UL 891 CRD-2018 UL Standard for Safety Switchboards - Section Paragraph Reference Sections 6 3 4 4 and 8 6 5A Clauses 8 1 15 1 8 6 5 and 8 6 5 2 Subject Add Requirements for Switc.pdf
《UL 891 CRD-2018 UL Standard for Safety Switchboards - Section Paragraph Reference Sections 6 3 4 4 and 8 6 5A Clauses 8 1 15 1 8 6 5 and 8 6 5 2 Subject Add Requirements for Switc.pdf》由会员分享,可在线阅读,更多相关《UL 891 CRD-2018 UL Standard for Safety Switchboards - Section Paragraph Reference Sections 6 3 4 4 and 8 6 5A Clauses 8 1 15 1 8 6 5 and 8 6 5 2 Subject Add Requirements for Switc.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared by UL LLC. It is normative for the applicable ULProduct Certification Program(
2、s); however, it is currently not part of the UL Standard(s) referencedbelow.Product Category (CCN): WEVZStandard Number: UL 891Standard Title: Standard for SwitchboardsEdition Date: July 26, 2005Edition Number: 11Section / Paragraph Reference: Sections 6.3.4.4 and 8.6.5A; Clauses 8.1.15.1, 8.6.5,and
3、 8.6.5.2Subject: Add Requirements for “Switchboards Marked for use with InterconnectedElectric Power Production Sources” (NEC Article 705 Applications)DECISION:6.3.4.4 Switchboards marked for use with interconnected electric power production sources6.3.4.4.1 A switchboard provided with connections m
4、arked for use with one or more electric powerproduction sources operating in parallel with a primary source of electricity shall be marked “Suitable foruse with interconnected parallel electric power production sources”, “Suitable for use in accordance withArticle 705 of the National Electrical Code
5、, NFPA 70”, or the equivalent.6.3.4.4.2 Each disconnect or provision for connection for interconnected parallel power productionsources shall be marked “Parallel Energy Source Disconnect”, Prime Parallel Energy Source TapPrime, or the equivalent, or be provided with a space for the sources to be lab
6、eled in the field.6.3.4.4.3 Switchboards with parallel energy source disconnects shall be marked Prime Turning OffParallel Energy Source Disconnect does not deenergize this switchboard. Turn off power from all sourcessupplying this switchboard before working inside.” or equivalent wording.6.3.4.4.4
7、A marking shall be placed near each Parallel Energy Source Disconnect to be visible when theterminals are visible to warn the user that both the line and load terminals may be energized when thebreaker is in the open (Off) position.6.3.4.4.5 For load side connections in accordance with 8.6.5A.1(b),
8、the switchboard shall be marked withthe maximum ampere rating for all disconnects marked for connection to electric power productionsources operating in parallel with primary sources.8.1.15 Equipment on supply side of service disconnect (not for Canada)8.1.15.1 Except for the following, equipment sh
9、all not be connected to the supply side of the servicedisconnecting means:a) meters nominally rated not in excess of 600 V located in the switchboard;b) instrument transformers (current and potential), high-impedance shunts, Type 1 surge-protective devices, and load management devices;c) control cir
10、cuits of power operable service disconnecting means, if suitable overcurrentprotection and disconnecting means are provided, see 8.1.11.1.1;UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULd) Ground-fault protection systems or surge-protective
11、devices, if suitable overcurrent protectionand disconnecting means are provided, see 8.1.11.1.1; ande) taps used to supply load management devices, circuits for stand-by power systems, firepumps, and fire and sprinkler alarms.f) interconnected electric power production sources, such as solar photovo
12、ltaic, wind, or fuel cellsystems.8.6.5 Double-ended switchboards (multiple source) Multiple source switchboards8.6.5.1 Unless intended for parallel operation, the disconnect identified in Figure 2 and Figure 3 as thetie-breaker shall be provided with mechanical, key, or electrical interlocking with
13、the service disconnectsshown in the figures so that sources cannot be paralleled. If the tie-breaker is omitted, all disconnects shallbe provided with mechanical, electrical, or key interlocking so that the sources cannot be paralleled(unless intended for parallel operation).8.6.5.2 If a switchboard
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL891CRD2018ULSTANDARDFORSAFETYSWITCHBOARDSSECTIONPARAGRAPHREFERENCESECTIONS6344AND865ACLAUSES81151865AND8652SUBJECTADDREQUIREMENTSFORSWITCPDF

链接地址:http://www.mydoc123.com/p-1069037.html