UL SUBJECT 2808-2015 UL Outline for Investigation Energy Monitoring Current Transformers (Issue 2)《能量监测电流互感器的调查大纲 (议题2)》.pdf
《UL SUBJECT 2808-2015 UL Outline for Investigation Energy Monitoring Current Transformers (Issue 2)《能量监测电流互感器的调查大纲 (议题2)》.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 2808-2015 UL Outline for Investigation Energy Monitoring Current Transformers (Issue 2)《能量监测电流互感器的调查大纲 (议题2)》.pdf(24页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULAUGUST 11, 20151UL 2808Outline of Investigation for Energy Monitoring Current TransformersIssue Number: 2August 11, 2015Summary of TopicsThis is the second issue of the Outline of Investigation f
2、or EnergyMonitoring Current Transformers, UL 2808. Updates include the following:1. Revised spacing requirements in accordance with UL 61010-1 basicinsulation requirements in lieu of requiring full reinforced levels2. Addition of requirements for enclosed-type current transformersintended for outdoo
3、r use3. Addition of requirements to address Rogowski coil type constructions4. Addition of requirements for terminal blocks and industrial cableassemblies for alternative wiring methods5. Addition of requirements for Signal Gathering/Multiplexer Accessoriesto allow multiple current transformers to b
4、e connected together withina panel to send the signal down one pair of conductors to the meter6. Increasing the maximum primary voltage rating to include 1,000 Vacand 1,500 Vdc circuitsULs Outlines of Investigation are copyrighted by UL. Neither a printed norelectronic copy of an Outline of Investig
5、ation should be altered in any way. All ofULs Outlines of Investigation and all copyrights, ownerships, and rights regardingthose Outlines of Investigation shall remain the sole and exclusive property of UL.COPYRIGHT 2015 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTH
6、ER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULAUGUST 11, 2015UL 28082No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 Components 43 Units of Measurement .54 Undated References 55 Gl
7、ossary .5CONSTRUCTION6 General 67 Case and Potting Materials .68 Spacings .89 Field wiring 1210 Burden Components 13PERFORMANCE11 Mold Stress Relief Test 1412 Dielectric Voltage-Withstand Test 1413 Lead Securement Test 1514 Permanence of Marking Test .1515 Temperature Test 1516 Permissible Limit Tes
8、t .1917 Outdoor Use Submersion Test .1918 Outdoor Use Cold Impact Test .19MARKINGS19 General 20INSTALLATION INSTRUCTIONS20 General 21ACCESSORIES21 Signal Gathering/Multiplexer Accessories 22APPENDIX AStandard for Components.A1AUGUST 11, 2015 UL 2808 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHE
9、R REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover open-type current transformers and their associated signal level combinerand/or multiplexer board accessories thereto intended for field installation within distribution and controlequipment such
10、as panelboards, switchboards, industrial control equipment, and energymonitoring/management equipment, to measure current on a branch circuit. Installation is in accordancewith the National Electrical Code, ANSI/NFPA 70. These requirements also cover Service Entranceenclosed-type current transformer
11、s intended for outdoor use.1.2 These current transformers are rated to measure current in a maximum 250 Vac, 600 Vac, or 1000Vac line-to-line circuits or in a maximum 1500 Vdc circuit. Transformers rated for use in an AC circuit mayalso be used in DC circuits that do not exceed the Vac rating.1.3 Cu
12、rrent transformer conductor leads under the scope of this Outline are considered a Class 1 circuit,as defined by the National Electrical Code, ANSI/NFPA 70, and are intended to be installed with NFPA 70Chapter 3 wiring methods. Isolation for the user is provided at the termination.1.4 This Outline d
13、oes not include investigation of the function of the controlled equipment.1.5 These current transformers have not been evaluated for accuracy or use with emergency controlsystems where the function of the control could affect safety.1.6 These current transformers are intended for use in an ambient t
14、emperature of 0 40C (32 104F)unless specifically indicated for use in other conditions.1.7 These current transformers are intended for use at altitudes up to 2000 meters (6562 ft) and in ahumidity tolerance of095percent, unless indicated for use in other conditions.1.8 Unless specifically evaluated
15、and marked “Service Entrance”, these current transformers areevaluated for installation within equipment on the load side of the service equipment overcurrent device.2 Components2.1 Except as indicated in 2.2, a component of a product covered by this Outline of Investigation shallcomply with the req
16、uirements for that component.2.2 A component is not required to comply with a specific requirement that:a) Involves a feature or characteristic not required in the application of the component in theproduct covered by this Outline, orb) Is superseded by a requirement in this Outline.2.3 A component
17、shall be used in accordance with its rating established for the intended conditions ofuse.AUGUST 11, 2015UL 28084UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL2.4 Specific components are incomplete in construction features or restricted in p
18、erformance capabilities.Such components are intended for use only under limited conditions, such as certain temperatures notexceeding specified limits, and shall be used only under those specific conditions.3 Units of Measurement3.1 Values stated without parentheses are the requirement. Values in pa
19、rentheses are explanatory orapproximate information.4 Undated References4.1 Any undated reference to a code or standard appearing in the requirements of this Outline shall beinterpreted as referring to the latest edition of that code or standard.5 Glossary5.1 For the purposes of this Outline, the fo
20、llowing definitions apply.5.2 BURDEN COMPONENT A resistor or other component that limits open circuit voltage of the currenttransformer.5.3 CLASS 1 CIRCUIT The portion of the wiring system between the load side of the overcurrent deviceor power-limited supply and the connected equipment.5.4 CLASS 2
21、CIRCUIT The portion of the wiring system between the load side of a Class 2 powersource and the connected equipment.5.5 OPEN-TYPE DEVICE A device that is not provided with a complete enclosure and is intended tobe placed in a suitable end-product enclosure.5.6 SERVICE ENTRANCE That portion of the in
22、stallation between the service point and the line sideof the service equipment.Note: Service entrance correlates with Overvoltage Category IV, or CAT IV, as defined in IEC 60364 andIEC 60664-1.5.7 CONTROLLED ENVIRONMENT Also known as Pollution Degree 2. Indicates current transformersare intended for
23、 installation in an environment where only non-conductive POLLUTION occurs, exceptthat occasionally a temporary conductivity caused by condensation is expected.5.8 ENCLOSED-TYPE DEVICE A device that is provided with a complete enclosure and may beinstalled outside of a separate end-product enclosure
24、.AUGUST 11, 2015 UL 2808 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONSTRUCTION6 General6.1 In order to reduce the likelihood of creating a risk of electric shock, all metallic parts shall becompletely encased or otherwise recessed with
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT28082015ULOUTLINEFORINVESTIGATIONENERGYMONITORINGCURRENTTRANSFORMERSISSUE2 能量 监测 电流 互感器 调查 大纲

链接地址:http://www.mydoc123.com/p-1069351.html