NFPA 13 AMD 2-2015 Standard for the Installation of Sprinkler Systems (Effective Date 09 07 2015).pdf
《NFPA 13 AMD 2-2015 Standard for the Installation of Sprinkler Systems (Effective Date 09 07 2015).pdf》由会员分享,可在线阅读,更多相关《NFPA 13 AMD 2-2015 Standard for the Installation of Sprinkler Systems (Effective Date 09 07 2015).pdf(20页珍藏版)》请在麦多课文档分享上搜索。
1、 Page 1 of 20 Tentative Interim Amendment NFPA 13 Standard for the Installation of Sprinkler Systems 2016 Edition Reference: 2.3.1, 3.11.9, A.3.11.9, 9.3.5.12, A.9.3.5.12, A.9.3.5.12.1 and E.7 TIA 16-2 (SC 15-8-15 / TIA Log #1180) Note: Text of the TIA was issued and incorporated into the document p
2、rior to printing, therefore no separate publication is necessary. 1. Revise the reference in 2.3.1 to read as follows: 2.3.1 ACI Publications. American Concrete Institute, P.O. Box 9094, Farmington Hills, MI 48333. ACI 318-14, Building Code Requirements for Structural Concrete and Commentary, 2014.
3、ACI 355.2, Qualification of Post-Installed Mechanical Anchors in Concrete and Commentary, 2007. 2. Add a new definition on Prying Factor and corresponding annex to read as follows: 3.11.9* Prying Factor. A factor based on fitting geometry and brace angle from vertical that results in an increase in
4、tension load due to the effects of prying between the upper seismic brace attachment fitting and the structure. A. 3.11.9 Prying factors in NFPA 13 are utilized to determine the design loads for attachments to concrete. Prying is a particular concern for anchorage to concrete because the anchor may
5、fail in a brittle fashion. Page 2 of 20 3. Revise section 9.3.5.12 as follows: 9.3.5.12* Fasteners. 9.3.5.12.1 The designated angle category for the fastener(s) used in the sway brace installation shall be determined in accordance with Figure 9.3.5.12.1. Figure 9.3.5.12.1 Designation of Angle Catego
6、ry Based on Angle of Sway Brace and Fastener Orientation. 9.3.5.12.12* For individual fasteners, unless alternate allowable loads are determined and certified by a registered professional engineer, the loads determined in 9.3.5.9 shall not exceed the allowable loads provided in Tables 9.3.5.12.2(a)
7、through 9.3.5.12.2(i). Page 3 of 20 Table 9.3.5.12.2 (a) Maximum Load for Wedge Anchors in 3000 psi (207 bar) Lightweight Cracked Concrete on Metal Deck. Wedge Anchors in 3000 psi Lightweight Cracked Concrete on Metal Deck (lbs.) Diameter (in.) Embedment (in.) A B C D E F G H I Pr Pr Pr Pr Pr Pr Pr
8、Pr Pr Brace angle from vertical nullnull null nullnullCnullAnullnullnullnullnull nullDnull/A If Cr Brace angle from vertical nullnull null nullnullnullnullnullnullnullnullnullnull null nullnull/null If Cr Brace angle from vertical nullnull null nullnullDnullnullnullnullnull nullnullnullnullnullnulln
9、ull/B If Cr Brace angle from vertical nullnull null nullnullDnullnullnullnullnull nullnullnullnullnullnullnull/A If Cr Brace angle from vertical nullnull null nullnullCnullnullnull null nullDnullnullnullnullnullnull/B For designated angle category G, H and I the Applied Tension including the effect
10、of prying (Pr) is as follows: For braces acting in TENSION: Page 14 of 20 nullnull null nullDBnull/nullnullnullnull For braces acting in COMPRESSION: Pr null nullnullnullnull/nullnullnullnull The lightweight concrete anchor tables 9.3.5.12.2(a) and (b) were based on sand lightweight concrete which r
11、epresents a conservative assumption for the strength of the material. For seismic applications cracked concrete was assumed. 6. Add a new Annex E.7 to read as follows: E.7 Allowable Loads for Concrete Anchors. The following sections provide step-by-step examples of the procedures for determining the
12、 allowable loads for concrete anchors as they are found in Tables 9.3.5.12.2(a) through 9.3.5.12.2(f). Tables 9.3.5.12.2(a) through (f) were developed using the prying factors found in Table E.7(a) and the representative strength design seismic shear and tension values for concrete anchors found in
13、Table E.7(b). Table E.7(a) Prying Factors for Table 9.3.5.12.2(a) through Table 9.3.5.12.2(f) Concrete Anchors Pr Range Fig. 9.3.5.12.1 Designated Angle Category A B C D E F G H I Lowest 2.0 1.1 0.7 1.2 1.1 1.1 1.4 0.9 0.8 Low 3.5 1.8 1.0 1.7 1.8 2.0 1.9 1.3 1.1 High 5.0 2.5 1.3 2.2 2.5 2.9 2.4 1.7
14、1.4 Highest 6.5 3.2 1.6 2.7 3.2 3.8 2.9 2.1 1.7 Page 15 of 20 Table E.7(b)Representative Strength Design Seismic Shear and Tension Values Used for Concrete Anchors Wedge Anchors in 3000 psi LW Sand Concrete on Metal Deck Anchor Dia. (in.) Nominal Embedment (in.) LRFD Tension (lbs.) LRFD Shear (lbs.)
