NEMA SG 10-2013 Guide to OSHA and NFPA 70E Safety Requirements When Servicing and Maintaining Medium-Voltage Switchgear Circuit Breakers and Medium-Voltage Controllers Rated above .pdf
《NEMA SG 10-2013 Guide to OSHA and NFPA 70E Safety Requirements When Servicing and Maintaining Medium-Voltage Switchgear Circuit Breakers and Medium-Voltage Controllers Rated above .pdf》由会员分享,可在线阅读,更多相关《NEMA SG 10-2013 Guide to OSHA and NFPA 70E Safety Requirements When Servicing and Maintaining Medium-Voltage Switchgear Circuit Breakers and Medium-Voltage Controllers Rated above .pdf(21页珍藏版)》请在麦多课文档分享上搜索。
1、NEMA Standards PublicationNational Electrical Manufacturers AssociationNEMA SG 10-2013Guide to OSHA and NFPA 70E Safety Requirements When Servicing and Maintaining Medium-Voltage Switchgear, Circuit Breakers, and Medium-Voltage Controllers Rated above 1000 VNEMA Standards Publication SG 10-2013 Guid
2、e to OSHA and NFPA 70E Safety Requirements When Servicing and Maintaining Medium-Voltage Switchgear, Circuit Breakers, and Medium-Voltage Controllers Rated above 1000 V Published by: National Electrical Manufacturers Association 1300 North 17th Street, Suite 900 Rosslyn, Virginia 22209 www.nema.org
3、2013 National Electrical Manufacturers Association. All rights, including translation into other languages, reserved under the Universal Copyright Convention, the Berne Convention for the Protection of Literacy and Artistic Works, and the International and Pan American copyright conventions. 2013 Na
4、tional Electrical Manufacturers Association NOTICE AND DISCLAIMER The information in this publication was considered technically sound by the consensus of persons engaged in the development and approval of the document at the time it was developed. Consensus does not necessarily mean that there is u
5、nanimous agreement among every person participating in the development of this document. NEMA standards and guideline publications, of which the document contained herein is one, are developed through a voluntary consensus standards development process. This process brings together volunteers and/or
6、 seeks out the views of persons who have an interest in the topic covered by this publication. While NEMA administers the process and establishes rules to promote fairness in the development of consensus, it does not write the document and it does not independently test, evaluate, or verify the accu
7、racy or completeness of any information or the soundness of any judgments contained in its standards and guideline publications. NEMA disclaims liability for any personal injury, property, or other damages of any nature whatsoever, whether special, indirect, consequential, or compensatory, directly
8、or indirectly resulting from the publication, use of, application, or reliance on this document. NEMA disclaims and makes no guaranty or warranty, express or implied, as to the accuracy or completeness of any information published herein, and disclaims and makes no warranty that the information in t
9、his document will fulfill any of your particular purposes or needs. NEMA does not undertake to guarantee the performance of any individual manufacturer or sellers products or services by virtue of this standard or guide. In publishing and making this document available, NEMA is not undertaking to re
10、nder professional or other services for or on behalf of any person or entity, nor is NEMA undertaking to perform any duty owed by any person or entity to someone else. Anyone using this document should rely on his or her own independent judgment or, as appropriate, seek the advice of a competent pro
11、fessional in determining the exercise of reasonable care in any given circumstances. Information and other standards on the topic covered by this publication may be available from other sources, which the user may wish to consult for additional views or information not covered by this publication. N
12、EMA has no power, nor does it undertake to police or enforce compliance with the contents of this document. NEMA does not certify, test, or inspect products, designs, or installations for safety or health purposes. Any certification or other statement of compliance with any health- or safety-related
13、 information in this document shall not be attributable to NEMA and is solely the responsibility of the certifier or maker of the statement. NEMA SG 10-2013 Page i 2013 National Electrical Manufacturers Association Foreword This guide was written to emphasize basic principles and guidance for safety
14、 when performing inspection, operation, and maintenance of medium-voltage switchgear, circuit breakers, and medium-voltage controllers rated above 1000 V. It also draws the readers attention to important OSHA and NFPA safety standards. Proposed or recommended revisions should be submitted to: Vice P
15、resident, Technical Services National Electrical Manufacturers Association 1300 North 17th Street, Suite 900 Rosslyn, VA 22209 This guide was developed by the Switchgear Section of the Power Equipment Division. Section approval of the guide does not necessarily imply that all section members voted f
16、or its approval or participated in its development. At the time this guide was approved, the Section was composed of the following members: ALSTOM Grid Inc.Charleroi, PA Cooper Power SystemsWaukesha, WI Eaton Inc.Pittsburgh, PA Federal PacificBristol, VA General Electric Co.Plainville, CT Hubbell Po
17、wer SystemsColumbia, SC Schneider ElectricSmyrna, TN S personal protective equipment; including arc-flash suit; insulating and shielding materials; and insulated tools and test equipment. A person can be considered qualified with respect to certain equipment and methods but still be unqualified for
18、others.” 2.2 APPROACH BOUNDARIES Refer to NFPA 70E Article 130.4 for specific requirements regarding distances from exposed energized electrical conductors and circuit parts that define approach boundaries. NEMA SG 10-2013 Page 6 2013 National Electrical Manufacturers Association Section 3 TRAINING
19、In accordance with 29 CFR 1910.332 and NFPA 70E Chapter 1, all personnel associated with maintenance or service of switchgear assemblies should be qualified. They should be trained in: a) Safety-related work practices and procedural requirements necessary to provide protection from electrical hazard
20、s b) The ability to identify and understand the relationship between electrical hazards and possible injury. c) The skill and techniques necessary to distinguish exposed energized parts from other parts of electrical equipment. d) The skills and techniques necessary to determine the nominal voltage
21、of exposed energized parts. e) Approach distances specified in 29 CFR 1910.333 and the flash protection boundary specified in NFPA 70E Chapter 1. f) Decision-making process necessary to determine the extent of the hazard and the personal protective equipment and job planning necessary to perform the
22、 task safely. Qualified persons should also be trained in and familiar with: a) Lockout/tagout procedures specified in 29 CFR 1910.147 and NFPA 70E Article 120.2. b) Proper use of and maintenance of personal protective equipment as specified in NFPA 70E Article 130.7. c) Proper use of test equipment
23、. d) Proper procedures to apply temporary protective grounds. e) Electrical equipment in general, as well as the particular model of equipment involved. NEMA SG 10-2013 Page 7 2013 National Electrical Manufacturers Association Section 4 JOB PLAN 4.1 JOB PLAN CREATION Before servicing, maintaining, o
24、r performing diagnostic routines on switchgear assemblies, a job plan in accordance with NFPA 70E Chapter 1 is required. See Appendix A for an example. Established standards and regulations related to maintenance, operation, installation, and safety, including OSHA requirements, National Electric Sa
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NEMASG102013GUIDETOOSHAANDNFPA70ESAFETYREQUIREMENTSWHENSERVICINGANDMAINTAININGMEDIUMVOLTAGESWITCHGEARCIRCUITBREAKERSANDMEDIUMVOLTAGECONTROLLERSRATEDABOVEPDF

链接地址:http://www.mydoc123.com/p-994419.html