SAE AS 5692 4-2012 ARC FAULT CIRCUIT BREAKER C AIRCRAFT TRIP FREE 25 TO 35 AMP TYPE 1《电弧故障断路器 1型25至35 AMP的自由释放的飞机》.pdf
《SAE AS 5692 4-2012 ARC FAULT CIRCUIT BREAKER C AIRCRAFT TRIP FREE 25 TO 35 AMP TYPE 1《电弧故障断路器 1型25至35 AMP的自由释放的飞机》.pdf》由会员分享,可在线阅读,更多相关《SAE AS 5692 4-2012 ARC FAULT CIRCUIT BREAKER C AIRCRAFT TRIP FREE 25 TO 35 AMP TYPE 1《电弧故障断路器 1型25至35 AMP的自由释放的飞机》.pdf(5页珍藏版)》请在麦多课文档分享上搜索。
1、AEROSPACE STANDARD ARC FAULT CIRCUIT BREAKER AIRCRAFT, TRIP FREE, 25 TO 35 AMP, TYPE 1 AS5692/4Copyright 2012 SAE International All rights reserved. No part of this publication may be reproduced, stored in a retrieval system or transmitted, in any form or by any means, electronic, mechanical, photoc
2、opying, recording, or otherwise, without the prior written permission of SAE. TO PLACE A DOCUMENT ORDER: Tel: 877-606-7323 (inside USA and Canada) Tel: +1 724-776-4970 (outside USA) Fax: 724-776-0790 Email: CustomerServicesae.org SAE WEB ADDRESS: http:/www.sae.org ISSUED 2012-03THIRD ANGLE PROJECTIO
3、N CUSTODIAN: AE-8B1 FEDERAL SUPPLY CLASS 5925 AS5692/4SHEET 1 OF 5PROCUREMENT SPECIFICATION: AS5692SAE Technical Standards Board Rules provide that: “This report ispublishedby SAE toadvance thestate of technicalandengineering sciences. Theuse ofthis report is entirely voluntary, andits applicability
4、 and suitability forany particular use,including any patent infringement arising therefrom, isthe soleresponsibilityofthe user.”SAE reviews eachtechnicalreport at least every five years at which time itmay berevised, reaffirmed, stabilized, orcancelled. SAE invites yourwrittencomments andsuggestions
5、. SAE values your input. To provide feedbackon this Technical Report, please visit http:/www.sae.org/technical/standards/AS5692/4RATIONALE THIS DOCUMENT IS CREATED TO ALLOW PROCUREMENT OF AFCBS THAT MEET THE REQUIREMENTS OF THIS DRAWING AND THE BASE DOCUMENT AS5692. THE REQUIREMENTS FOR ACQUIRING TH
6、E PRODUCT(S) DESCRIBED HEREIN SHALL CONSIST OF THIS SPECIFICATION SHEET AND THE LATEST ISSUE OF AS5692. FIGURE 1 - CIRCUIT BREAKER CONFIGURATIONS AND DIMENSIONS .705 .353 AEROSPACE STANDARD AS5692/4SHEET 2 OF 5ARC FAULT CIRCUIT BREAKER AIRCRAFT, TRIP FREE, 25 TO 35 AMP, TYPE 1 FIGURE 1 - CIRCUIT BRE
7、AKER CONFIGURATIONS AND DIMENSIONS (CONTD)AEROSPACE STANDARD AS5692/4SHEET 3 OF 5ARC FAULT CIRCUIT BREAKER AIRCRAFT, TRIP FREE, 25 TO 35 AMP, TYPE 1 TABLE 1 - ELECTRICAL AND MECHANICAL CHACTERISTICS DASHNO. NOMINAL AMPERAGE RATING(A) VOLTAGE DROP MAX (V) WEIGHT MAX (LBS) OPERATING FORCE MAX. (LBS) E
8、NDURANCE CYCLES MECH NO LOADCYCLES RESISTIVE INDUCTIVE PULLOUT RESET AC AC 25 25 0.25 .095 .75 6.0 1.2 -8.0 1/5000 1/2500 10 000 30 30 0.25 35 35 0.25 1/ 400 HZ 115/200 VOLT SYSTEM, TESTED AT 120 5 VOLTS 380-420 HZ 2/ TABLE 2 - DETAIL CALIBRATION REQUIREMENTS NOMINAL AMPERAGE RATING(A) OVERLOAD TRIP
