VA 26 43 13-2009 TRANSIENT-VOLTAGE SURGE SUPPRESSION.pdf
《VA 26 43 13-2009 TRANSIENT-VOLTAGE SURGE SUPPRESSION.pdf》由会员分享,可在线阅读,更多相关《VA 26 43 13-2009 TRANSIENT-VOLTAGE SURGE SUPPRESSION.pdf(5页珍藏版)》请在麦多课文档分享上搜索。
1、4-09 26 43 13-1 SECTION 26 43 13 TRANSIENT-VOLTAGE SURGE SUPPRESSION SPEC WRITER NOTE: Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable to the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION Section includes transient volta
2、ge surge suppression equipment for low-voltage power distribution and control equipment. 1.2 RELATED WORK A. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General requirements that are common to more than one section of Division 26. B. Section 26 23 00, LOW-VOLTAGE SWITCHGEAR: For fac
3、tory-installed TVSS. C. Section 26 24 11, DISTRIBUTION SWITCHBOARDS: For factory-installed TVSS. D. Section 26 24 16, PANELBOARDS: For factory-installed TVSS. E. Section 26 26 00, POWER DISTRIBUTION UNITS FOR UNINTERRUPTIBLE POWER SYSTEMS: For factory-installed TVSS. 1.3 QUALITY ASSURANCE Refer to P
4、aragraph, QUALIFICATIONS, in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. 1.4 SUBMITTALS A. Include rated capacities, operating weights, electrical characteristics, furnished specialties, and accessories. B. Operation and Maintenance Data: For TVSS devices to include in emergency, op
5、eration, and maintenance manuals. C. Warranties: Sample of special warranties. D. Certifications: 1. Two weeks prior to final inspection, submit four copies of the following to the Resident Engineer: a. Certification by the Contractor that the assemblies have been properly installed, adjusted and te
6、sted.3. b. Certified copies of all of the factory design and production tests, field test data sheets and reports for the assemblies. 1.5 APPLICABLE PUBLICATIONS Publications listed below (including amendments, addenda, revisions, supplement and errata) form a part of this specification to the exten
7、t Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-4-09 26 43 13-2 referenced. Publications are referenced in the text by the basic designation only. A. Institute of Engineering and Electronic Engineers (IEEE): IEEE C62.41.2 Recommended Practice on Ch
8、aracterization of Surges in Low-Voltage (1000 V and Less) AC Power Circuits IEEE C62.45 Recommended Practice on Surge Testing for Equipment Connected to Low-Voltage (1000 V and Less) AC Power Circuits B. National Electrical Manufacturers Association (NEMA): NEMA LS 1 Low Voltage Surge Protective Dev
9、ices C. Underwriters Laboratories, Inc. (UL): UL 1283 Electromagnetic Interference Filters UL 1449Surge Protective Devices D. National Fire Protection Association (NFPA): NFPA 70 National Electrical Code (NEC) PART 2 - PRODUCTS 2.1 SWITCHGEAR/SWITCHBOARD SUPPRESSORS A. Surge Protection Devices: 1. C
10、omply with UL 1449. /2. Modular design with field-replaceable modules/Non-modular design/. 3. Fuses, rated at 200-kA interrupting capacity. 4. Fabrication using bolted compression lugs for internal wiring. 5. Integral disconnect switch. 6. Redundant suppression circuits. 7. Redundant replaceable mod
11、ules. 8. Arrangement with copper bus bars and for bolted connections to phase buses, neutral bus, and ground bus. 9. Arrangement with wire connections to phase buses, neutral bus, and ground bus. 10. LED indicator lights for power and protection status. 11. Audible alarm, with silencing switch, to i
12、ndicate when protection has failed. 12. Form-C contacts rated at 5 A and 250-V ac, one normally open and one normally closed, for remote monitoring of protection status. Contacts shall reverse on failure of any surge diversion module or Provided by IHSNot for ResaleNo reproduction or networking perm
13、itted without license from IHS-,-,-4-09 26 43 13-3 on opening of any current-limiting device. Coordinate with building power monitoring and control system. 13. Four-digit transient-event counter set to totalize transient surges. B. Peak Single-Impulse Surge Current Rating: /320 kA per mode/640 kA/ /
14、240 kA per mode/480 kA/ /160 kA per mode/320 kA/ per phase. C. Minimum single impulse current ratings, using 8-by-20-mic.sec waveform described in IEEE C62.41.2 1. Line to Neutral: /70,000/ /Insert value/ A. 2. Line to Ground: /70,000/ /Insert value/ A. 3. Neutral to Ground: /50,000/ /Insert value/
15、A. D. Protection modes and UL 1449 SVR for grounded wye circuits shall be as follows: 1. Line to Neutral: 800 V for 480Y/277 V, 400 V for 208Y/120 V. 2. Line to Ground: 800 V for 480Y/277 V, 400 V for 208Y/120 V. 3. Neutral to Ground: 800 V for 480Y/277 V, 400 V for 208Y/120 V. E. Protection modes a
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2643132009TRANSIENTVOLTAGESURGESUPPRESSIONPDF

链接地址:http://www.mydoc123.com/p-1074975.html