REG NASA-LLIS-6776-2012 Lessons Learned Triggering an Office Fire Alarm Shut Down an Adjacent Data Center.pdf
《REG NASA-LLIS-6776-2012 Lessons Learned Triggering an Office Fire Alarm Shut Down an Adjacent Data Center.pdf》由会员分享,可在线阅读,更多相关《REG NASA-LLIS-6776-2012 Lessons Learned Triggering an Office Fire Alarm Shut Down an Adjacent Data Center.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Public Lessons Learned Entry: 6776 Lesson Info: Lesson Number: 6776 Lesson Date: 2012-09-25 Submitting Organization: JPL Submitted by: David Oberhettinger Subject: Triggering an Office Fire Alarm Shut Down an Adjacent Data Center Abstract: A sprinkler head failure in office spaces triggered a power
2、shutdown in an adjacent data center during non-office hours. Assure that Center security and facilities organizations are prepared to respond appropriately to emergencies. Assess the need for major data centers to be equipped with an isolated fire alarm/suppression system that will not be triggered
3、by alarms originating in the buildings non-critical spaces. Description of Driving Event: On August 26, 2011, a fire suppression sprinkler head leaked and then failed in Building 600 at the NASA/Caltech Jet Propulsion Laboratory (JPL), inundating several office cubicles. The initial leak was reporte
4、d earlier in the day to the JPL Office of Protective Services (OPS), OPS contacted the building owner, and a maintenance crew was responding when the sprinkler head triggered the full water release. The impact of the water damage was minor. However, the affected office space shares the fire alarm sy
5、stem with an adjacent data center that, among other activities, supported Mars Science Laboratory (MSL) Assembly, Test, and Launch Operations (ATLO). There was no water release in the data center, but it was believed that the fire alarm system was programmed to shut down power to the data center unl
6、ess the shutdown was manually countermanded within ten minutes. The data center was not staffed because August 26 was an RDO*, the security guard arrived after the ten-minute period had elapsed, and the data center suffered a power outage. Building 600 is one of the few JPL buildings that is leased
7、from a private owner. Although the procedure for placing the data center electrical system in bypass is posted in the electrical room of the data center, subsequent investigation found that the shutdown was immediate: there is no ten-minute delay in triggering the power shutdown after the fire alarm
8、 is triggered. JPL was misinformed, and such a delay is not compatible with the fire code. To prevent a recurrence of this incident, JPL installed a double-interlock, preaction, fire suppression system to replace the existing system in the Building 600 data center. Preaction systems are suitable for
9、 water sensitive environments like data centers because (until a valve is electrically activated) they contain no water in the sprinkler piping so a sprinkler head failure does not release water. The double-interlock feature prevents flow of water until both a sprinkler head and a separate detector
10、are triggered simultaneously. (Triggering only one of the two devices will produce an alarm, but no water flow into the system.) Because this fire suppression system is separate and isolated from the system in the Building 600 office space, an alarm in the office space will not trigger an electrical
11、 shutdown in the data center. *Most JPL personnel work a schedule that allows them an additional day off work every other Friday, and August 26, 2011 was such a Regular Day Off (RDO). References: 1. “B600 Power Failure,“ Incident Surprise Anomaly Report No. 49896, NASA/Caltech Jet Propulsion Laborat
12、ory, August 30, 2011. 2. “DNS Server Outage Caused Loss of Uplink In MSTB During ORT2,“ Incident Surprise Anomaly Report No. 49699, NASA/Caltech Jet Propulsion Laboratory, August 11, 2011. Lesson(s) Learned: Electrical outages in data centers and other critical facilities that are triggered in error
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- REGNASALLIS67762012LESSONSLEARNEDTRIGGERINGANOFFICEFIREALARMSHUTDOWNANADJACENTDATACENTERPDF

链接地址:http://www.mydoc123.com/p-1019551.html