1、ATLANTIC*NAVFAC UFGS-L-15080N (August 2003)-Preparing Activity: NAVFAC LANT Superceding UFGS-L-15080N (April 2003)UNIFIED FACILITIES GUIDE SPECIFICATIONSUse for LANTNAVFACENGCOM projects onlyRevised throughout - Format changes and reference dates not indicated byCHG tags. Other revisions are indicat
2、ed by CHG tags.*SECTION 15080NMECHANICAL INSULATION08/03*NOTE: This guide specification covers the requirements for field-applied mechanical insulation for mechanical systems including heating, ventilation, and cooling (HVAC) equipment, ducts, and piping which is located within, on, under, and adjac
3、ent to buildings; and for plumbing systems.NOTE: Suggestions for improvement of this specification will be welcomed using the Navy “Change Request Forms“ subdirectory located in SPECSINTACT in Jobs or Masters under “Forms/Documents“ directory or DD Form 1426. Suggestions should be forwarded to:Atlan
4、tic DivisionNaval Facilities Engineering CommandAttention EICO1510 Gilbert StreetNorfolk, VA 23511-2699FAX: (757) 322-4416 or DSN 262-4416Email: LantDivefdlant.navfac.navy.milUse of electronic communication is encouraged.Brackets are used in the text to indicate designer choices or locations where t
5、ext must be supplied by the designer.*PART 1 GENERAL1.1 REFERENCESThe publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.SECTION 15080N Page 1Provided by IHSNot for ResaleNo reproduction
6、 or networking permitted without license from IHS-,-,-ATLANTICASTM INTERNATIONAL (ASTM)ASTM B 209 (2002a) Aluminum and Aluminum-Alloy Sheet and PlateASTM B 209M (2002a) Aluminum and Aluminum-Alloy Sheet and Plate (Metric)ASTM C 1126 (2000) Faced or Unfaced Rigid Cellular Phenolic Thermal InsulationA
7、STM C 1136 (2003) Flexible, Low Permeance Vapor Retarders for Thermal InsulationASTM C 533 (1995; R 2001) Calcium Silicate Block and Pipe Thermal InsulationASTM C 534 (2003) Preformed Flexible Elastomeric Cellular Thermal Insulation in Sheet and Tubular FormASTM C 547 (2003) Mineral Fiber Pipe Insul
8、ationASTM C 552 (2000e1) Cellular Glass Thermal InsulationASTM C 553 (2002) Mineral Fiber Blanket Thermal Insulation for Commercial and Industrial ApplicationsASTM C 591 (2001) Unfaced Preformed Rigid Cellular Polyisocyanurate Thermal InsulationASTM C 612 (2000a) Mineral Fiber Block and Board Therma
9、l InsulationASTM D 1784 (2003) Rigid Poly(Vinyl Chloride) (PVC) Compounds and Chlorinated Poly(Vinyl Chloride) (CPVC) CompoundsASTM E 84 (2003) Surface Burning Characteristics of Building Materials1.2 SYSTEM DESCRIPTIONProvide new and modify existing field-applied mechanical insulation for mechanica
10、l systems and existing insulated mechanical systems affected by the Contractors operations. Mechanical systems include heating, ventilating, and cooling equipment, ducts, and piping which is located within, on, under, and adjacent to buildings; and for plumbing systems. Obtain Contracting Officers w
11、ritten approval of each system before applying field-applied insulation. Provide new asbestos-free insulation materials.1.3 SUBMITTALS*NOTE: Where a “G“ in submittal tags follows a submittal item, it indicates Government approval for SECTION 15080N Page 2Provided by IHSNot for ResaleNo reproduction
12、or networking permitted without license from IHS-,-,-ATLANTICthat item. Add “G“ in submittal tags following any added or existing submittal items deemed sufficiently critical, complex, or aesthetically significant to merit approval by the Government. Submittal items not designated with a “G“ will be
13、 approved by the QC organization.*Submit the following in accordance with Section 01330, “Submittal Procedures.“SD-03 Product DataPiping insulation and jacketDuct insulation and jacketEquipment insulation and jacketBoiler stack insulation and jacketSD-07 CertificatesField Insulation Inspector; GSD-0
14、8 Manufacturers InstructionsPiping insulation/jacket installationDuct insulation/jacket installationEquipment insulation/jacket installationBoiler stack insulation/jacket installationSD-09 Manufacturers Field ReportsPiping insulation/jacket; G1.4 IDENTIFICATION OF NEW ASBESTOS-FREE INSULATION*NOTE:
15、Do not use for new buildings or existing buildings with no asbestos insulation.*Identify new asbestos-free insulation with “ASBESTOS-FREE“ markings spaced at maximum of 6.1 m 20 foot intervals on the insulation jacket. Indicate the limits of new asbestos-free insulation with 51 mm2 inch wide orange
16、bands with attached arrows pointing in the direction of the “ASBESTOS-FREE“ markings.PART 2 PRODUCTS2.1 PIPING INSULATION AND JACKET2.1.1 Mineral Fiber Preformed Pipe InsulationASTM C 547. Provide piping insulation jacket.SECTION 15080N Page 3Provided by IHSNot for ResaleNo reproduction or networkin
17、g permitted without license from IHS-,-,-ATLANTIC2.1.2 Rigid Cellular Phenolic Preformed Pipe InsulationASTM C 1126. Provide piping insulation jacket.2.1.3 Cellular Glass Preformed Pipe InsulationASTM C 552. Provide piping insulation jacket.2.1.4 Flexible Cellular Preformed Pipe InsulationASTM C 534
18、. Piping insulation jacket is not required.2.1.5 Polyisocyanurate InsulationASTM C 591. Provide piping insulation jacket.2.1.6 Piping Insulation JacketProvide manufacturers standard fire-retardant vapor barrier jacket. Jacket shall be suitable for painting. Provide factory prefabricated one-piece PV
19、C insulation covers and mineral fiber insulation inserts of the same thickness as piping insulation for fittings, valves, and flanges.2.1.7 Polyvinylidene Chloride Polymer Film (PVDC)ASTM C 1136. PVDC film may be used in lieu of standard piping insulation jacket. PVDC film provided shall meet or exc
20、eed the permeance of the manufacturers standard jacket2.1.8 Aluminum JacketASTM B 209MASTM B 209, Temper H14, minimum thickness of 0.41 mm 0.016 inch, with factory-applied polyethylene and kraft paper moisture barrier on inside surface. Provide smooth surface aluminum jackets for insulation outside
21、diameters less than 204 mm 8 inches. Provide corrugated surface aluminum jackets for insulation outside diameters 204 mm 8 inches and larger. Provide stainless steel bands, minimum width of 13 mm 0.5 inch. Provide factory prefabricated aluminum insulation covers for fittings, valves, and flanges.2.1
22、.9 PVC Jacket*NOTE: NOTE: Use bracketed paragraph if project site ambient design wet bulb temperature is below 21 degrees C 70 degrees F for summer design conditions, i.e., a site of low humidity. This jacket may be a Contractors choice that is provided covering mineral fiber piping insulation.*ASTM
23、 D 1784, PVC jacketing, pre-cut and curled, 20 mil thick, white UV-resistant, and flame/smoke rating of 25/50 in accordance with ASTM E 84. All joints and seams shall be solvent welded in accordance with manufacturers recommendations. Tacks and staples will not be allowed.SECTION 15080N Page 4Provid
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYUFGSL15080N2003MECHANICALINSULATION 机械 绝缘 系统 PDF

链接地址:http://www.mydoc123.com/p-984878.html