1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJULY 11, 20141UL 98AOutline of Investigation for Open Type SwitchesIssue Number: 2July 11, 2014Summary of TopicsThis second issue of the Outline of Investigation for Open Type Switches,UL 98A, is
2、 being published to allow for electrically operated switches.ULs Outlines of Investigation are copyrighted by UL. Neither a printed norelectronic copy of an Outline of Investigation should be altered in any way. All ofULs Outlines of Investigation and all copyrights, ownerships, and rights regarding
3、those Outlines of Investigation shall remain the sole and exclusive property of UL.COPYRIGHT 2014 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJULY 11, 2014UL 98A2No Text on This PageUL COPYRIGHTED MATERIAL NOT
4、 AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 Components .43 Units of Measurement .54 Undated References 55 Glossary 5CONSTRUCTION6 Enclosure 57 Operating Handle .58 Electrical Operators .68.1 General .68.2 Mounting 68.3 Field wiring 78
5、.4 Strain relief 78.5 Installation .89 Spacings .9PERFORMANCE10 Test Enclosure Details 910.1 General 910.2 Electrical operator interrupting tests 1010.3 Electrical operator endurance test 1010.4 Temperature test on coils and windings .1110.5 Dielectric voltage-withstand test 1210.6 Strain relief 12R
6、ATINGS11 Details .12MARKING12 Details .1313 Electrical Operators .14APPENDIX A (normative)JULY 11, 2014 UL 98A 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover open type switches for installation
7、 without an enclosure, where acceptable,or for installation in a panelboard, switchboard, motor control center, industrial control panel or the like, orfor installation in a Listed cabinet or cutout box in accordance with the switch installation instructions.1.2 Open type switches are manually opera
8、ble by means of an external handle.1.3 These requirements also cover motor operators for use with enclosed switches.1.4 These requirements are intended to be used in conjunction with the requirements specified in theStandard for Enclosed and Dead-Front Switches, UL 98, except as modified or suppleme
9、nted by thisOutline.2 Components2.1 Except as indicated in 2.2, a component of a product covered by this Outline of Investigation shallcomply with the requirements for that component.2.2 A component is not required to comply with a specific requirement that:a) Involves a feature or characteristic no
10、t required in the application of the component in theproduct covered by this Outline of Investigation; orb) Is superseded by a requirement in this Outline of Investigation.2.3 A component shall be used in accordance with its rating established for the intended conditions ofuse.2.4 Specific component
11、s are incomplete in construction features or restricted in performance capabilities.Such components are intended for use only under limited conditions, such as certain temperatures notexceeding specified limits, and shall be used only under those specific conditions.JULY 11, 2014UL 98A4UL COPYRIGHTE
12、D MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL3 Units of Measurement3.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory orapproximate information.4 Undated References4.1 Any undated reference to a code or stan
13、dard appearing in the requirements of this Outline ofInvestigation shall be interpreted as referring to the latest edition of that code or standard.5 Glossary5.1 For the purpose of this outline, the following definitions apply.5.2 ELECTRICAL OPERATOR An electrical controlling device which is used to
14、 operate themechanism of a switch in order to open and close the switch.CONSTRUCTION6 Enclosure6.1 Open-type switches are provided with a partial enclosure or without an enclosure.6.2 Open-type switches shall be provided with means for mounting.7 Operating Handle7.1 Switches are provided with an ope
15、rating handle.Exception: Switches evaluated for use with more than one operating handle may be shipped without anoperating handle. See 12.7.7.2 If an operating handle is intended for mounting such that movement of the operating handle, eithervertically or rotationally, between the ON and OFF positio
16、ns results in one position being above the otherposition, then the upper position shall be the ON position.Exception No. 1: A switch that is operated rotationally with the ON and OFF positions at the same levelneed not comply with this requirement.Exception No. 2: A switching device having two ON po
17、sitions such as a transfer switch or a double throwswitch need not comply with this requirement.7.3 The switch operating mechanism meets the intent of the requirement in 7.1 if it is constructed for fieldinstallation of the operating handle and handle assembly. Field installation of the operating ha
18、ndle andhandle assembly shall be by the use of common tools with no disassembly of the switch.JULY 11, 2014 UL 98A 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL7.4 The operating handle kit intended for field installation shall contain all
19、the necessary mountinghardware, installation instructions and details for maintaining the enclosure environmental rating(s).8 Electrical Operators8.1 General8.1.1 A component part of an electrical operator shall comply with the requirements for that component.8.1.2 One sample of each electrical oper
20、ator is to be installed in the intended manner to determinecompliance with the construction requirements of this outline.8.1.3 A winding shall be such as to resist the absorption of moisture and shall be formed and assembledin a workmanlike manner.8.1.4 With regard to the requirement in 8.1.3, film-
21、coated magnet wire is not required to be additionallytreated to prevent absorption of moisture, but fiber slot liners, cloth coil wrap, and similarmoisture-absorptive materials should be provided with impregnation or otherwise treated to preventmoisture absorption.8.1.5 An electrical operator intend
22、ed to be mounted externally to the switch may be factory- orfield-installed. Instructions shall be provided with the electrical operator when it is intended to befield-installed.8.1.6 Provision shall be made for manual operation of a switch that is equipped with an electrical operatorand shall be so
23、 located that when in use, the wiring space and live parts are not exposed. Means shall beprovided to prevent the electrical operator from functioning during manual operation if electrical operationcan result in a risk of electric shock or injury to operating personnel.8.1.7 An electrical operator s
24、hall be provided with means for grounding all exposed accessible metalparts.8.2 Mounting8.2.1 An electrical operator shall be securely mounted in position and prevented from loosening or turningif such motion may adversely affect the intended performance of the switch or reduce the minimumspacing to
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT98A2014OUTLINEOFINVESTIGATIONFOROPENTYPESWITCHESISSUE2 开放型 开关 调查 大纲 议题 PDF

链接地址:http://www.mydoc123.com/p-1069524.html