UL SUBJECT 213B-2010 OUTLINE OF INVESTIGATION FOR WELDED OUTLET FITTINGS FOR FIRE PROTECTION SYSTEMS (Issue 5)《SUBJECT 213B 防火系统中使用的焊式出口管接头调查大纲发布号 5》.pdf
《UL SUBJECT 213B-2010 OUTLINE OF INVESTIGATION FOR WELDED OUTLET FITTINGS FOR FIRE PROTECTION SYSTEMS (Issue 5)《SUBJECT 213B 防火系统中使用的焊式出口管接头调查大纲发布号 5》.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 213B-2010 OUTLINE OF INVESTIGATION FOR WELDED OUTLET FITTINGS FOR FIRE PROTECTION SYSTEMS (Issue 5)《SUBJECT 213B 防火系统中使用的焊式出口管接头调查大纲发布号 5》.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJune 21, 20101SUBJECT 213BOUTLINE OF INVESTIGATIONFORWELDED OUTLET FITTINGS FOR FIRE PROTECTION SYSTEMSIssue Number: 5JUNE 21, 2010Summary of TopicsThis Fifth Issue of the Outline of Investigatio
2、n for Welded Outlet Fittingsfor Fire Protection Systems, Subject 213B, includes the following changesin requirements from the Fourth Issue of the Outline:Inclusion of references to installation standards where steelwelded outlet fittings are intended for useAddition of Paragraph 5.2 to include a def
3、inition for NPS orNominal Pipe SizeAddition of Paragraph 5.3 to include a definition for RubberGasketed FittingsAddition of references to Paragraph 6.1 and new Section 7 forother acceptable materials used to construct these fittingsAddition of references to Paragraphs 6.2 and 6.3 for otheracceptable
4、 pipe threads for threaded fittingsAddition of references to new Paragraph 8.5 to specify the weldmethod and pipe preparation as specified in NFPA 13 whenfabricating test samplesClarification of requirements for the Leakage and HydrostaticTests in Sections 9 and 10 respectivelyAddition of the Bendin
5、g Moment Test, Section 11, when the outletpipe wall thickness is less than the wall thickness of the run pipeRemoval of the Metallic Material Test and replacing the testingrequirements with the material specification compliance in MetallicMaterial, Section 7See the Fourth Issue for the current requi
6、rements until the effective dateis met.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULThe UL Foreword is no longer located within the UL Standard. For informationconcerning the use and application of the requirements contained in thisStandard
7、, the current version of the UL Foreword is located onULStandardsInfoNet at: http:/ 2010 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 General 52.1 Components .52.2 Units of measu
8、rement .52.3 Undated references .53 Rated Pressure .54 Sizes 65 Glossary .6CONSTRUCTION6 General 67 Metallic Materials .7PERFORMANCE8 Samples .79 Leakage Test .810 Hydrostatic Pressure Test .811 Bending Moment Test 8MARKING12 General .9JUNE 21, 2010 SUBJECT 213B 3UL COPYRIGHTED MATERIAL NOT AUTHORIZ
9、ED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover steel welded outlet fittings intended for use in water based fire protectionsystems in accordance with the following installation standards:a) Standard for Low-, Medium-, and High-Exp
10、ansion Foam, NFPA 11;b) Standard for the Installation of Sprinkler Systems, NFPA 13;c) Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings andManufactured Homes, NFPA 13D;d) Standard for the Installation of Sprinkler Systems in Residential Occupancies Up to andIncludi
11、ng Four Stories in Height, NFPA 13R;e) Standard for the Installation of Standpipe and Hose Systems, NFPA 14;f) Standard for Water Spray Fixed Systems for Fire Protection, NFPA 15; andg) Standard for the Installation of Foam-Water Sprinkler and Foam-Water Spray Systems,NFPA 16;1.2 Welded Outlet Fitti
12、ngs consist of steel outlets intended to be welded to steel run pipe in Schedules10, 30, 40 and Listed steel sprinkler pipe having the same outside diameter as Schedule 40 pipe where:a) The outlet pipe having wall thickness the same as or less than the run pipe orb) The run pipe has a wall thickness
13、 equivalent to Schedule 10 steel pipe and the outlet wallthickness is equivalent to Schedule 40 steel pipe.These fittings may be suitable for use with other Listed steel run pipe when intended for use with outletwall thicknesses greater than the run pipe wall thickness, when evaluated as described i
14、n BendingMoment Test, Section 11.JUNE 21, 2010SUBJECT 213B4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL2 General2.1 Components2.1.1 Except as indicated in this paragraph, a component of a product covered by this Outline ofInvestigation sha
15、ll comply with the requirements for that component.2.1.2 A component is not required to comply with a specific requirement that:a) Involves a feature or characteristic not required in the application of the component in theproduct covered by this Outline of Investigation orb) Is superseded by a requ
16、irement in this Outline of Investigation.2.1.3 A component shall be used in accordance with its rating established for the intended conditions ofuse.2.1.4 Specific components are incomplete in construction features or restricted in performancecapabilities. Such components are intended for use only u
17、nder limited conditions, such as certaintemperatures not exceeding specified limits, and shall be used only under those specific conditions.2.2 Units of measurement2.2.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory orapproximate information.2.3 Undated
18、 references2.3.1 Any undated reference to a code or standard appearing in the requirements of this Outline ofInvestigation shall be interpreted as referring to the latest edition of that code or standard.3 Rated Pressure3.1 Welded Outlet fittings shall be constructed for use at a minimum rated press
19、ure of 175 psig.JUNE 21, 2010 SUBJECT 213B 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL4 Sizes4.1 Outlet fittings sizes shall be 1/8 NPS or larger.5 Glossary5.1 For the purpose of these requirements, the following definitions apply.5.2 NP
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT213B2010OUTLINEOFINVESTIGATIONFORWELDEDOUTLETFITTINGSFORFIREPROTECTIONSYSTEMSISSUE5SUBJECT213B

链接地址:http://www.mydoc123.com/p-1069233.html