1、 Errata NFPA 70National Electrical Code2014 Edition Reference: Various Errata No.: 70-14-1 The National Electrical Code Correlating Committee notes the following errors in the 2014 edition of NFPA 70, National Electrical Code. How to Use this Errata Sheet This is a list of errata to the first printi
2、ng of the 2014 NEC. 1. In Section 200.7, remove shading from the first line of the title. Add shading to “or Gray” in the second line. 2. In Table 220.3, on list item “Electric vehicle charging system branch-circuit and feeder calculations,” change the section reference to 625.41. 3. Revise the titl
3、e of Table 220.44 as follows: “Table 220.44 Demand Factors for Non-Dwelling Receptacle Loads” 4. In Section 400.4, insert as first sentence “Flexible cords and flexible cables shall conform to the description in Table 400.4.” 5. In heading above 400.30, Part II should be Part III. 6. In 422.51(A), d
4、elete “identified for portable use”. 7. Replace Section 490.48 with the following: 490.48. Substation Design, Documentation, and Required Diagram. (A) Design and Documentation. Substations shall be designed by a qualified licensed professional engineer. Where components or the entirety of the substa
5、tion are listed by a qualified electrical testing laboratory, documentation of internal design features subject to the listing investigation shall not be required. The design shall address but not be limited to the following topics and the documentation of this design shall be made available to the
6、authority having jurisdiction. (1) Clearances and exits (2) Electrical enclosures (3) Securing and support of electrical equipment (4) Fire protection (5) Safety ground connection provisions (6) Guarding live parts (7) Transformers and voltage regulation equipment (8) Conductor insulation, electrica
7、l and mechanical protection, isolation, and terminations (9) Application, arrangement, and disconnection of circuit breakers, switches, and fuses (10) Provisions for oil filled equipment (11) Switchgear (12) Surge arrestors (B) Diagram. A permanent single-line diagram of the switchgear shall be prov
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NFPA70ERTA12013NATIONALELECTRICALCODEPDF