9、 TIME IN SECONDS AT PERCENT RATED CURRENT 55 to +85 CAMBIENT EFFECT ON CALIBRATION AT PERCENT RATED CURRENT 200% 500% 1000% +25 C +85 C -55 C115% 145% 100% 145% 115% 170% 251.5 to 50 .15 to 3.0 .035 to 0.8MUST HOLD 1HOURMIN MUST TRIP 1 HOUR MAXMUST HOLD 1HOURMIN MUST TRIP 1 HOUR MAXMUST HOLD 1HOURMI
10、N MUST TRIP 1 HOUR MAX3035AMBIENT TOLERANCE +/-2 C 2/SEE TABLE 5 FOR ADDITIONAL CALIBRATION REQUIREMENTS TABLE 3- INTERRUPTING CAPACITY (AMPERES) REQUIREMENTS NOMINAL AMPERAGE RATING(A) TEST DESIGNATION PER AS 5692 A B 251000 1000 3035TABLE 4- ENVIRONMENTAL PERFORMANCE MAX. OPERATING ALTITUDE 70 000
11、 FEET INTERMITTENT HIGH TEMPERATURE 115 OC FOR 5 MINUTES MAXIMUM. (SEE NOTE 14) OPERATING AMBIENT TEMPERATURE RANGE (-)55 oC (+)85 oCVIBRATION IN ACCORDANCE WITH AS5692 SINE - REQUIRED HIGH SINE REQUIRED RANDOM REQUIRED LEVEL D SHOCK 50G, MIL-STD-202, METHOD 213, CONDITION A ACCELERATION 10G AEROSPA
12、CE STANDARD AS5692/4SHEET 4 OF 5ARC FAULT CIRCUIT BREAKER AIRCRAFT, TRIP FREE, 25 TO 35 AMP, TYPE 1 TABLE 5 TEST CONDITIONS Minimum Level of Ultimate TripMUST HOLD OPERATING ALTITUDE TEMP. % RATED CURRENT SIMULATEDCONDITION 15 MINUTES 50 000 FEET (-)55 OC 115% COLD START AND OPERATE30 MINUTES 50 000
13、 FEET (+)80 OC 100% HOT TRANSIENT OPERATION60 MINUTES 50 000 FEET (+)36 OC 100% ALTITUDE HOT OPERATION 2 MINUTES 70 000 FEET (+)49 OC 100% HIGH ALTITUDE TRANSIENT THESE TESTS SHALL BE PERFORMED WITH 36 INCH WIRES CONFORMING TO AS22759/4 OR MS25471 AND TERMINATION AS SPECIFIED BELOW. ALL OTHER TESTS
14、CALLING FOR WIRE LEADS SHALL BE PERFORMED AS SPECIFIED IN AS5692 NOMINAL CURRENT RATING (AMPERES)WIRE SIZE (AWG) INSULATED TERMINAL LUG (MS PART NO.) 25 12 MS25036-112 30 10 -11235 10 -112 REQUIREMENTS ALL REQUIREMENTS SHALL CONSIST OF THIS SPECIFICATION AND THE LATEST ISSUE OF AS5692 : 1. DESIGN CI
15、RCUIT BREAKERS SHALL BE DESIGNED IN ACCORDANCE WITH FIGURES 1 AND 2 1. ALL QUALIFICATION INSPECTION TESTS REQUIRED BY AS5692 SHALL BE PERFORMED EXCEPT FOR THE FOLLOWING CHANGES. TABLE V INITIAL QUALIFICATION TESTING SHALL INCLUDE AN ADDITIONAL GROUP WITH 5 SAMPLES OF EACH RATING. EACH OF THESE SAMPL
16、ES SUBJECTED TO THE TESTS IN TABLE V AND SHALL NOT BE SUBJECTED TO TEST GROUP I. THESE TESTS SHALL BE PERFORMED AS FOLLOWS: AFTER THE CIRCUIT BREAKER HAS BEEN CARRYING THE MINIMUM LIMIT OF ULTIMATE TRIP CURRENT FOR THE SPECIFIED TEST CONDITIONS, THE CURRENT SHALL BE INCREASED AT A RATE OF 2% OF CURR
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- SAEAS569242012ARCFAULTCIRCUITBREAKERCAIRCRAFTTRIPFREE25TO35AMPTYPE1 电弧 故障 断路器 25 35 AMP 自由 释放 飞机 PDF

链接地址:http://www.mydoc123.com/p-1024924.html