15、 3/8 2 573 11721/2 2.375 804 1616 5/8 3.125 1102 1744 Wedge Anchors in 3000 psi LW Sand Concrete Anchor Dia. (in.) Nominal Embedment (in.) LRFD Tension (lbs.) LRFD Shear (lbs.) 3/8 2 637 5501/2 3.625 871 745 5/8 3.875 1403 1140 3/4 4.125 1908 1932 Wedge Anchors in 3000 psi NW Concrete Anchor Dia. (i
16、n.) Nominal Embedment (in.) LRFD Tension (lbs.) LRFD Shear (lbs.) 3/8 2 1063 9171/2 3.625 2639 2052 5/8 3.875 3004 2489 3/4 4.125 3179 3206 Wedge Anchors in 4000 psi NW Concrete Anchor Dia. (in.) Nominal Embedment (in.) LRFD Tension (lbs.) LRFD Shear (lbs.) 3/8 2 1226 10881/2 3.625 2601 2369 5/8 3.8
17、75 3469 2586 3/4 4.125 3671 3717 Page 16 of 20 Wedge Anchors in 6000 psi NW Concrete Anchor Dia. (in.) Nominal Embedment (in.) LRFD Tension (lbs.) LRFD Shear (lbs.) 3/8 2.25 1592 1322 1/2 3.625 3186 2902 5/8 3.875 4249 3167 3/4 4.125 4497 4553 Undercut Anchors in 3000 psi NW Concrete Anchor Dia. (in
18、.) Nominal Embedment (in.) LRFD Tension (lbs.) LRFD Shear (lbs.) 3/8 5 4096 18671/2 7 5322 2800 5/8 9.5 6942 56753/4 12 10182 9460 E.7.1 Procedure for Selecting a Wedge Anchor Using Tables 9.3.5.12.2(a) through 9.3.5.12.2(f). Step 1. Determine the ASD Horizontal Earthquake Load Fpw. Step 1a. Calcula
19、te the weight of the water-filled pipe within the Zone of Influence of the brace. Step 1b. Find the applicable Seismic Coefficient Cp in Table 9.3.5.9.3 Step 1c. Multiply the Zone of Influence weight by Cp to determine the ASD Horizontal Earthquake Load Fpw. Step 2. Select a concrete anchor from Tab
20、les 9.3.5.12.2(a) through 9.3.5.12.2(f) with a maximum load capacity that is greater than the calculated horizontal earthquake load Fpw from Step 1. Step 2a. Locate the table for the applicable concrete strength. Step 2b. Find the column in the selected table for the applicable designated angle cate
21、gory (A thru I) and the appropriate prying factor Pr range. Step 2c. Scan down the category column to find a concrete anchor diameter, embedment depth, and maximum load capacity that is greater than the calculated horizontal earthquake load Fpw from Step 1. (ALTERNATIVE) Step 2. As an alternative to
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NFPA13AMD22015STANDARDFORTHEINSTALLATIONOFSPRINKLERSYSTEMSEFFECTIVEDATE09072015PDF

链接地址:http://www.mydoc123.com/p-1008267.html