1、*USACE / NAVFAC / AFCESA / NASA UFGS-26 12 19.10 (February 2012)-Preparing Activity: NAVFAC SupersedingUFGS-26 12 19.10 (August 2011)UFGS-26 12 19.10 (November 2009)UFGS-26 12 19.10 (April 2006)UFGS-16272 (January 2006)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL date
2、d January 2012*SECTION TABLE OF CONTENTSDIVISION 26 - ELECTRICALSECTION 26 12 19.10THREE-PHASE PAD-MOUNTED TRANSFORMERS02/12PART 1 GENERAL1.1 REFERENCES1.2 RELATED REQUIREMENTS1.3 DEFINITIONS1.4 SUBMITTALS1.4.1 Government Submittal Review1.4.2 Reduced Submittal Requirements1.5 QUALITY ASSURANCE1.5.1
3、 Pad-Mounted Transformer Drawings1.5.2 Regulatory Requirements1.5.3 Standard Products1.5.3.1 Alternative Qualifications1.5.3.2 Material and Equipment Manufacturing Date1.6 MAINTENANCE1.6.1 Additions to Operation and Maintenance Data1.7 WARRANTYPART 2 PRODUCTS2.1 PRODUCT COORDINATION2.2 THREE-PHASE P
4、AD-MOUNTED TRANSFORMERS2.2.1 Compartments2.2.1.1 High Voltage, Dead-Front2.2.1.2 High Voltage, Live-Front2.2.1.3 Low Voltage2.2.2 Transformer2.2.2.1 Specified Transformer Efficiencies2.2.3 Insulating Liquid2.2.3.1 Liquid-Filled Transformer Nameplates2.2.4 Corrosion Protection2.3 WARNING SIGNS2.4 Arc
5、 Flash Warning LabelSECTION 26 12 19.10 Page 1Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-2.5 GROUNDING AND BONDING2.6 PADLOCKS2.7 CAST-IN-PLACE CONCRETE2.8 SOURCE QUALITY CONTROL2.8.1 Transformer Test Schedule2.8.2 Design Tests2.8.3 Routine and
6、Other TestsPART 3 EXECUTION3.1 INSTALLATION3.2 GROUNDING3.2.1 Grounding Electrodes3.2.2 Pad-Mounted Transformer Grounding3.2.3 Connections3.2.4 Grounding and Bonding Equipment3.3 INSTALLATION OF EQUIPMENT AND ASSEMBLIES3.3.1 Meters and Current Transformers3.4 FIELD APPLIED PAINTING3.5 WARNING SIGN M
7、OUNTING3.6 FOUNDATION FOR EQUIPMENT AND ASSEMBLIES3.6.1 Cast-In-Place Concrete3.6.2 Sealing3.7 FIELD QUALITY CONTROL3.7.1 Performance of Acceptance Checks and Tests3.7.1.1 Pad-Mounted Transformers3.7.1.2 Current Transformers3.7.1.3 Watthour Meter3.7.1.4 Grounding System3.7.1.5 Surge Arresters, Mediu
8、m- and High-Voltage3.7.2 Follow-Up Verification- End of Section Table of Contents -SECTION 26 12 19.10 Page 2Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-*USACE / NAVFAC / AFCESA / NASA UFGS-26 12 19.10 (February 2012)-Preparing Activity: NAVFAC S
9、upersedingUFGS-26 12 19.10 (August 2011)UFGS-26 12 19.10 (November 2009)UFGS-26 12 19.10 (April 2006)UFGS-16272 (January 2006)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated January 2012*SECTION 26 12 19.10THREE-PHASE PAD-MOUNTED TRANSFORMERS02/12*NOTE: This guide
10、specification covers three-phase pad-mounted transformers of the dead-front and live-front types for exterior applications.Adhere to UFC 1-300-02 Unified Facilities Guide Specifications (UFGS) Format Standard when editing this guide specification or preparing new project specification sections. Edit
11、 this guide specification for project specific requirements by adding, deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information.Remove information and requirements not required in respective project, whether or not brackets are present.Comments, s
12、uggestions and recommended changes for this guide specification are welcome and should be submitted as a Criteria Change Request (CCR).*NOTE: Use pad-mounted transformers (properly protected with bayonet type, oil-immersed, expulsion fuses in series with oil-immersed, partial-range, current-limiting
13、 fuses) for kVA ratings up to and including 1500 kVA on 5 kV systems and for kVA ratings up to and including 2500 kVA on 15, 25, and 35 kV systems.For voltages above 35 kV and in ratings above those previously indicated, this specification requires significant modifications and additional specificat
14、ion sections may need to be added on the project.The use of pad-mounted transformers with secondary SECTION 26 12 19.10 Page 3Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-currents exceeding 3000 amperes is discouraged due to the size and quantity
15、of secondary conductors. Therefore, transformers above 1000 kVA serving 208Y/120 volt loads and transformers above 2500 kVA serving 480Y/277 volt loads should be in a secondary unit substation configuration.Available fault current level and arc-flash energy become extremely hazardous at the larger k
16、VA size transformers. Designer should consider these parameters and evaluate multiple service points.*NOTE: This specification incorporates a “reduced shop drawing submittal process“ for listed manufacturers who previously satisfied reduced shop drawing submittal process requirements. This specifica
17、tion also includes unique routine and other test requirements, transformer loss certificate, transformer test schedule, and field quality control acceptance tests and reports. The preparing activity, NAVFAC LANT, has significant experience and technical expertise in these areas. If Reach-back suppor
18、t is desired, the technical representative (electrical engineer) editing this document for a specific project must contact the NAVFAC LANT Capital Improvements Electrical Engineering (Code CIEE) Office for consultation during the design stage of the project.*NOTE: Use the following related guide spe
19、cifications for power distribution equipment:-Section 26 08 00 APPARATUS INSPECTION AND TESTING-Section 26 11 13.00 20 PRIMARY UNIT SUBSTATIONS-Section 26 11 16 SECONDARY UNIT SUBSTATION-Section 26 12 19.20 SINGLE-PHASE PAD-MOUNTED TRANSFORMERS-Section 26 13 00.00 20 SF6/HIGH-FIREPOINT FLUID INSULAT
20、ED PAD-MOUNTED SWITCHGEAR-Section 26 23 00 SWITCHBOARDS AND SWITCHGEAR-Section 26 27 13.10 30 ELECTRIC METERS-Section 26 27 14.00 20 ELECTRICITY METERING-Section 33 71 01 OVERHEAD TRANSMISSION AND DISTRIBUTIONDo not use the following related guide specifications except for Army Civil Works projects.
21、 They have not been unified.-Section 26 11 14.00 10 MAIN ELECTRIC SUPPLY STATION AND SUBSTATION-Section 26 28 00.00 10 MOTOR CONTROL CENTERS, SWITCHBOARDS AND PANELBOARDS-Section 26 22 00.00 10 480-VOLT STATION SERVICE SWITCHGEAR AND TRANSFORMERSSECTION 26 12 19.10 Page 4Provided by IHSNot for Resal
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYUFGS261219102012THREEPHASEPADMOUNTEDTRANSFORMERS 三相 安装 衬垫 变压器 PDF

链接地址:http://www.mydoc123.com/p-984820.html