NEMA OFP 1-2017 Protection of Receptacle Outlets in Wet Locations According to the National Electrical Code (NEC).pdf
《NEMA OFP 1-2017 Protection of Receptacle Outlets in Wet Locations According to the National Electrical Code (NEC).pdf》由会员分享,可在线阅读,更多相关《NEMA OFP 1-2017 Protection of Receptacle Outlets in Wet Locations According to the National Electrical Code (NEC).pdf(11页珍藏版)》请在麦多课文档分享上搜索。
1、NEMA Standards PublicationNational Electrical Manufacturers AssociationNEMA OFP 1-2017Protection of Receptacle Outlets in Wet LocationsAccording to the National Electrical Code (NEC)A Joint NEMA Conduit Fittings and Outlet in locations subject to saturation with water or other liquids, such as vehic
2、le washing areas; and in unprotected locations exposed to weather. 210.52(E) Outdoor Outlets. Outdoor receptacle outlets shall be installed in accordance with 210.52(E) (1) through (E) (3). Informational Note: See 210.8(A)(3). (1) One-Family and Two-Family Dwellings. For a one-family dwelling and ea
3、ch unit of a two-family dwelling that is at grade level, at least one receptacle outlet readily accessible from grade and not more than 2.0 m (6 ft.) above grade level shall be installed at the front and back of the dwelling. (2) Multifamily Dwellings. For each dwelling unit of a multifamily dwellin
4、g where the dwelling unit is located at grade level and provided with individual exterior entrance/egress, at least one receptacle outlet readily accessible from grade and not more than 2.0 m (6 ft.) above grade level shall be installed. (3) Balconies, Decks, and Porches. Balconies, decks, and porch
5、es that are attached to the dwelling unit and are accessible from inside the dwelling unit shall have at least one receptacle outlet accessible from the balcony, deck, or porch. The receptacle outlet shall not be located more than 2.0 m (612 ft) above the balcony, deck, or porch walking surface. 314
6、.15 Damp or Wet Locations. In damp or wet locations, boxes, conduit bodies, outlet box hoods, and fittings shall be placed or equipped so as to prevent moisture from entering or accumulating within the box, conduit body, or fitting. Boxes, conduit bodies, outlet box hoods, and fittings installed in
7、wet locations shall be listed for use in wet locations. Approved drainage openings not smaller than 3 mm (1/8 in.) and not larger than 6 mm (1/4 in.) in diameter shall be permitted to be installed in the field in boxes or conduit bodies listed for use in damp or wet locations. For installation of li
8、sted drain fittings, larger openings are permitted to be installed in the field in accordance with manufacturers instructions. Informational Note No. 1: For boxes in floors, see 314.27(B). Informational Note No. 2: For protection against corrosion, see 300.6. 314.23(B) Structural Mounting. An enclos
9、ure supported from a structural member or from grade shall be rigidly supported either directly or by using a metal, polymeric, or wood brace. (1) Nails and Screws. Nails and screws, where used as a fastening means, shall secure boxes by using brackets on the outside of the enclosure, or by using mo
10、unting holes in the back or in a single side of the enclosure, or they NEMA OFP 1-2017 Page 9 2017 National Electrical Manufacturers Association shall pass through the interior within 6 mm (14 in.) of the back or ends of the enclosure. Screws shall not be permitted to pass through the box unless exp
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NEMAOFP12017PROTECTIONOFRECEPTACLEOUTLETSINWETLOCATIONSACCORDINGTOTHENATIONALELECTRICALCODENECPDF

链接地址:http://www.mydoc123.com/p-994371.html