltage parallel-type systems and medium-voltage seri
2、es-type systems. PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of exterior luminaires, poles, and supports. 1.2 RELATED WORK A. Section 09 06 00, SCHEDULE FOR FINISHES: Finishes for exterior light poles and luminaires. B. Section 26 05 11, REQUI
3、REMENTS FOR ELECTRICAL INSTALLATIONS: General electrical requirements and items that are common to more than one section of Division 26. /C. Section 26 05 13, MEDIUM-VOLTAGE CABLES: Medium voltage cables for series-connected street lighting. / D. Section 26 05 21, LOW-VOLTAGE ELECTRICAL POWER CONDUC
4、TORS AND CABLES (600 VOLTS AND BELOW): Low voltage power and lighting wiring. E. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS: Requirements for personnel safety and to provide a low impedance path for possible ground fault currents. F. Section 26 05 33, RACEWAY AND BOXES FOR ELECTR
5、ICAL SYSTEMS: Conduits, fittings, and boxes for raceway systems. G. Section 26 05 41, UNDERGROUND ELECTRICAL CONSTRUCTION: Underground handholes and conduits. H. Section 26 09 23, LIGHTING CONTROLS: Controls for exterior lighting. 1.3 QUALITY ASSURANCE Refer to Paragraph, QUALIFICATIONS, in Section
6、26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. 1.4 SUBMITTALS A. Submit in accordance with Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. B. Shop Drawings: Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 56 00 - 2 1. Clea
7、rly present sufficient information to determine compliance with drawings and specifications. SPEC WRITER NOTE: Edit paragraph below to conform to project requirements. 2. Include electrical ratings, dimensions, mounting, details, materials, required clearances, terminations, wiring and connection di
8、agrams, photometric data, ballasts, poles, luminaires, lamps, and accessories. / Include electronic photometric files in IES format, or provide link (URL) to manufacturers website that contains photometric data for each specific fixture used, excluding wallpack fixtures./ C. Manuals: Two weeks prior
9、 to final inspection, submit four copies of operating and maintenance manuals to the /Resident Engineer/ /COTR/. Include technical data sheets, wiring and connection diagrams, and information for ordering replacement lamps, ballasts, and parts. D. Certifications: Two weeks prior to final inspection,
10、 submit four copies of the following to the /Resident Engineer/ /COTR/: 1. Certification by the manufacturer that the materials are in accordance with the drawings and specifications. 2. Certification by the contractor that the complete installation has been properly installed and tested. 1.5 APPLIC
11、ABLE PUBLICATIONS A. Publications listed below (including amendments, addenda, revisions, supplements, and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by designation only. B. Aluminum Association Inc. (AA): AAH35.1-06 . Alloy and Temper
12、 Designation Systems for Aluminum C. American Association of State Highway and Transportation Officials (AASHTO): LTS-5-09 Structural Supports for Highway Signs, Luminaires and Traffic Signals D. American Concrete Institute (ACI): 318-05 Building Code Requirements for Structural Concrete E. American
13、 National Standards Institute (ANSI): Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 56 00 - 3 C81.61-09 . Electrical Lamp Bases Specifications for Bases (Caps) for Electric Lamps F. American Society for Testing and Materials (ASTM): A123/A
14、123M-09 . Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products A153/A153M-09 Zinc Coating (Hot-Dip) on Iron and Steel Hardware B108-03a-08 . Aluminum-Alloy Permanent Mold Castings C1089-06 Spun Cast Prestressed Concrete Poles G. Federal Aviation Administration (FAA): AC 70/7460-IK-07 . Obst
15、ruction Lighting and Marking AC 150/5345-43F-06 . Obstruction Lighting Equipment H. Illuminating Engineering Society of North America (IESNA) HB-9-00 Lighting Handbook RP-8-05 Roadway Lighting RP-20-98 . Lighting for Parking Facilities RP-33-99 . Lighting for Exterior Environments LM-5-96 Photometri
16、c Measurements of Area and Sports Lighting Installations LM-50-99 . Photometric Measurements of Roadway Lighting Installations LM-52-99 . Photometric Measurements of Roadway Sign Installations LM-64-01 . Photometric Measurements of Parking Areas LM-72-97 . Directional Positioning of Photometric Data
17、 LM-79-08 . Approved Method for the Electrical and Photometric Measurements of Solid-Sate Lighting Products LM-80-08 . Approved Method for Measuring Lumen Maintenance of LED Light Sources I. National Electrical Manufacturers Association (NEMA): C78.41-06 Electric Lamps Guidelines for Low-Pressure So
18、dium Lamps C78.42-07 . Electric Lamps Guidelines for High-Pressure Sodium Lamps C78.43-07 . Electric Lamps Single-Ended Metal-Halide Lamps Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 56 00 - 4 C78.1381-98 Electric Lamps 70-Watt M85 Doubl
19、e-Ended Metal-Halide Lamps C82.4-02 Ballasts for High-Intensity-Discharge and Low-Pressure Sodium Lamps (Multiple-Supply Type) C136.3-05 . For Roadway and Area Lighting Equipment Luminaire Attachments C136.17-05 . Roadway and Area Lighting Equipment Enclosed Side-Mounted Luminaires for Horizontal-Bu
20、rning High-Intensity-Discharge Lamps Mechanical Interchangeability of Refractors ICS 2-00 (R2005) Controllers, Contactors and Overload Relays Rated 600 Volts ICS 6-93 (R2006) Enclosures J. National Fire Protection Association (NFPA): 70-08 . National Electrical Code (NEC) K. Underwriters Laboratorie
21、s, Inc. (UL): 496-08 Lampholders 773-95 . Plug-In, Locking Type Photocontrols for Use with Area Lighting 773A-06 . Nonindustrial Photoelectric Switches for Lighting Control 1029-94 High-Intensity-Discharge Lamp Ballasts 1598-08 . Luminaires 8750-08.Light Emitting Diode (LED) Light Sources for Use in
22、 Lighting Products 1.6 DELIVERY, STORAGE, AND HANDLING Provide manufacturers standard provisions for protecting pole finishes during transport, storage, and installation. Do not store poles on ground. Store poles so they are at least 12 in 305 mm above ground level and growing vegetation. Do not rem
23、ove factory-applied pole wrappings until just before installing pole. PART 2 - PRODUCTS SPEC WRITER NOTE: Ensure that material requirements agree with applicable requirements specified in the referenced Applicable Publications. Update and specify only that which applies to the project. Provided by I
24、HSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 56 00 - 5 2.1 MATERIALS AND EQUIPMENT Materials and equipment shall be in accordance with NEC, UL, ANSI, and as shown on the drawings and specified. 2.2 POLES A. General: 1. Poles shall be as shown on the d
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2656002010EXTERIORLIGHTINGPDF