SAE AS 5692 2-2007 ARC FAULT CIRCUIT BREAKER - AIRCRAFT TRIP FREE 1-20 AMP TYPE I《航空器用I型电流1~20A自动断路电弧故障断电器》.pdf
《SAE AS 5692 2-2007 ARC FAULT CIRCUIT BREAKER - AIRCRAFT TRIP FREE 1-20 AMP TYPE I《航空器用I型电流1~20A自动断路电弧故障断电器》.pdf》由会员分享,可在线阅读,更多相关《SAE AS 5692 2-2007 ARC FAULT CIRCUIT BREAKER - AIRCRAFT TRIP FREE 1-20 AMP TYPE I《航空器用I型电流1~20A自动断路电弧故障断电器》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、 AEROSPACE STANDARD ARC FAULT CIRCUIT BREAKER - AIRCRAFT, TRIP FREE, 1-20 AMP, TYPE I AS5692/2Copyright 2014 SAE International All rights reserved. No part of this publication may be reproduced, stored in a retrieval system or transmitted, in any form or by any means, electronic, mechanical, photoco
2、pying, recording, or otherwise, without the prior written permission of SAE. TO PLACE A DOCUMENT ORDER: Tel: 877-606-7323 (inside USA and Canada) Tel: +1 724-776-4970 (outside USA) Fax: 724-776-0790 Email: CustomerServicesae.org SAE WEB ADDRESS: http:/www.sae.org ISSUED 2007-01REAFFIRMED 2014-09THIR
3、D ANGLE PROJECTION CUSTODIAN: AE-8/AE-8B1 FEDERAL SUPPLY CLASS 5925 AS5692/2 SHEET 1 OF 4 PROCUREMENT SPECIFICATION: AS5692SAE Technical Standards Board Rules provide that: “This report ispublishedby SAE toadvance thestate of technicalandengineeringsciences.The useofthis reportisentirelyvoluntary, a
4、ndits applicability and suitability forany particular use,including any patent infringement arising therefrom, isthe soleresponsibilityofthe user.”SAE reviews eachtechnicalreport at least every five years at which time itmay berevised,reaffirmed, stabilized, orcancelled. SAE invites yourwrittencomme
5、nts andsuggestions. SAE values your input. To provide feedbackon this Technical Report, please visit http:/www.sae.org/technical/standards/PRODCODE RATIONALE AS5692/2 HAS BEEN REAFFIRMED TO COMPLY WITH THE SAE FIVE-YEAR REVIEW POLICY. THE REQUIREMENTS FOR PROCURING THE PRODUCT DESCRIBED HEREIN SHALL
6、 CONSIST OF THIS SPECIFICATION SHEET AND THE LATEST ISSUE OF: SAE AS5692. FIGURE 1 REF. LINE A REPRESENTS THE LOCATION OF THE INTERFACE BETWEEN THE AFCB AND THE PANEL. DIMENSIONS REFERENCED FROM “REF. LINE A” ARE THE DIMENSION FROM THE BACK OF THE PANEL TO THE DIMENSIONED FEATURE. AEROSPACE STANDARD
7、 AS5692/2 SHEET 2 OF 4 ARC FAULT CIRCUIT BREAKER - AIRCRAFT, TRIP FREE, 1-20 AMP, TYPE I TABLE 1 - ELECTRICAL AND MECHANICAL CHACTERISTICS ENDURANCE CYCLES OPERATING FORCE MAX (LB) RESISTIVE INDUCTIVE DASH NO. NOMINAL AMPERAGE RATING (A) VOLTAGE DROP MAX (V) WEIGHT MAX (LB) PULLOUT RESET AC AC MECH
8、NO LOAD CYCLES 1 1 1.10 1- 1.5 (1-) 0.80 2 2 0.75 2- 2.5 (2-) 0.70 3 3 0.55 4 4 0.45 5 5 0.35 7- 7.5 (7-) 0.30 10 10 0.28 15 15 0.25 20 20 0.25 .090 .75-5 1.2-8 1/ 5,000 1/ 2,500 10,000 1/ 115/200 VOLT 400 HZ SYSTEM, TESTED AT 120 5 VOLTS 380-420 HZ. TABLE 2 - DETAIL CALIBRATION REQUIREMENTS OVERLOA
9、D TRIP TIME IN SECS AT PERCENT RATED CURRENT 25 C AMBIENT EFFECT ON CALIBRATION AT PERCENT RATED CURRENT +25 C +71 C -55 C NOMINAL AMPERAGE RATING (A) 200% 500% 1000% 115% 138% 90% 138% 115% 165% 1 1- 2 2- 3 4 5 7- 10 15 20 1.5 TO 40 0.15 TO 3.0 0.35 TO 0.80 MUST HOLD - 1 HOURMIN MUST TRIP - 1 HOUR
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- SAEAS569222007ARCFAULTCIRCUITBREAKERAIRCRAFTTRIPFREE120AMPTYPEI 航空 器用 电流 20 自动 断路 电弧 故障 断电 PDF

链接地址:http://www.mydoc123.com/p-1024922.html