UL SUBJECT 2075A-2008 OUTLINE OF INVESTIGATION FOR CO Gas Test Kit for Gas and Vapor Detectors and Sensors (Issue 1)《用于气体和蒸汽探测器和传感器的一氧化碳气体测试试剂盒的调查大纲 (议题1)》.pdf
《UL SUBJECT 2075A-2008 OUTLINE OF INVESTIGATION FOR CO Gas Test Kit for Gas and Vapor Detectors and Sensors (Issue 1)《用于气体和蒸汽探测器和传感器的一氧化碳气体测试试剂盒的调查大纲 (议题1)》.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 2075A-2008 OUTLINE OF INVESTIGATION FOR CO Gas Test Kit for Gas and Vapor Detectors and Sensors (Issue 1)《用于气体和蒸汽探测器和传感器的一氧化碳气体测试试剂盒的调查大纲 (议题1)》.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULSeptember 4, 20081SUBJECT 2075AOUTLINE OF INVESTIGATIONFORCO Gas Test Kit for Gas and Vapor Detectors and SensorsIssue Number: 1SEPTEMBER 4, 2008COPYRIGHT 2008 UNDERWRITERS LABORATORIES INC.UL CO
2、PYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULSEPTEMBER 4, 2008SUBJECT 2075A2No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 General 42.1
3、 Units of measurement .42.2 Undated references .43 Glossary .4CONSTRUCTION4 General 4PERFORMANCE5 Tests 5MARKING6 Product Marking 7Instructions7 Instructions .8SEPTEMBER 4, 2008 SUBJECT 2075A 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULIN
4、TRODUCTION1 Scope1.1 These requirements cover CO gas test kits used to test CO gas and vapor detectors and sensors.1.2 The products covered by this outline of investigation are intended to be used as a means to test COgas and vapor detectors and sensors. Installation/operating document(s) and/or pro
5、duct markinginformation provided with the product describe the operation of the accessory.2 General2.1 Units of measurement2.1.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory orapproximate information.2.2 Undated references2.2.1 Any undated reference to
6、 a code or standard appearing in the requirements of this standard shallbe interpreted as referring to the latest edition of that code or standard.3 Glossary3.1 For the purpose of this document the following definitions apply.3.2 CARBON MONOXIDE (CO) A colorless, odorless toxic gas.3.3 PPM Gas conce
7、ntration in parts per million.CONSTRUCTION4 General4.1 Gas test kits shall be constructed to comply with the following:4.2 The container shall have a DOT (Department of Transportation) rating suitable for the material beingdispensed. The manufacturer shall provide evidence that the DOT rating is sui
8、table.SEPTEMBER 4, 2008SUBJECT 2075A4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULPERFORMANCE5 Tests5.1 Except for 5.6 all tests are to be completed in sequential order.5.2 Sensitivity Test Conduct on 12 end product detectors or sensors per
9、 clause 15 of the standard forGas and Vapor Detectors and Sensors, UL 2075, (reference the sensitivity limits of Clause 38 of thestandard for Single and Multiple Station Carbon Monoxide Alarms, UL 2034, where appropriate).5.3 Normal Operation To be conducted as outlined in the operating instructions
10、 for the CO Gas Test Kiton 12 end product sample detectors.5.4 Abnormal Usage Expose 12 end product CO detectors to the abnormal exposure levels. The entirecontents of one can is to be dispensed as close to the sensor as possible (while the detector/sensor is inits normal operating configuration) to
11、 determine if subsequent operation of the detectors/sensor has beenadversely affected.5.5 Sensitivity Test Following 5.4, verify that the Sensitivity of the alarm has not been affected bysubjecting the samples to the Sensitivity Test outlined in Section 15 of Gas and Vapor Detectors andSensors, UL 2
12、075, (reference the CO sensitivity limits outlined in Section 38 of Single and Multiple StationCarbon Monoxide Detectors, UL 2034 where appropriate).5.6 As described/defined in the operating instructions, dispense the gas (CO) from the can into a gassample bag. Using a CO monitor/analyzer with an ac
13、curacy of 1 percent or better, analyze theconcentration of the CO that was injected into the gas sample bag. Verify that the measured COconcentration recorded by the CO analyzer is within 5 percent of the manufacturers specifications.Equivalent methods to quantify the gas concentration may be engine
14、ering reviewed to determine theirmeans of repeatability and reliability toward validating CO concentration contained within a can.5.7 Using the mechanical print provided by the manufacturer, calculate the internal volume of the can.Using 3 mutually exclusive end product cans of CO, measure and recor
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT2075A2008OUTLINEOFINVESTIGATIONFORCOGASTESTKITFORGASANDVAPORDETECTORSANDSENSORSISSUE1 用于 气体

链接地址:http://www.mydoc123.com/p-1069228.html