UL 924 TGD-2017 UL Standard for Safety Emergency Lighting and Power Equipment - Section Paragraph Reference See Subject Topics Topic 1 Representative Luminance Measurement Testing.pdf
《UL 924 TGD-2017 UL Standard for Safety Emergency Lighting and Power Equipment - Section Paragraph Reference See Subject Topics Topic 1 Representative Luminance Measurement Testing.pdf》由会员分享,可在线阅读,更多相关《UL 924 TGD-2017 UL Standard for Safety Emergency Lighting and Power Equipment - Section Paragraph Reference See Subject Topics Topic 1 Representative Luminance Measurement Testing.pdf(16页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUL TECHNICAL GUIDANCE DOCUMENTSThis Document is prepared and published by UL.Product Category (CCN): FTBR, FTBV, FWBX, OUSTStandard Number: UL 924Standard Title: Standard for Emergency Lighting a
2、nd Power EquipmentEdition Date: May 9, 2016Edition Number: 10Section / Paragraph Reference: See Subject TopicsTopic 1: Representative Luminance Measurement Testing for Exit Signs- Section /Paragraph Reference: 43.1.9Topic 2: Representative Fluorescent Lamp Loads for Emergency Battery Pack Tests(maxi
3、mum load verification) )- Section / Paragraph Reference: 48.6, 54.1, 78.1,78.2Topic 3: Equipment with Battery Heaters and Heater Controls- Section / ParagraphReference: 47.5, 48.2, 54.2Topic 4: Calculating Extended Operating Time based on Increased Number ofBatteries- Section / Paragraph Reference:
4、73.1.7 (marked operating time)Topic 5: Transformer Requirements for Canadian (C-UL) Certification- Section /Paragraph Reference: Supplement SDTopic 6: Thermally-sensitive Components in Exit Signs- Section / ParagraphReference: 40.2Topic 7: “EXIT Text Legend Observation Test as Representative for a L
5、egend inOther Languages- Section / Paragraph Reference: 43.2.3(b)Topic 8: Alternative / Replacement LED Arrays in Exit Signs- Section / ParagraphReference: 43.3Topic 9: Certification of Emergency LED Drivers- Section / Paragraph Reference:Supplements SA and SGTopic 10: Representative Fluorescent Lam
6、p Loads for Battery / Inverter SystemTests (Minimum Light Output) - Section / Paragraph Reference: SA3.5, SG2Topic 11: Emergency Luminaire Maximum Mounting Height Calculations- Section /Paragraph Reference: SG3.2Topic 12: Vertically Oriented Exit Signs- Section / Paragraph Reference: N/ATopic 13: Ex
7、it Signs with a Supplemental Directional Arrow- Section / ParagraphReference: Section 40Topic 14: Cord and Plug-Connected Emergency Lighting Equipment- Section /Paragraph Reference: Sections 17 and 18Topic 15: Graphical Symbol Exit Signs with Two Directional Arrows: Section /Paragraph Reference: 42.
8、1GUIDANCE:Topic 1: Representative Luminance Measurement Testing for Exit Signs - Section / ParagraphReference: 41.1.8Consideration should be given to the proportionate reduction in DC voltage and to the previously recordedluminance measurement data relative to the minimum luminance requirement (8.7
9、cd/m2). These datacomparisons are only valid where the LED array, its affiliated circuitry, and its physical / optical relationshipto the exit sign face are identical. Where a family of exit signs (using the same LED array) has beencertified, luminance data at various DC voltage levels may already b
10、e available.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULAs a general rule of thumb, the luminance measurement test need not be repeated if the DC voltagereduction is 5% or less (0.3V on a 6V nominal system; 0.24V on a 4.8V system) for an e
11、xit sign whosemeasured luminance exceeds the minimum requirement by 25% or more (approx. 11 cd/m2). Where theoriginally measured luminance output is even greater, higher levels of DC voltage reduction can beaccommodated (provided that the battery terminal voltage still meets the minimum 87.5% nomina
12、lrequirement).As an alternative, a manufacturer can request the luminance measurement test to be conducted at thenominal 87.5% battery voltage. If compliant results are obtained, any subsequent change in batteryperformance that still complies with the battery discharge test of Section 48 (retaining
13、minimum 87.5%battery voltage) can be permitted without repeating the luminance measurement test.Topic 2: Representative Fluorescent Lamp Loads for Emergency Battery Pack Tests (maximumload verification) )- Section / Paragraph Reference: 46.7, 52A.1, 75.1, 75.2In lieu of UL conducting battery dischar
14、ge current measurement tests on all requested lamp types andconfigurations to determine a representative sample configuration for the battery discharge cycling test,the emergency battery pack manufacturer should be invited to submit their own complete data set. Theyshould have this data to support t
15、heir claim that their battery system is suitable for operating the requestedrange of lamp types/configurations for the minimum 90 minute requirement of UL 924. If they do not havesupporting data, UL can generate it for them as a preliminary phase of the overall investigation (this wouldbe a separate
16、 service from the UL 924 compliance assessment).If the manufacturer submits data, UL should countercheck at least two but no more than five of the datapoints by conducting its own independent measurements of battery discharge current (note - this activitywould typically be considered integral to the
17、 UL 924 compliance assessment project). Unless there isreason to do otherwise, the data points selected for counterchecking should be among the highest currentlevels shown in the manufacturers data.A DC supply adjusted to nominal battery terminal voltage should be used for these measurements. Thecur
18、rent drawn from the supply by each load should be measured no sooner than one minute afterenergizing the supply. This one-minute delay allows for dissipation of any transients and stabilization ofthe lamp condition. The lamps used for the measurements should be acquired by UL (not provided by theman
19、ufacturer) and, if fluorescent, seasoned (operated) for at least 100 hours prior to takingmeasurements.All data collected during this process (whether from UL or the manufacturer) should be retained. If at somesubsequent time the manufacturer requests to further increase the range of eligible lamps,
20、 or submits analternative battery or charging system, this data set can be used to determine the extent of retesting, ifany, that will be needed.Topic 3: Equipment with Battery Heaters and Heater Controls- Section / Paragraph Reference:45.2.3, 46.2, 52A.2The minimum operational reliability investiga
21、tion for a heater control is its performance during the extremelow ambient phase of the referenced test programs. If the heater does not activate but the equipment isable to comply with the requirements, the heater circuit is only supplemental relative to equipmentcompliance with UL 924. If the heat
22、er fails to turn on and the battery is unable to comply with any of thereferenced test requirements, the equipment would be considered non-compliant.STANDARD NUMBER: UL 924 -2-UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULIf a heater control
23、 known to comply with requirements that evaluate its calibration and reliability (such asUL 353, UL 873, or UL 60730) does turn on during a low ambient phase of one of the referenced tests,the most severe low temperature condition would be at the point just prior to activation of the heater. Thelow
24、temperature phase of the program should be conducted at an ambient just prior to activation of theheater circuit.If a heater control NOT known to comply with requirements that evaluate its calibration and reliability turnson during a low ambient phase of one of the referenced tests, two supplemental
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL924TGD2017ULSTANDARDFORSAFETYEMERGENCYLIGHTINGANDPOWEREQUIPMENTSECTIONPARAGRAPHREFERENCESEESUBJECTTOPICSTOPIC1REPRESENTATIVELUMINANCEMEASUREMENTTESTINGPDF

链接地址:http://www.mydoc123.com/p-1069060.html