1、UFC 1-200-01 16 August 2010 Change 2, 28 November 2011 UNIFIED FACILITIES CRITERIA (UFC) GENERAL BUILDING REQUIREMENTS APPROVED FOR PUBLIC RELEASE; DISTRIBUTION UNLIMITED Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-UFC 1-200-01 16 August 2010 Cha
2、nge 2, 28 November 2011 UNIFIED FACILITIES CRITERIA (UFC) GENERAL BUILDING REQUIREMENTS Any copyrighted material included in this UFC is identified at its point of use. Use of the copyrighted material apart from this UFC must have the permission of the copyright holder. U.S. ARMY CORPS OF ENGINEERS
3、NAVAL FACILITIES ENGINEERING COMMAND (Preparing Activity) AIR FORCE CIVIL ENGINEER SUPPORT AGENCY Record of Changes (changes are indicated by 1 . /1/) Change No. Date Location 1 7-19-2011 Throughout document: Applicability has been revised to include non-permanent facilities in support of military o
4、perations. The terms “Building Official“ and “Authority Having Jurisdiction“ have been expanded and clarified. DOD use of references for accessibility in the ABA have been clarified. Target publication dates for criteria guidance that are presently in production have been updated. Additional require
5、ments and references for Munitions and Explosives facilities and Sensitive Compartmented Information Facilities have been added. New explanations for levels of construction have been added. 2 11-28-2011 Revision summary sheet; paragraph 1.4: Administration and Enforcement has been changed. Target pu
6、blication dates for criteria guidance that are presently in production have been updated. This UFC supersedes UFC 1-200-01, dated 27 November 2007, including change 2, implemented 27 January 2010. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-UFC 1
7、-200-01 16 August 2010 Change 2, 28 November 2011 FOREWORD The Unified Facilities Criteria (UFC) system is prescribed by MIL-STD-3007 and provides planning, design, construction, sustainment, restoration, and modernization criteria, and applies to the Military Departments, the Defense Agencies, and
8、the DoD Field Activities in accordance with USD(AT U.S. Navy, NAVFACENGCOM HQ Code CHE; U.S. Marine Corps, HQMC Code LFF-1; and U.S. Air Force, HQ AFCESA/CEO. The enforcement of the codes and standards as they pertain to facility projects can be delegated to the local Component Offices Chief Enginee
9、rs Technical Representative at the discretion of the components aforementioned office. /2/Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-UFC 1-200-01 16 August 2010 Change 2, 28 November 2011 3 CHAPTER 2 - MODIFICATIONS TO THE INTERNATIONAL BUILDING
10、 CODE (IBC) 2-1 CHAPTER 1 ADMINISTRATION Use Sections 101, 102, 110, and 112 of IBC Chapter 1. 2-2 CHAPTER 2 DEFINITIONS Use IBC Chapter 2. Definitions apply to terms used in the model code and are not intended to replace definitions and terms in military documents. 2-3 CHAPTER 3 USE AND OCCUPANCY C
11、LASSIFICATION Use IBC Chapter 3 and UFC 3-600-01. If any conflict occurs between IBC Chapter 3 and UFC 3-600-01, the requirements of UFC 3-600-01 take precedence. 2-4 CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY Use UFC 3-600-01 in lieu of IBC Chapter 4. 2-5 CHAPTER 5 GENERAL B
12、UILDING HEIGHTS AND AREAS Use IBC Chapter 5. The building area for funding and planning purposes may be calculated differently than the method defined in IBC Chapter 5. 2-6 CHAPTER 6 TYPES OF CONSTRUCTION Use IBC Chapter 6 and UFC 3-600-01. If any conflict occurs between IBC Chapter 6 and UFC 3-600-
