NFPA 58 AMD 3-2013 Liquefied Petroleum Gas Code (Effective Date 11 11 2013).pdf
《NFPA 58 AMD 3-2013 Liquefied Petroleum Gas Code (Effective Date 11 11 2013).pdf》由会员分享,可在线阅读,更多相关《NFPA 58 AMD 3-2013 Liquefied Petroleum Gas Code (Effective Date 11 11 2013).pdf(2页珍藏版)》请在麦多课文档分享上搜索。
1、 Tentative Interim Amendment NFPA58 Liquefied Petroleum Gas Code 2014 Edition Reference: 5.7.4, 11.4.1.11, 11.4.1.15, and 11.13.2.8 TIA 14-3 (SC 13-10-3/TIA Log #1116) Pursuant to Section 5 of the NFPA Regulations Governing the Development of NFPA Standards, the National Fire Protection Association
2、has issued the following Tentative Interim Amendment to NFPA 58, Liquefied Petroleum Gas Code, 2014 edition. The TIA was processed by the Technical Committee on Liquefied Petroleum Gases, and was issued by the Standards Council on October 22, 2013, with an effective date of November 11, 2013. A Tent
3、ative Interim Amendment is tentative because it has not been processed through the entire standards-making procedures. It is interim because it is effective only between editions of the standard. A TIA automatically becomes a public input of the proponent for the next edition of the standard; as suc
4、h, it then is subject to all of the procedures of the standards-making process. 1. Revise 5.7.4 to read as follows: 5.7.4 Container Valves and Other Appurtenances. 5.7.4.1 Containers of 4000 gal (15.2 m3) water capacity or less shall comply with 5.7.4.1(A) through 5.7.4.1(B). (A) The following conta
5、iners shall be permitted to be equipped with external pressure relief valves: (1) Underground ASME containers (2) ASME containers originally equipped with external pressure relief valves (3) ASME containers with 125 gal (0.5 m3) water capacity or less, having a pressure relief valves integrated as p
6、art of a multiple function valve (B) Containers in other than bulk plant or industrial plant service shall be fitted with valves and other appurtenances in accordance with 5.7.8.1, Table 5.7.4.1(B), and the following: (1) and (2) unchanged. (3) Containers greater than 125 gal through 4000 gal (0.5 m
7、3through 15.2 m3) water capacity shall be provided with an actuated liquid withdrawal excess-flow valve with a connection not smaller than 34 in. NPT (19 mm) and the container connection shall not be smaller than 34 in. NPT (19 mm). (4) through (7) unchanged (8) Manual shutoff valves in vapor servic
8、e shall be equipped with one of the following: (a) An orifice between the container contents and the shutoff valve outlet, not exceeding 516 in. (8 mm) in diameter, and an approved regulator directly attached, or attached with a flexible connector, to the manual shutoff valve outlet (b) An excess-fl
9、ow valve (9) through (10) unchanged (11) Full internal pressure relief valves or flush-type full internal pressure relief valves shall be installed in multiple function valves that are used with single opening cylinders used in industrial truck service and shall have the springs and guiding mechanis
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NFPA58AMD32013LIQUEFIEDPETROLEUMGASCODEEFFECTIVEDATE11112013PDF

链接地址:http://www.mydoc123.com/p-1008727.html