1、10-10 09 51 00 - 1 SECTION 09 51 00 ACOUSTICAL CEILINGS SPEC WRITER NOTE: 1. Delete between /_/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. 2. Coordinate with Section 09 06 00, SCHEDULE FOR FINISHESS, to define text
2、ure, patterns, and colors other than white with locations in the room finish schedule and reflective ceiling plans. 3. Fire rated assemblies: Do not use except with special authorization. Limit use to existing structures where other means to achieve desired fire rating are not practical. This sectio
3、n does not include fire rated assemblies, include applicable UL systems and specify when permitted. 4. Section does not include acoustical plaster, spray or trowel applications and special panels or tile units such as “Structural cement-fiber Units“ See UL listings; Units have flame spread of 20 and
4、 smoke developed of 0. 5. Do not use glass fiber units for lay-in ceiling applications. 6. Insure the reflective ceiling plans show panel sizes and layouts with unusual conditions and tile ceilings. PART 1- GENERAL 1.1 DESCRIPTION A. Metal ceiling suspension system for acoustical ceilings. B. Acoust
5、ical units. C. Adhesive application. 1.2 RELATED WORK A. Color, pattern, and location of each type of acoustical unit: Section 09 06 00, SCHEDULE FOR FINISHES. /B. Linear Metal Ceilings: Section 09 54 23, LINEAR METAL CEILINGS./ /C. Access doors in adhesive applied tile: Section 08 31 13, ACCESS DOO
6、RS AND FRAMES./ 1.3 SUBMITTAL A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-10-10 09 51 00 - 2 B. Samples: 1. Acoustical units, each type, with label indicatin
7、g conformance to specification requirements, / including units specified to match existing. / 2. Colored markers for units providing access. C. Manufacturers Literature and Data: 1. Ceiling suspension system, each type, showing complete details of installation /, including suspension system specifie
8、d to match existing and upward access system details for concealed grid systems. / 2. Acoustical units, each type /3. Runners designed for snap-in attachment of metal pans./ D. Manufacturers Certificates: Acoustical units, each type, in accordance with specification requirements. 1.4 DEFINITIONS A.
9、Standard definitions as defined in ASTM C634. B. Terminology as defined in ASTM E1264. SPEC WRITER NOTE: Make material requirements agree with applicable requirements specified in the referenced Applicable Publications. Update and specify only that which applies to the project. 1.5 APPLICABLE PUBLIC
10、ATIONS A. Publications listed below form a part of this specification to extent referenced. Publications are referenced in the text by basic designation only. B. American Society for Testing and Materials (ASTM): A641/A641M-03.Zinc-coated (Galvanized) Carbon Steel Wire A653/A653M-07.Steel Sheet, Zin
11、c-Coated (Galvanized) or Zinc-Iron Alloy-coated (Galvannealed) by the Hot-Dip Process C423-07.Sound Absorption and Sound Absorption Coefficients by the Reverberation Room Method C634-02 (E2007).Standard Terminology Relating to Environmental Acoustics C635-04.Metal Suspension Systems for Acoustical T
12、ile and Lay-in Panel Ceilings C636-06.Installation of Metal Ceiling Suspension Systems for Acoustical Tile and Lay-in Panels Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-10-10 09 51 00 - 3 E84-07Surface Burning Characteristics of Building Material
13、s E119-07.Fire Tests of Building Construction and Materials E413-04.Classification for Rating Sound Insulation. E580-06.Application of Ceiling Suspension Systems for Acoustical Tile and Lay-in Panels in Areas Requiring Seismic Restraint E1264-(R2005).Classification for Acoustical Ceiling Products PA
14、RT 2- PRODUCTS SPEC WRITER NOTE: 1. Make material requirements agree with applicable requirements specified in the referenced Applicable Publications. 2. Exposed grid for 600 mm X 1200 mm (2 by 4 feet) lay-in panels is preferred system for economy. 3. Do not use narrow exposed grid face suspension s
15、ystem for lay-in mineral base acoustical units. Minimum width is 22 mm (7/8) inch with 8 mm (5/16 inch) minimum bearing area for panel edge. No exceptions. 2.1 METAL SUSPENSION SYSTEM A. ASTM C635, heavy-duty system, except as otherwise specified. 1. Ceiling suspension system members may be fabricat
16、ed from either of the following unless specified otherwise. a. Galvanized cold-rolled steel, bonderized. b. Extruded aluminum. c. Fire resistant plastic (glass fiber) having a flame spread and smoke developed rating of not more than 25 when tested in accordance with ASTM E84. 2. Use same constructio
17、n for cross runners as main runners. Use of lighter-duty sections for cross runners is not acceptable. 3. Use aluminum suspension in kitchens and aluminum or fire resistant plastic in toilets adjacent to shower areas, hydrotherapy, and swimming pools. B. Exposed grid suspension system for support of
18、 lay-in panels: 1. Exposed grid width not less than 22 mm (7/8 inch) with not less than 8 mm (5/16 inch) panel bearing surface. 2. Fabricate wall molding and other special molding from the same material with same exposed width and finish as the exposed grid members. Provided by IHSNot for ResaleNo r
19、eproduction or networking permitted without license from IHS-,-,-10-10 09 51 00 - 4 3. On exposed metal surfaces apply baked-on enamel flat texture finish in color to match adjacent acoustical units unless specified otherwise in Section 09 06 00, SCHEDULE FOR FINISHES. C. Concealed grid suspension s
20、ystem for support of mineral base acoustical tile: 1. Concealed grid upward access suspension system to provide an initial opening of 300 mm by 600 mm (12 by 24 inches) and for removal of adjacent runners and tile without the use of special tools, and without damage to suspension system and acoustic
21、al tile. 2. Minimum flange width of 22 mm (7/8 inch) except for access hook and angle. 3. Minimum flange width of 11 mm (7/16 inch) for access hook and angle. D. Suspension system for support of Metal Type V, VI, and VII tiles: Concealed grid type having runners designed for the snap-in attachment o
22、f metal tile (pans). 2.2 PERIMETER SEAL A. Vinyl, polyethylene or polyurethane open cell sponge material having density of 1.3 plus or minus 10 percent, compression set less than 10 percent with pressure sensitive adhesive coating on one side. B. Thickness as required to fill voids between back of w
23、all molding and finish wall. C. Not less than 9 mm (3/8 inch) wide strip. 2.3 WIRE A. ASTM A641. B. For wire hangers: Minimum diameter 2.68 mm (0.1055 inch). C. For bracing wires: Minimum diameter 3.43 mm (0.1350 inch). 2.4 ANCHORS AND INSERTS A. Use anchors or inserts to support twice the loads imp
24、osed by hangers attached thereto. B. Hanger Inserts: 1. Fabricate inserts from steel, zinc-coated (galvanized after fabrication). 2. Nailing type option for wood forms: a. Upper portion designed for anchorage in concrete and positioning lower portion below surface of concrete approximately 25 mm (on
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA0951002010ACOUSTICALCEILINGSPDF