13、01, the requirements of UFC 3-600-01 take precedence. 2-7 CHAPTER 7 FIRE-RESISTANCE-RATED CONSTRUCTION Use IBC Chapter 7 and UFC 3-600-01. If any conflict occurs between IBC Chapter 7 and UFC 3-600-01, the requirements of UFC 3-600-01 take precedence. 2-8 CHAPTER 8 INTERIOR FINISHES Use UFC 3-600-01
14、 in lieu of IBC Chapter 8. 2-9 CHAPTER 9 FIRE PROTECTION SYSTEMS Use UFC 3-600-01 in lieu of IBC Chapter 9. 2-10 CHAPTER 10 MEANS OF EGRESS Use UFC 3-600-01 in lieu of IBC Chapter 10. 2-11 CHAPTER 11 ACCESSIBILITY Provided by IHSNot for ResaleNo reproduction or networking permitted without license f
15、rom IHS-,-,-UFC 1-200-01 16 August 2010 Change 2, 28 November 2011 4 Use the ABA Accessibility Standard for Department of Defense Facilities as adopted by the Deputy Secretary of Defense memorandum dated October 31, 2008, in lieu of IBC Chapter 11. 1 Where the ABA references the IBC 2000-3 and suppl
16、ements, the latest version of the IBC is acceptable when it meets or exceeds the ABA requirements./1/ 2-12 CHAPTER 12 INTERIOR ENVIRONMENT Use IBC Chapter 12, except as modified below: 2-12.1 Delete paragraph 1204.1, including the exception, and replace with the following: “1204.1 Use the applicable
17、 Unified Facilities Criteria and individual military service standards for temperature control criteria.” 2-12.2 For Navy and Marine Corps bachelor housing facilities, delete paragraphs 1207.2, 1207.3, 1208.3 and 1208.4, and use UFC 4-721-10 for air-borne and structure-borne sound transmission crite
18、ria, for minimum room sizes, and for dwelling unit criteria. 2-13 CHAPTER 13 ENERGY EFFICIENCY Use UFC 3-400-01 in lieu of IBC Chapter 13. 2-14 CHAPTER 14 EXTERIOR WALLS Use IBC Chapter 14. 2-15 CHAPTER 15 ROOF ASSEMBLIES AND ROOFTOP STRUCTURES Use IBC Chapter 15. 2-16 CHAPTER 16 STRUCTURAL DESIGN U
19、se IBC Chapter 16 as modified by UFC 3-301-01. Use IBC Chapter 16 and UFC 3-310-04 for seismic design. 2-17 CHAPTER 17 STRUCTURAL TESTS AND INSPECTIONS Use IBC Chapter 17 as modified by UFC 3-301-01. 2-17.1 In Paragraph 1704.1 General, add the following after the first paragraph: “When the construct
20、ion contractor is required by the Government to provide special inspections as part of his work, the contractor shall retain third-party quality assurance agencies to conduct the special inspections required by the IBC. The inspecting agency shall provide reports of the special inspections directly
21、to the government.” 2-18 CHAPTER 18 SOILS AND FOUNDATIONS Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-UFC 1-200-01 16 August 2010 Change 2, 28 November 2011 5 Use IBC Chapter 18 as modified by UFC 3-301-01. For Navy and Marine Corps facilities, a
22、lso use UFC 3-220-01N. 2-19 CHAPTER 19 CONCRETE Use IBC Chapter 19 as modified by UFC 3-301-01. 2-20 CHAPTER 20 ALUMINUM Use IBC Chapter 20. 2-21 CHAPTER 21 MASONRY Use IBC Chapter 21 as modified by UFC 3-301-01. 2-22 CHAPTER 22 STEEL Use IBC Chapter 22 as modified by UFC 3-301-01. 2-23 CHAPTER 23 W
23、OOD Use IBC Chapter 23. 2-24 CHAPTER 24 GLASS AND GLAZING Use IBC Chapter 24. 2-25 CHAPTER 25 GYPSUM BOARD AND PLASTER Use IBC Chapter 25. 2-26 CHAPTER 26 PLASTIC Use IBC Chapter 26. 2-27 CHAPTER 27 ELECTRICAL Use IBC Chapter 27 and the following: 1. Use UFC 3-501-01 for general electrical requireme
24、nt criteria. 2. Use UFC 3-520-01 for interior electrical systems criteria. 3. Use UFC 3-530-01 for interior and exterior lighting and controls criteria. 4. Use UFC 3-550-01 for exterior power distribution systems criteria. 5. Use UFC 3-560-01 for electrical safety and electrical O to prevent unautho
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UFC120001CHANGE22011GENERALBUILDINGREQUIREMENTSPDF

链接地址:http://www.mydoc123.com/p-1066911.html