UL SUBJECT 98B-2015 Outline of Investigation for Enclosed and Dead-front Switches for use in Photovoltaic Systems (Issue 3)《在光伏发电系统中使用的封闭和无电面板开关的调查大纲 (议题3)》.pdf
《UL SUBJECT 98B-2015 Outline of Investigation for Enclosed and Dead-front Switches for use in Photovoltaic Systems (Issue 3)《在光伏发电系统中使用的封闭和无电面板开关的调查大纲 (议题3)》.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 98B-2015 Outline of Investigation for Enclosed and Dead-front Switches for use in Photovoltaic Systems (Issue 3)《在光伏发电系统中使用的封闭和无电面板开关的调查大纲 (议题3)》.pdf(26页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULFEBRUARY 4, 20151UL 98BOutline of Investigation for Enclosed and Dead-front Switches for use inPhotovoltaic SystemsIssue Number 3February 4, 2015Summary of TopicsThis is the third issue of the Ou
2、tline of Investigation for Enclosed andDead-Front Switches for Use in Photovoltaic Systems, Subject 98B. Theserequirements cover enclosed and dead-front switches rated up to 1500 Vdc, intended for use in dc photovoltaic (PV) systems and installed inaccordance with Article 690 of the National Electri
3、cal Code, ANSI/NFPA-70. These switches are intended for ambient conditions between minus 20to +50C.The following table lists the future effective dates with the correspondingreference.Future Effective Dates ReferencesDecember 31, 2019 Paragraphs 13.5, 13.6, 13.10, 13.12, 14.5, 22.1,23.3, 23.6, 23.12
4、 23.17, Sections 17, 20, and24 27.ULs Outlines of Investigation are copyrighted by UL. Neither a printed norelectronic copy of an Outline of Investigation should be altered in any way. All ofULs Outlines of Investigation and all copyrights, ownerships, and rights regardingthose Outlines of Investiga
5、tion shall remain the sole and exclusive property of UL.COPYRIGHT 2015 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULFEBRUARY 4, 2015UL 98B2No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER
6、REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .52 Components 53 Units of Measurement .64 Undated References 65 Glossary .6CONSTRUCTION6 General 67 Spacings .78 Wire Terminals .79 Bus Bars .810 Enclosure Doors .811 Fusing 912 Wiring and Bending Space 9PERFORMANCE13
7、 General .914 Heating Test .1115 Endurance Test 1216 Close-Open Test .1217 Short Circuit Withstand Test .1218 Electrically Tripped Switches .1318.1 General .1318.2 Heating test .1318.3 Endurance test for electrically tripped switches 1318.4 Contact opening test for electrically tripped switches .131
8、9 Mold Stress Relief Test 1420 Strength of Insulating Base and Support Test 1421 Wire Terminals for Other Class and Strand Configurations .14RATINGS22 General 14MARKINGS23 General 15ACCESSORIES24 Construction .1724.1 General .1724.2 Mounting 1724.3 Field wiring .1824.4 Strain relief 1824.5 Spacings
9、19FEBRUARY 4, 2015 UL 98B 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL24.6 Electrical tripping mechanism 1924.7 Overvoltage-trip release devices .2024.8 Electrical operators .2024.9 Alarm and auxiliary switches .2024.10 Alarm switches 202
10、5 PERFORMANCE .2025.1 General .2025.2 Electrical tripping mechanism 2125.3 (Reserved) 2125.4 Overvoltage-trip release devices .2125.5 Electrical operators .2325.6 Alarm and auxiliary switches .2326 Ratings 2527 Markings .26FEBRUARY 4, 2015UL 98B4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REP
11、RODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover open, enclosed and dead-front switches rated up to 1500 V dc, intendedfor use in dc photovoltaic (PV) systems and installed in accordance with Article 690 of the NationalElectrical Code, ANSI/NFPA-70.
12、These switches are intended for ambient conditions between minus 20to +50C.1.2 These requirements are intended to be used in conjunction with requirements in the Standard forEnclosed and Dead-Front Switches, UL 98, except as modified or supplemented by the followingrequirements.1.3 Unless otherwise
13、specified, when the term switch is used in this outline, it refers to a photovoltaic,enclosed, open, or dead-front switch.1.4 Fusible switches are intended for use with photovoltaic (PV) fuses which comply with therequirements of Outline for Low-Voltage Fuses Fuses for Photovoltaic Systems, UL 2579.
14、1.5 These requirements also apply to open type switches, used in conjunction with the Outline ofInvestigation for Open Type Switches, UL 98A.1.6 These requirements also cover fused and unfused electrically tripped PV switches.2 Components2.1 Except as indicated in 2.2, a component of a product cover
15、ed by this outline shall comply with therequirements for that component.2.2 A component is not required to comply with a specific requirement that:a) Involves a feature or characteristic not required in the application of the component in theproduct covered by this outline; orb) Is superseded by a r
16、equirement in this outline.2.3 A component shall be used in accordance with its rating established for the intended conditions ofuse.2.4 Specific components are incomplete in construction features or restricted in performance capabilities.Such components are intended for use only under limited condi
17、tions, such as certain temperatures notexceeding specified limits, and shall be used only under those specific conditions.FEBRUARY 4, 2015 UL 98B 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL3 Units of Measurement3.1 Values stated without
18、parentheses are the requirement. Values in parentheses are explanatory orapproximate information.4 Undated References4.1 Any undated reference to a code or standard appearing in the requirements of this outline shall beinterpreted as referring to the latest edition of that code or standard.5 Glossar
19、y5.1 For the purpose of this outline, the following definitions apply.5.2 PHOTOVOLTAIC (PV) SWITCH an open, enclosed or dead-front switch, with or withoutfuseholders, intended to operate in photovoltaic (PV) systems.CONSTRUCTION6 General6.1 The construction of a PV switch shall comply with the requi
20、rements as specified in Section 6 of theStandard for Enclosed and Dead-Front Switches, UL 98, except as noted in 6.2 6.5 as applicable.6.2 Multi-pole switches shall be considered as individual poles for individual loads unless marked inaccordance with 23.5.6.3 Fusible PV switches shall isolate the f
21、useholders from the line and load connections when the switchis in the open position.Exception: Fusible PV switches that do not isolate the fuseholders from both the line and loadconnections when in the open position shall be marked in accordance with 23.10.6.4 Doors shall be interlocked to prevent
22、access to the interior of the switch enclosure when the switchis in the closed position.Exception: A means requiring the use of a tool may be provided to bypass the interlock.6.5 The investigation of a PV switch shall take into consideration both the line and load terminals may beconnected to a PV s
23、ource.FEBRUARY 4, 2015UL 98B6UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL7 Spacings7.1 The electrical spacings for PV switches shall meet the requirements of the Standard for Enclosed andDead-Front Switches, UL 98. Those PV switches rated
24、601 1500 V shall meet the requirements for 600V of the Standard for Enclosed and Dead-Front Switches, UL 98.8 Wire Terminals8.1 The field wiring terminal of a PV switch shall have a capacity acceptable for the number, wire sizeand type of stranding associated with the maximum ampere rating of the sw
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT98B2015OUTLINEOFINVESTIGATIONFORENCLOSEDANDDEADFRONTSWITCHESFORUSEINPHOTOVOLTAICSYSTEMSISSUE3

链接地址:http://www.mydoc123.com/p-1069525.html