UL SUBJECT 2755-2018 UL Standard for Safety Outline of Investigation for Modular Data Centers (Issue 2).pdf
《UL SUBJECT 2755-2018 UL Standard for Safety Outline of Investigation for Modular Data Centers (Issue 2).pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 2755-2018 UL Standard for Safety Outline of Investigation for Modular Data Centers (Issue 2).pdf(72页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJuly 18, 20181UL 2755Outline of Investigation for Modular Data CentersIssue Number: 2July 18, 2018Summary of TopicsThis is the Second Issue of the Outline of Investigation for Modular DataCenters
2、, Subject 2755, which covers pre-engineered data center modulesconsisting of an outer cabinet or container that houses informationtechnology equipment (ITE) and various support equipment such aselectrical service and distribution equipment, HVAC systems and the like.ULs Outlines of Investigation are
3、 copyrighted by UL LLC. Neither a printed norelectronic copy of an Outline of Investigation should be altered in any way. All ofULs Outlines of Investigation and all copyrights, ownerships, and rights regardingthose Outlines of Investigation shall remain the sole and exclusive property of ULLLC.COPY
4、RIGHT 2018 UL LLCUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJULY 18, 2018UL 27552No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTS1 Scope .52 Equipment, S
5、ub-Assemblies and Components 53 Units of Measurement .64 Undated References 65 Glossary .66 Electrical .96.1 General .96.2 Electrical supply and distribution 96.3 Wiring and protection 106.4 Wiring methods and materials .106.5 Field wiring compartments 106.6 Field Wiring Terminals .116.7 Wire bendin
6、g space .156.8 Flexible cable .166.9 Separation of circuits 166.10 Disconnecting means .186.11 Service equipment services rated 600 V or less 196.12 Panelboards and switchboards .206.13 Power transformers .246.14 Receptacles .256.15 Lighting .256.16 Emergency lighting .276.17 Intrusion alarms .287 G
7、rounding 287.1 General 287.2 Grounding terminals and connectors .297.3 Identification of equipment grounding conductors and terminals .308 Working Space 318.1 General 318.2 Equipment operating at 600 Volts, nominal, or less 328.3 ITE 328.4 Working space markings .339 Battery Supplies and Ventilation
8、 339.1 General 339.2 Batteries .339.3 Battery mounting 349.4 Battery enclosure and enclosure venting .359.5 Hydrogen detection system .369.6 Work areas and working space around batteries 379.7 Replaceable batteries 379.8 Battery supply performance .3810 General Construction 4010.1 Materials 4010.2 G
9、lass covered openings 4010.3 Installed equipment .4110.4 Mechanical hazards 4211 Enclosures .4211.1 Materials 4211.2 Certified ISO type shipping containers 4311.3 Other types of MDC enclosures .4411.4 Doors .49JULY 18, 2018 UL 2755 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORD
10、ISTRIBUTION WITHOUT PERMISSION FROM UL11.5 Floors .4911.6 Stacking 4912 Exit Routes 5012.1 General .5012.2 Exit doors .5012.3 Number of exit routes .5112.4 Secondary exits 5112.5 Height and width requirements .5212.6 Emergency exit identification .5313 Fire Detection and Suppression 5413.1 Smoke/fir
11、e detection/protection 5413.2 Fire suppression systems .5413.3 Fire resistance rating .5414 Environmental Considerations 5414.1 General .5415 HVAC .5515.1 General .5515.2 Room type air conditioners 5515.3 Stationary air conditioning systems .5615.4 Fixed electric space heating equipment .5715.5 Cool
12、ing system plumbing and piping 5716 Noise Exposure 5917 Product Assembly 6017.1 General .6017.2 Shipping unassembled 6017.3 Field installed accessories .6117.4 Assembly test .6317.5 MDCs not fully configured .6318 Performance .6418.1 General .6418.2 Temperature test .6418.3 Dielectric voltage-withst
13、and test 6418.4 Transport and handling vertical impact test 6519 Markings .6619.1 General .6619.2 ITE and other load equipment electrical rating marking .6719.3 Field wiring terminal markings .6819.4 Panelboard and switchboard markings 6820 Instructions 68APPENDIX A (Normative)Standards for Componen
14、tsA1JULY 18, 2018UL 27554UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL1 Scope1.1 This Outline of Investigation covers Modular Data Centers (MDC). The Modular Data Centers coveredby these requirements are pre-fabricated units consisting of a
15、n outer enclosure housing ITE and varioussupport equipment such as electrical service and distribution equipment, HVAC systems and the like.Some configurations may have the support equipment housed in a separate enclosure. A typicalconstruction may use a standard ISO shipping container or other stru
16、cture as the outer enclosure, racksor cabinets of ITE, NEC compliant service entrance equipment and power distribution components, powerstorage such as a UPS and an air or liquid cooling system.1.2 These factory-built modules incorporate pre-installed materials and equipment which, afterinstallation
17、, may be concealed and may not be accessible for inspection at the final installation site.1.3 The modular data centers covered by these requirements are intended for fixed installation eitherindoors or outdoors based on their construction and resistance to environmental conditions. MDCsintended for
18、 outdoor use shall be identified with a NEMA environmental class rating.1.4 These requirements are intended to demonstrate compliance with the National Electrical Code (NEC),NFPA 70 and other national Codes such as Building, Fire, Plumbing, Mechanical, and the like. Wherestate or local codes differ
19、from the national codes anticipated by these requirements, determiningcompliance with these codes is the responsibility of the local authority having jurisdiction.1.5 When these requirements do not cover a specific technology or construction feature, the applicablerequirements of the National Codes
20、shall be used.1.6 This Outline of Investigation assumes that the final installation of the MDC will be performed byqualified service personnel in accordance with the applicable installation instructions, installation practicesand national installation codes. These MDCs are intended for installation
21、subject to approval by theAuthority Having Jurisdiction.2 Equipment, Sub-Assemblies and Components2.1 Except as indicated in 2.2, equipment, subassemblies and components used as a part of an MDCcovered by this Outline of Investigation shall comply with the requirements for that equipment,subassembly
22、 or component. See Appendix A for a list of standards covering equipment, subassembliesand components.2.2 Equipment, subassemblies and components are not required to comply with a specific requirementthat:a) Involves a feature or characteristic not required in the application of the component in the
23、product covered by this Outline of Investigation; orb) Is superseded by a requirement in this Outline of Investigation.2.3 Equipment, subassemblies and components shall be used in accordance with their ratings and anyinstallation requirements established for the intended conditions of use.JULY 18, 2
24、018 UL 2755 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL2.4 Equipment, subassemblies and components that are incomplete in construction features or restrictedin performance capabilities shall be used only under the specific conditions for
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT27552018ULSTANDARDFORSAFETYOUTLINEOFINVESTIGATIONFORMODULARDATACENTERSISSUE2PDF

链接地址:http://www.mydoc123.com/p-1069347.html