PAS 121-2007 Specification for active nfire curtain barrier nassemblies and active nfire curtain barrier nassemblies with smoke nrating《带有排烟等级的活动屏蔽挡火墙组装件和活动挡火墙组装件的规范》.pdf
《PAS 121-2007 Specification for active nfire curtain barrier nassemblies and active nfire curtain barrier nassemblies with smoke nrating《带有排烟等级的活动屏蔽挡火墙组装件和活动挡火墙组装件的规范》.pdf》由会员分享,可在线阅读,更多相关《PAS 121-2007 Specification for active nfire curtain barrier nassemblies and active nfire curtain barrier nassemblies with smoke nrating《带有排烟等级的活动屏蔽挡火墙组装件和活动挡火墙组装件的规范》.pdf(42页珍藏版)》请在麦多课文档分享上搜索。
1、PAS 121:2007Specification for active fire curtain barrier assemblies and active fire curtain barrier assemblies with smoke ratingICS 13.220.20NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWPUBLICLY AVAILABLE SPECIFICATIONLicensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 0
2、6/12/2007 07:10, Uncontrolled Copy, (c) BSIPublishing and copyright informationThe BSI copyright notice displayed in this document indicates when the document was last issued. BSI 2007ISBN 978 0 580 60132 3Amendments issued since publicationAmd. no. Date Text affectedPAS 121:2007Licensed Copy: Wang
3、Bin, ISO/EXCHANGE CHINA STANDARDS, 06/12/2007 07:10, Uncontrolled Copy, (c) BSI BSI 2007 iPAS 121:2007ContentsForeword iii0 Introduction 11 Scope 22 Normative references 33 Terms and definitions 44 Product requirements 65 Performance requirements and classifications 186 Installation information 237
4、Maintenance information 238 Marking and labelling 24AnnexesAnnex A (informative) Building management 25Annex B (normative) General testing requirements 25Annex C (normative) Test method for reliability and response time of the product and the durability of materials 27Annex D (normative) Test method
5、 for the determination of the fire resistance performance of fire curtain barrier assemblies 28Annex E (informative) An engineered approach to using insulating zones 32Annex F (informative) Thermal limits Human factors 33Bibliography 34List of figuresFigure 1 Protection of side retention guide 7Figu
6、re 2 Overlapping and conjoining of active fire curtain barrier assemblies Typical example 20Figure D.1 Orientation of test specimen 29List of tablesTable 1 Overview of typical barrier test specification 8Table 2 Initiation of deployment 10Table 3 Applications, method of deployment and initiation 11T
7、able 4 Operation of barrier when in operational position 13Table 5 Warning systems 14Table 6 Number of cycles for testing reliability and durability 18Table A.1 Maintenance testing of active fire curtain barrier assemblies 25Summary of pagesThis document comprises a front cover, an inside front cove
8、r, pages i to iv, pages 1 to 35 and a back cover.Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 06/12/2007 07:10, Uncontrolled Copy, (c) BSIPAS 121:2007ii BSI 2007 This page deliberately left blankLicensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 06/12/2007 07:10, Uncontrolled Copy, (c)
9、 BSI BSI 2007 iiiPAS 121:2007ForewordPublishing informationThis Publicly Available Specification was published by BSI and came into effect on 31 August 2007.Acknowledgement is given to the following organizations that were involved in the development of this specification: Bodycote warringtonfire Ch
10、iltern International Fire City of Westminster Building Control International Fire Consultants Royal Borough of Kensington b) barriers remain retracted when the fire alarm system is activated and only deploy upon receipt of a signal from a local smoke/heat detector. In these circumstances, the only f
11、ire curtain barrier assemblies to deploy are those where fire or smoke are in the vicinity;c) barriers remain retracted when the fire alarm system is activated for a predetermined time to allow for evacuation before deploying fully;d) barriers move to given height above fixed floor level when the fi
12、re alarm system is activated and act as a smoke barrier for a predetermined time before closing fully for fire containment;e) barriers only deploy upon local detection of smoke or fire, independent of the fire alarm system such as a fusible link;f) barriers are required to remain retracted as part o
13、f a buildings smoke extraction design;g) barriers will deploy on loss of primary and auxiliary power supply.1 ScopeThis Publicly Available Specification gives requirements for design, specification, testing, installation, commissioning and maintenance of active fire curtain barrier assemblies.It is
14、applicable for use by active fire curtain barrier assemblies manufacturers, designers, specifiers, regulators and installers:a) in creating protected routes for the purpose of means of escape as an alternative to fire doors, non-load bearing walls, non-load bearing ceilings or fire shutters;b) in cr
15、eating fire separation horizontally, vertically or angled for compartmentation;c) as a method of upgrading non-fire resisting elements, e.g. in front of non-fire resisting glazing and doorsets, where required for compartmentation or protecting means of escape;d) in providing a smoke barrier in conju
16、nction with non-smoke rated doors/shutters and other products protecting openings to reduce leakage of smoke.Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 06/12/2007 07:10, Uncontrolled Copy, (c) BSI BSI 2007 3PAS 121:20072 Normative referencesThe following referenced documents are indispen
17、sable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.BS 476-22, Fire tests on building materials and structures Part 22: Methods for determination of
18、the fire resistance of non-loadbearing elements of constructionBS 476-31.1, Fire tests on building materials and structures Part 31: Methods for measuring smoke penetration through doorsets and shutter assemblies Section 1: Method of measurement under ambient temperature conditionsBS 5839-1:2002, Fi
19、re detection and fire alarm systems for buildings Part 1: Code of practice for system design, installation, commissioning and maintenanceBS 7346-6, Components for smoke and heat control systems Part 6: Specifications for cable systemsBS 8434-2, Methods of test for assessment of the fire integrity of
20、 electric cables Part 2: Test for unprotected small cables for use in emergency circuits BS EN 50200 with 930 deg flame and with water sprayBS EN 949, Windows and curtain walling, doors, blinds and shutters Determination of the resistance to soft and heavy body impact for doorsBS EN 1363-1:1999, Fir
21、e resistance tests Part 1: General requirementsBS EN 1363-2, Fire resistance tests Part 2: Alternative and additional proceduresBS EN 1364-1, Fire resistance tests for non-loadbearing Part 1: WallsBS EN 1364-2, Fire resistance tests of non-loadbearing Part 2: CeilingsBS EN 1634-1, Fire resistance te
22、sts for door and shutter assemblies Part 1: Fire doors and shuttersBS EN 1634-3, Fire resistance tests for door and shutter assemblies Part 3: Smoke control doors and shuttersBS EN 12101-1, Smoke and heat control systems Part 1: Specification for smoke barriersBS EN 12101-9, Smoke and heat control s
23、ystems Part 9: Control panels 2)BS EN 12101-10, Smoke and heat control systems Part 10: Power suppliesBS EN 13501-2:2003, Fire classification of construction products and building elements Part 2: Classification using data from fire resistance tests, excluding ventilation services2)In preparation.Li
24、censed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 06/12/2007 07:10, Uncontrolled Copy, (c) BSIPAS 121:20074 BSI 2007BS EN 14600:2005, Doorsets and openable windows with fire resisting and/or smoke control characteristics Requirements and classificationBS EN ISO 13943, Fire safety Vocabulary3 Term
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- PAS1212007SPECIFICATIONFORACTIVENFIRECURTAINBARRIERNASSEMBLIESANDACTIVENFIRECURTAINBARRIERNASSEMBLIESWITHSMOKENRATING

链接地址:http://www.mydoc123.com/p-1016536.html