《UL 48 CRD-2015 UL Standard for Safety Electric Signs - Section Paragraph Reference 2 65 1 4 4 6 1 1 4 4 6 1 6 7 7 2 and 8 2 2 Subject Rough-In Sign Sections (Edition 15 September .pdf》由会员分享,可在线阅读,更多相关《UL 48 CRD-2015 UL Standard for Safety Electric Signs - Section Paragraph Reference 2 65 1 4 4 6 1 1 4 4 6 1 6 7 7 2 and 8 2 2 Subject Rough-In Sign Sections (Edition 15 September .pdf(2页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared and published by Underwriters Laboratories Inc.(UL). It is normative for the a
2、pplicable UL Product Certification Program(s); however, it is currently notpart of the UL Standard(s) referenced below.Product Category (CCN): UYWU/8Standard Number: UL 48Standard Title: Standard for Electric SignsEdition Date: September 2, 2011Edition Number: 15Section / Paragraph Reference: 2.65.1
3、, 4.4.6.1.1, 4.4.6.1.6, 7.7.2, and 8.2.2Subject: Rough-In Sign SectionsDECISION:2.65.1 (NEW) SECTION SIGN, ROUGH-IN - A section of electric sign intended to be installed during therough-in phase of building construction.4.4.6.1.1 Except as noted in 4.4.6.1.6, aA section sign shall not be shipped for
4、 field installation to anexisting sign.4.4.6.1.6 (NEW) Sign sections may be shipped separately when one or more sections are installed in therough-in phase of building construction and the remaining sections are installed in the finish phase of thebuilding construction. See Par. 7.7.2.7.7.2_(NEW) A
5、sign section intended for installation during the rough-in phase of building construction andshipped separate from the rest of the sign shall be marked Rough-In Section and the section number.8.2.2 (NEW) A sign section identified as Rough-In is provided with a set of installation instructions thatid
6、entifies all the connected sign sections by number including the rough-in section sign. Sign sectionsshipped at a later date include a duplicate set of instructions that identifies all the connected sign sectionsby number including the rough-in sign section.RATIONALE FOR DECISION:Equipment room or u
7、tility room mounting of power supplies and LED drivers for remote channel letters isbecoming more common as an installation practice that affords better protection of the power sourceswhile helping facilitate more efficient electric sign maintenance. This type of installation is permitted by theNEC
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL48CRD2015ULSTANDARDFORSAFETYELECTRICSIGNSSECTIONPARAGRAPHREFERENCE26514461144616772AND822SUBJECTROUGHINSIGNSECTIONSEDITION15SEPTEMBERPDF

链接地址:http://www.mydoc123.com/p-1068187.html