NAVY UFGS-21 21 01 00 20-2009 CARBON DIOXIDE FIRE EXTINGUISHING (HIGH PRESSURE)《二氧化碳消防设施(高压)》.pdf
《NAVY UFGS-21 21 01 00 20-2009 CARBON DIOXIDE FIRE EXTINGUISHING (HIGH PRESSURE)《二氧化碳消防设施(高压)》.pdf》由会员分享,可在线阅读,更多相关《NAVY UFGS-21 21 01 00 20-2009 CARBON DIOXIDE FIRE EXTINGUISHING (HIGH PRESSURE)《二氧化碳消防设施(高压)》.pdf(21页珍藏版)》请在麦多课文档分享上搜索。
1、*USACE / NAVFAC / AFCESA / NASA UFGS-21 21 01.00 20 (November 2009)-Preparing Activity: NAVFAC SupersedingUFGS-21 21 01.00 20 (April 2006)UFGS-13961N (September 1999)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated October 2009*SECTION TABLE OF CONTENTSDIVISION 21 -
2、 FIRE SUPPRESSIONSECTION 21 21 01.00 20CARBON DIOXIDE FIRE EXTINGUISHING (HIGH PRESSURE)11/09PART 1 GENERAL1.1 REFERENCES1.2 SYSTEM DESCRIPTION1.2.1 Detail Drawings1.2.2 System Calculations1.2.3 As-Built Drawings of Each System1.3 SUBMITTALS1.4 QUALITY ASSURANCE1.4.1 Qualifications of Installer1.5 S
3、PARE PARTS1.6 ELECTRICAL WORKPART 2 PRODUCTS2.1 DESIGN OF CARBON DIOXIDE FIRE EXTINGUISHING SYSTEMS2.1.1 Underfloor Total Flooding Systems2.1.2 Underfloor Total Flooding Systems Supply2.2 PIPE AND FITTINGS2.2.1 Pipe2.2.2 Threaded Fittings2.2.3 Unions2.3 PIPING ACCESSORIES2.3.1 Escutcheon Plates2.3.2
4、 Pipe Sleeves2.3.3 Pipe Hangers and Supports2.4 PRESSURE RELIEF DEVICE2.5 SYSTEM CONTROL2.5.1 Manual Control Station for Underfloor Total Flooding System2.5.2 Sequence of Operation2.5.3 Pressure-Operated Fire Alarm Switch2.5.4 Pressure-Operated Equipment Switch2.5.5 Control Panel2.5.5.1 Trouble Sign
5、als2.5.5.2 Panel SwitchesSECTION 21 21 01.00 20 Page 1Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-2.5.6 Secondary Power Supply2.5.6.1 Storage Batteries2.5.6.2 Battery Charger2.6 DETECTOR2.6.1 Open-Area (Spot-Type) Smoke Detectors2.6.1.1 Ionizatio
6、n Detectors2.6.1.2 Photoelectric Detectors2.6.2 Spot Heat Activated Detectors2.6.3 Detector Spacing and Location2.7 INHIBIT SWITCH2.8 ALARM SIGNALLING DEVICES2.8.1 Alarm Bells2.8.2 Alarm Horns2.8.3 Visual Alarms2.9 MAIN ANNUNCIATOR2.9.1 Annunciation Zones2.9.1.1 Remote Annunciator Panel2.9.1.2 Graph
7、ic Annunciator Panel2.10 AUTOMATIC SMOKE-FIRE DAMPERS2.11 SMOKE AND CARBON DIOXIDE EXHAUST SYSTEM2.12 OPERATING POWER2.13 CONDUCTOR IDENTIFICATION2.14 OPERATING INSTRUCTIONSPART 3 EXECUTION3.1 INSTALLATION3.2 PIPE AND FITTINGS3.3 PIPE HANGERS AND SUPPORTS3.4 FIELD PAINTING3.4.1 Systems in Unfinished
8、 Areas3.4.2 Systems in Other Areas3.5 FIELD QUALITY CONTROL3.5.1 Preliminary Tests3.5.2 Formal Inspection and Tests3.6 SCHEDULE- End of Section Table of Contents -SECTION 21 21 01.00 20 Page 2Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-*USACE / N
9、AVFAC / AFCESA / NASA UFGS-21 21 01.00 20 (November 2009)-Preparing Activity: NAVFAC SupersedingUFGS-21 21 01.00 20 (April 2006)UFGS-13961N (September 1999)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated October 2009*SECTION 21 21 01.00 20CARBON DIOXIDE FIRE EXTING
10、UISHING (HIGH PRESSURE)11/09*NOTE: This guide specification covers the requirements for high-pressure carbon dioxide fire extinguishing systems for protection of data processing equipment and similar electronics occupancies?.Edit this guide specification for project specific requirements by adding,
