UFC 3-410-01FA CHANGE 4-2010 HEATING VENTILATING AND AIR CONDITIONING [Superseded ARMY ARMY TI 810-10].pdf
《UFC 3-410-01FA CHANGE 4-2010 HEATING VENTILATING AND AIR CONDITIONING [Superseded ARMY ARMY TI 810-10].pdf》由会员分享,可在线阅读,更多相关《UFC 3-410-01FA CHANGE 4-2010 HEATING VENTILATING AND AIR CONDITIONING [Superseded ARMY ARMY TI 810-10].pdf(26页珍藏版)》请在麦多课文档分享上搜索。
1、UFC 3-410-01FA 15 May 2003 Including change 4, January 2010 UNIFIED FACILITIES CRITERIA (UFC) HEATING, VENTILATING, AND AIR CONDITIONING APPROVED FOR PUBLIC RELEASE; DISTRIBUTION UNLIMITED Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-UFC 3-410-01F
2、A 15 May 2003 Including change 4, January 2010 UNIFIED FACILITIES CRITERIA (UFC) HEATING, VENTILATING, AND AIR CONDITIONING Any copyrighted material included in this UFC is identified at its point of use. Use of the copyrighted material apart from this UFC must have the permission of the copyright h
3、older. U.S. ARMY CORPS OF ENGINEERS (Preparing Activity) NAVAL FACILITIES ENGINEERING COMMAND AIR FORCE CIVIL ENGINEER SUPPORT AGENCY Record of Changes (changes are indicated by 1 . /1/) Change No. Date Location 1 Oct 2006 Conform to UFC 1-300-01 and miscellaneous updates 2 Dec 2007 Incorporate EPAc
4、t05 requirements: Para 1-3.4 U.S. Navy, NAVFACENGCOM HQ Code CHENG; U.S. Marine Corps, HQMC Code LFF-1; U.S. Air Force, HQ AFCESA/CES; Defense Logistics Agency (DLA), DSS-IP; National Imagery and Mapping Agency (NIMA), Security and Installations; and all other DOD components, Deputy Under Secretary
5、of Defense for Installations via the DOD Committee on Heating, Ventilating, and Air Conditioning Engineering. 1-3 BASIC PRINCIPLES. The designer shall base all designs on the following basic principles: 1-3.1 Select interior design conditions, including temperature, humidity, filtration, ventilation
6、, air changes, etc., that are suitable for the intended occupancy. 1-3.2 All design work shall be “sustainable” in accordance with ECB 2006-2. 1-3.3 Base system selections on life cycle cost effectiveness. 1-3.4 3Energy consumption shall comply with the UFC 3-400-01. /3/ 31-3.5 Each design shall mee
7、t the requirements of UFC 4-030-01. /3/1-3.6 Each design shall be as simple as possible. 1-3.7 Identify space necessary to access items that require maintenance, such as filters, coils and drain pans, strainers, and chillers on the drawings in three-dimensions. Provided by IHSNot for ResaleNo reprod
8、uction or networking permitted without license from IHS-,-,-UFC 3-410-01FA 15 May 2003 Including change 4, January 2010 2 1-3.8 Provide systems with the features necessary for successful testing, adjusting, and balancing, system commissioning, and for easy access for maintenance. 1-4 WAIVERS. Where
9、a valid need exists and an alternate solution involving sound engineering is available, designers may submit requests for a criteria waiver to the applicable AHJ. Requests for waiver must include justification, life cycle cost analysis, energy compliance analysis, criteria used, and other pertinent
10、data. 1-5 REDUNDANT SYSTEMS. Generally, redundant HVAC systems are not required. However, when a system failure would result in unusually high repair costs or replacement of process equipment, or when activities are disrupted that are vital to national security, the designer may submit a request for
11、 approval to the applicable respective service proponents office in accordance with paragraph 1-4 to provide redundant HVAC systems. No waiver is required where redundant HVAC systems are specified by other applicable criteria. Provided by IHSNot for ResaleNo reproduction or networking permitted wit
12、hout license from IHS-,-,-UFC 3-410-01FA 15 May 2003 Including change 4, January 2010 3 CHAPTER 2 FUNDAMENTALS 2-1 CALCULATIONS. Perform multiple load calculations where suggested by ASHRAE in order to determine HVAC system requirements. One example where at least two load calculations are required
13、is in order to verify comfort (including both indoor temperature and humidity levels) at the most challenging “low ambient sensible peak ambient latent” design conditions for systems installed in humid areas as specified herein; 2-1.1 Heating Load Calculations. Exclude anticipated internal and solar
14、 heat gains from heating load calculations. Increase the calculated size of equipment and distribution system by up to 30 percent where necessary to compensate for morning recovery due to night setback. 2-1.2 Cooling Load Calculations. If necessary, increase the calculated size of equipment and dist
15、ribution system(s) by up to 10 percent to compensate for morning recovery due to night set forward or by up to 10 percent to compensate for unanticipated loads or changes in space usage. Limit the total combined increase above the size calculated of equipment and distribution system(s) to 15 percent
16、 total. Submit a psychometric plot of each air-conditioning system along with the calculations. Clearly identify all points in the conditioning process on the psychrometric chart and verify the sensible, the latent, and the total cooling capacity using the appropriate data from the chart. List the s
17、ensible, latent, and total capacity requirements for each cooling coil specified. For applications where reheat is required for humidity control, the capacity of the reheat will be equal to the total internal sensible heat generated in the area served. 2-2 DESIGN CONDITIONS. 2-2.1 Outdoor Design Con
18、ditions. Outdoor design conditions will be obtained at www.afccc.af.mil . 2-2.1.1 Cooling. The outdoor design temperature for comfort cooling will be the 1.0 percent dry bulb and the corresponding mean coincident wet bulb temperature. Base the selection of evaporative equipment on the 1.0 percent we
19、t bulb temperature. For applications where maintaining indoor temperature or humidity conditions is critical, the designer may use the corresponding 0.4 percent temperatures. For the selection of condensers and condensing units that will be subjected to unusually high radiation heat gain, add 5 degr
20、ees F (3 degrees C) to the dry bulb temperature specified above. 2-2.1.2 Heating. The outdoor design temperature for comfort heating will be the 99 percent dry bulb temperature. For applications where maintaining indoor temperature or humidity conditions is critical, the designer may substitute the
21、99.6 percent temperature for the 99 percent temperature. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-UFC 3-410-01FA 15 May 2003 Including change 4, January 2010 4 2-2.2 Indoor Design Conditions. 2-2.2.1 Cooling. The indoor design temperature for
22、comfort cooling will be 15 degrees F (8 degrees C) less than the 1.0 percent outdoor design temperature, but will not be lower than 75 degrees F (24 degrees C) nor higher than 78 degrees F (26 degrees C). The indoor design specific humidity will not exceed the outdoor design specific humidity; other
23、wise, the indoor design relative humidity will be 50 percent. The indoor design temperature provided by evaporative cooling or comfort mechanical ventilation will be 80 degrees F (27 degrees C); the above requirements for specific humidity do not apply where evaporative cooling is used. 2-2.2.2 Heat
24、ing. The indoor design temperature for comfort heating will be 68 degrees F (20 degrees C) in areas with low levels of physical activity and 55 degrees F (13 degrees C) in areas with moderate to high levels of physical activity. The indoor design temperature for freeze protection will be 40 degrees
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UFC341001FACHANGE42010HEATINGVENTILATINGANDAIRCONDITIONINGSUPERSEDEDARMYARMYTI81010PDF

链接地址:http://www.mydoc123.com/p-1066934.html