1、09-10 26 12 19 - 1 SECTION 26 12 19 PAD-MOUNTED, LIQUID-FILLED, MEDIUM-VOLTAGE TRANSFORMERS SPEC WRITER NOTE: Delete between /-/ if not applicable to project. This spec is applicable for transformers 2500 kVA and less on 5 kV and 15 kV systems, with source not over 8.3 kV phase-to ground. PART 1 - G
2、ENERAL 1.1 DESCRIPTION A. This section specifies the furnishing, installation, and connection of pad-mounted transformers. B. Pad-mounted transformers shall be complete, outdoor type, continuous duty, integral assembly, grounded, tamper-resistant, and weatherproof, with liquid-immersed transformers.
3、 1.2 RELATED WORK A. Section 09 06 00, SCHEDULE FOR FINISHES: Finishes for electrical equipment. /B. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS: Requirements for seismic restraint of non-structural components./ C. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INST
4、ALLATIONS: General electrical requirements that are common to more than one section of Division 26. D. Section 26 05 13, MEDIUM-VOLTAGE CABLES: Medium-voltage cables. E. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS: Requirements for personnel safety and to provide a low impedance p
5、ath to ground for possible ground currents. F. Section 26 05 41, UNDERGROUND ELECTRICAL CONSTRUCTION: Manholes, pull-boxes, and duct lines for underground raceway systems. G. Section 26 05 71, ELECTRICAL SYSTEM PROTECTIVE DEVICE STUDY: Short-circuit and coordination study. 1.3 QUALITY ASSURANCE Refe
6、r to Paragraph, QUALIFICATIONS, in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. 1.4 FACTORY TESTS Transformers shall be thoroughly tested at the factory to ensure that there are no electrical or mechanical defects. Tests shall be conducted as per UL and ANSI Standards. Factory tests
7、shall be certified. The following tests shall be performed: 1. Perform insulation-resistance tests, winding-to-winding and each winding-to-ground. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 12 19 - 2 2. Perform turns-ratio tests at all
8、tap positions. 1.5 SUBMITTALS A. In accordance with Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, submit the following: B. Shop Drawings: 1. Clearly present sufficient information to determine compliance with drawings and specifications. 2. Include electrical ratings, nameplate data,
9、impedance, outline drawing with dimensions and front, top, and side views, weight, mounting details, decibel rating, termination information, temperature rise, no-load and full-load losses, regulation, overcurrent protection, connection diagrams, and accessories. 3. Complete nameplate data, includin
10、g manufacturers name and catalog number. C. Manuals: 1. When submitting the shop drawings, submit companion copies of complete maintenance and operating manuals, including technical data sheets, wiring diagrams, and information for ordering replacement parts. a. Identify terminals on wiring diagrams
11、 to facilitate installation, maintenance, and operation. b. Indicate on wiring diagrams the internal wiring for each piece of equipment and interconnections between the pieces of equipment. c. Approvals will be based on complete submissions of manuals, together with shop drawings. 2. Two weeks prior
12、 to the final inspection, submit four copies of the final up-dated maintenance and operation manuals to the /Resident Engineer/ /COTR/. a. Update the manual to include any information necessitated by shop drawing approval. b. Show all terminal identification. c. Include information for testing, repa
13、ir, trouble-shooting, assembly, disassembly, and recommended maintenance intervals. d. Provide a replacement parts list with current prices. Include a list of recommended spare parts, tools, and instruments for testing and maintenance purposes. e. Furnish manuals in loose-leaf binder or manufacturer
14、s standard binder. D. Certifications: Two weeks prior to the final inspection, submit four copies of the following certifications to the /Resident Engineer/ /COTR/: Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 12 19 - 3 1. Certification b
15、y the manufacturer that the materials conform to the requirements of the drawings and specifications. 2. Certification by the contractor that the materials have been properly installed, connected, and tested. 1.6 APPLICABLE PUBLICATIONS A. Publications listed below (including amendments, addenda, re
16、visions, supplements, and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by designation only. B. American Concrete Institute (ACI): 318-05 . Building Code Requirements for Structural Concrete C. American National Standards Institute (ANSI)
17、: C37.47-00 High Voltage Current-Limiting Type Distribution Class Fuses and Fuse Disconnecting Switches C57.12.00-00 . General Requirements for Liquid-Immersed Distribution, Power and Regulating Transformers C57.12.25-90 . Transformers-Pad-Mounted, Compartmental-Type, Self Cooled, Single-Phase Distr
18、ibution Transformers with Separable Insulated High Voltage Connectors; High Voltage, 34500 Grd Y/19920 Volts and Below; Low-Voltage 240/120 Volts; 167 kVA and Smaller Requirements C57.12.28-05 . Pad-Mounted Equipment Enclosure Integrity C57.12.29-99 . Pad-Mounted Equipment Enclosure Integrity for Co
19、astal Environments C57.12.34-04 . Pad-Mounted, Compartmental-Type, Self Cooled, Three-Phase Distribution Transformers, 2500kVA and Smaller High Voltage 34500 Grd Y/19920 Volts and Below; Low-Voltage 480 Volts and Below D. American Society for Testing and Materials (ASTM): D3487-08 . Standard Specifi
20、cation for Mineral Insulating Oil Used in Electrical Apparatus E. Institute of Electrical and Electronic Engineers (IEEE): C2-07 National Electrical Safety Code C62.11-99 Metal-Oxide Surge Arresters for Alternating Current Power Circuits 48-09 Test Procedures and Requirements for Alternating Current
21、 Cable Terminations Used on Shielded Cables Having Laminated Insulation Rated 2.5kV Through 765kV or Extruded Insulation Rated 2.5kV Through 500kV Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 12 19 - 4 386-06 . Standard for Separable Insu
22、lated Connector Systems for Power Distribution Systems Above 600V 592-96 . Standard for Exposed Semiconducting Shields on High Voltage Cable Joints and Separable Insulated Connectors F. National Electrical Manufacturers Association (NEMA): C57.12.26-87 . Pad-Mounted, Compartmental-Type, Self-Cooled,
23、 Three-Phase Distribution Transformers for Use with Separable Insulated High-Voltage Connectors, High-Voltage, 34500 Grd Y/19920 Volts and Below; 2500 kVA and Smaller LA1-92 . Surge Arresters TP1-02 . Guide for Determining Energy Efficiency for Distribution Transformers TR1-00 . Transformers, Regula
24、tors, and Reactors G. National Fire Protection Association (NFPA): 70-08 National Electrical Code (NEC) H. Underwriters Laboratories Inc. (UL): 467-07 . Grounding and Bonding Equipment PART 2 - PRODUCTS 2.1 EQUIPMENT, GENERAL A. Equipment shall be in accordance with ANSI, ASTM, IEEE, NEMA, NFPA, UL,
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2612192010PADMOUNTEDLIQUIDFILLEDMEDIUMVOLTAGETRANSFORMERSPDF

链接地址:http://www.mydoc123.com/p-1074953.html