11、deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information.Remove information and requirements not required in respective project, whether or not brackets are present.Comments and suggestions on this guide specification are welcome and should be dir
12、ected to the technical proponent of the specification. A listing of technical proponents, including their organization designation and telephone number, is on the Internet.Recommended changes to a UFGS should be submitted as a Criteria Change Request (CCR).*NOTE: System requirements must conform to
13、Unified Facilities Criteria (UFC) 3-600-01 Fire Protection Engineering for Facilities and NFPA 12, “Carbon Dioxide Extinguishing Systems.“*NOTE: With minor changes, this guide specification can be adapted to other occupancies or needs, such as the protection of electric generators. Total flooding ca
14、rbon dioxide systems shall not be installed in normally occupied spaces. In other spaces, consideration must be given to the possibility that personnel could be trapped in an SECTION 21 21 01.00 20 Page 3Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-
15、,-atmosphere made by the discharge of carbon dioxide. Lockout keyed switches or audible pre-discharge signals shall be provided. Provide a sufficient time delay to allow for evacuation under worst case conditions. Refer to safety cautions in NFPA 12. If there are questions concerning system design,
16、the Engineering Field Division, Naval Facilities Engineering Command, Fire Protection Engineer, should be consulted.*PART 1 GENERAL1.1 REFERENCES*NOTE: This paragraph is used to list the publications cited in the text of the guide specification. The publications are referred to in the text by basic
17、designation only and listed in this paragraph by organization, designation, date, and title.Use the Reference Wizards Check Reference feature when you add a RID outside of the Sections Reference Article to automatically place the reference in the Reference Article. Also use the Reference Wizards Che
18、ck Reference feature to update the issue dates.References not used in the text will automatically be deleted from this section of the project specification when you choose to reconcile references in the publish print process.*The publications listed below form a part of this specification to the ext
19、ent referenced. The publications are referred to within the text by the basic designation only.ASME INTERNATIONAL (ASME)ASME B16.11 (2009) Forged Fittings, Socket-Welding and ThreadedASME B16.3 (2006) Malleable Iron Threaded Fittings, Classes 150 and 300ASME B16.39 (2009) Standard for Malleable Iron
20、 Threaded Pipe Unions; Classes 150, 250, and 300ASTM INTERNATIONAL (ASTM)ASTM A 106/A 106M (2008) Standard Specification for Seamless Carbon Steel Pipe for High-Temperature ServiceASTM A 53/A 53M (2007) Standard Specification for Pipe, SECTION 21 21 01.00 20 Page 4Provided by IHSNot for ResaleNo rep
21、roduction or networking permitted without license from IHS-,-,-Steel, Black and Hot-Dipped, Zinc-Coated, Welded and SeamlessFM GLOBAL (FM)FM P7825 (2005) Approval GuideMANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS INDUSTRY (MSS)MSS SP-58 (2002) Standard for Pipe Hangers and Support
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYUFGS21210100202009CARBONDIOXIDEFIREEXTINGUISHINGHIGHPRESSURE 二氧化碳 消防设施 高压 PDF

链接地址:http://www.mydoc123.com/p-984789.html