1、09-10 26 18 41 - 1 SECTION 26 18 41 MEDIUM-VOLTAGE SWITCHES SPEC WRITER NOTE: Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable to the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, in
2、stallation and connection of medium voltage switches. 1.2 RELATED WORK A. Section 09 06 00, SCHEDULE FOR FINISHES: Switch finishes. /B. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS: Requirement for seismic restraint for nonstructural Components./ /C. Section 25 10 1
3、0, ADVANCED UTILITY METERING: Electricity meters installed in medium voltage switches./ D. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General electrical requirements that are common to more that one section of Division 26. E. Section 26 05 13, MEDIUM-VOLTAGE CABLES: Medium voltage
4、cables and splices. F. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS: Requirements for personnel safety and to provide a low impedance path to ground for possible ground fault currents. G. Section 26 05 71, ELECTRICAL SYSTEM PROTECTIVE DEVICE STUDY: Short circuit and coordination st
5、udy. 1.3 QUALITY ASSURANCE Refer to Paragraph, QUALIFICATIONS, in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. 1.4 FACTORY TESTS A. Medium voltage switches shall be thoroughly tested at the factory to assure that there are no electrical or mechanical defects. Tests shall be conducted
6、 as per UL and ANSI Standards. Factory tests shall be certified. The following tests shall be performed: 1. Verify that fuse sizes and types are in accordance with drawings and coordination study. 2. Verify tightness of bolted electrical connections by calibrated torque-wrench method in accordance w
7、ith manufacturers published data. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 18 41 - 2 3. Verify operation and sequencing of interlocking systems. 4. Verify correct phase barrier installation. 5. Verify correct operation of all indicati
8、ng and control devices. 6. Verify appropriate lubrication on moving current-carrying parts and on moving and sliding surfaces. 7. Exercise all active components. 8. Perform insulation-resistance tests on each pole, phase-to-phase and phase-to-ground with switch closed, and across each open pole. App
9、ly voltage in accordance with manufacturers published data. 9. Perform a dielectric withstand voltage test on each pole with switch closed. Test each pole-to-ground with all other poles grounded. Test voltage shall be in accordance with manufacturers published data. B. Furnish four (4) copies of cer
10、tified manufacturers factory test reports to the Resident Engineer prior to shipment of the switches to ensure that the switches have been successfully tested as specified. /C. The Government shall have an option to witness the factory tests. All expenses of the Government Representatives trips to w
11、itness the testing will be paid by the Government. Notify the Resident Engineer not less than 30 days prior to making tests at the factory./ 1.5 SUBMITTALS A. In accordance with Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, submit the following: B. Shop Drawings: 1. Provide detailed d
12、rawings with sufficient information, clearly presented, to determine compliance with drawings and specifications. 2. Provide information such as complete electrical ratings, dimensions and approximate design weights, mounting details, materials, required clearances, cable terminations, fuse sizes an
13、d class, interrupting ratings, wiring and connection diagrams, front, side and rear elevations, sectional views, safety features, accessories and nameplate data. C. Manuals: 1. Submit, simultaneously with the shop drawings, companion copies of complete maintenance and operating manuals including tec
14、hnical data sheets, wiring diagrams and information for ordering replacement parts. 2. Two weeks prior to the project final inspection, submit four copies of the final updated maintenance and operating manuals to the Resident Engineer. (Update the manuals to include any revisions necessitated by sho
15、p drawing approval). Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 18 41 - 3 D. Certification: Two weeks prior to final inspection, submit four copies of the following to the /Resident Engineer/ /COTR/: SPEC WRITER NOTE: Refer to VA Handbo
16、ok H-18-8 for Seismic Design Requirements. Specify Region of Seismicity, based on location of the equipment so motor control center manufacturers can check/design seismic strength of their equipment. Delete the following paragraph if the motor control center(s) is located outside the seismic zone. /
17、1. Certification from the manufacturer that the switches will withstand the seismic forces and that the unit will be fully operational after the seismic event at the project site./ 2. Certification by the manufacturer that the materials conform to the requirements of the drawings and specifications.
18、 3. Certification by the Contractor that the materials have been properly installed, adjusted, and tested. 1.6 APPLICABLE PUBLICATIONS A. Publications listed below (including amendments, addenda, revisions, supplements, and errata) form a part of this specification to the extent referenced. Publicat
19、ions are referenced in the text by designation only. B. American National Standards Institute (ANSI): C37.47 . Medium voltage Current-Limiting Type Distribution Class Fuses and Fuse Disconnect Switches C37.58 . Conformance Test Procedures for Indoor AC Medium-Voltage Switches for Use in Metal-Enclos
20、ed Switchgear C. Institute of Electrical and Electronics Engineers (IEEE): C37.20.3 . Metal-Enclosed Interrupter Switchgear C37.48 . Guide for Application, Operation and Maintenance of Medium voltage Fuses, Distribution Enclosed Single Pole Air Switches, Fuse Disconnecting Switches and Accessories D
21、. National Electrical Manufacturers Association (NEMA): C37.22 . Preferred Ratings and Required Capabilities for Indoor AC Medium-Voltage Switches Used in Metal-Enclosed Switchgear SG 6 . Power Switching Equipment E. National Fire Protection Association (NFPA): 70 . National Electrical Code (NEC) Pr
22、ovided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 18 41 - 4 PART 2 - PRODUCTS 2.1 MEDIUM VOLTAGE AIR BREAK SWITCHES A. Shall be in accordance with ANSI, IEEE, NEMA, NFPA, as shown on the drawings and have the following features: 1. Deadfront air
23、 break, three-pole gang-operated, rated load interrupter type, with manual stored energy operator. 2. Copper blades. 3. A separate door for the fuse section. A mechanical interlock shall prevent opening the door unless the switch blades are open, and prevent closing the switch if the door is open. 4
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2618412010MEDIUMVOLTAGESWITCHESPDF