UL 60335-2-40 CRD-2016 UL Standard for Safety Household and Similar Electrical Appliances Part 2-40 Particular Requirements for Electrical Heat Pumps Air-Conditioners and Dehumidif.pdf
《UL 60335-2-40 CRD-2016 UL Standard for Safety Household and Similar Electrical Appliances Part 2-40 Particular Requirements for Electrical Heat Pumps Air-Conditioners and Dehumidif.pdf》由会员分享,可在线阅读,更多相关《UL 60335-2-40 CRD-2016 UL Standard for Safety Household and Similar Electrical Appliances Part 2-40 Particular Requirements for Electrical Heat Pumps Air-Conditioners and Dehumidif.pdf(2页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared by UL LLC. It is normative for the applicable ULProduct Certification Program(
2、s); however, it is currently not part of the UL Standard(s) referencedbelow.Product Category (CCN): AFFT/7Standard Number: UL 60335-2-40Standard Title: Standard for Particular Requirements for Electrical Heat Pumps,Air-Conditioners and DehumidifiersEdition Date: November 30, 2012Edition Number: 1Sec
3、tion / Paragraph Reference: 19.101DV, 22.112DV.18, 30.2.3DVSubject:DECISION:19.101DV D2 - Modification by adding the following at the end of 19.101In appliances in which the compressor is enclosed in an unventilated enclosure where temperatures of theenclosure or components within the enclosure migh
4、t become a hazard upon loss of refrigerant flow, therefrigerant flow shall be reduced by removal of the refrigerant from the system.The test shall be conducted under each of the following conditions:- with 75% of the charge removed- with the system pressure less than 1.2 atm, but not less than 1.0 a
5、tm with the appliance de-energizedThe appliance shall be operated under the conditions of Clause 11 at the lower limit of the rated voltageand an ambient temperature of 23 C 5 C. The appliance shall be operated until all components andthe enclosure temperatures stabilize or are declining, but for no
6、t less than 24 hours, or until the operationof the compressor is terminated by a non-self-resetting protective device. Any self-resetting protectivedevices that actuates during this test shall be allowed to cycle as intended.Component temperatures shall:- not exceed the temperature limits in Clause
7、11- not exceed the relative thermal index of the material in accordance with UL746B and CAN/CSA C22.2No. 0.17 for polymeric materials22.112DV.18 Self-resetting protective devices which cycle during 19.101DV shall be rated for at least100,000 cycles for line break devices and 5,000 cycles for non-lin
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL60335240CRD2016ULSTANDARDFORSAFETYHOUSEHOLDANDSIMILARELECTRICALAPPLIANCESPART240PARTICULARREQUIREMENTSFORELECTRICALHEATPUMPSAIRCONDITIONERSANDDEHUMIDIFPDF

链接地址:http://www.mydoc123.com/p-1068408.html