1、*USACE / NAVFAC / AFCESA / NASA UFGS-21 13 19.00 20 (November 2009)-Preparing Activity: NAVFAC SupersedingUFGS-21 13 19.00 20 (April 2006)UFGS-13945N (September 1999)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated October 2009*SECTION TABLE OF CONTENTSDIVISION 21 -
2、 FIRE SUPPRESSIONSECTION 21 13 19.00 20DELUGE PREACTION FIRE SPRINKLER SYSTEMS11/09PART 1 GENERAL1.1 REFERENCES1.2 SYSTEM DESCRIPTION1.3 SPRINKLER SYSTEM DESIGN1.3.1 Location of Sprinkler Heads1.3.2 Water Distribution1.3.3 Density of Application of Water1.3.4 Sprinkler Design Area1.3.5 Outside Hose
3、Allowances1.3.6 Friction Losses1.3.7 Water Supply1.3.8 Detail Drawing1.3.9 As-Built Drawings1.4 SUBMITTALS1.5 QUALITY ASSURANCE1.5.1 Qualifications of InstallerPART 2 PRODUCTS2.1 ABOVEGROUND PIPING SYSTEMS2.1.1 Sprinkler Piping2.1.2 Sprinkler Heads2.1.3 Cabinet for System2.1.4 Deluge Preaction Valve
4、s2.1.5 Water Motor Alarms2.1.6 Pressure Switch2.1.7 Pipe Hangers and Supports2.1.8 Valves2.1.8.1 Valve Supervision2.1.9 Backflow Preventer2.1.10 Identification Signs2.1.11 Test Connections2.1.11.1 Inspectors Test Connection for Preaction Systems2.1.11.2 Backflow Preventer Test ConnectionSECTION 21 1
5、3 19.00 20 Page 1Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-2.1.12 Main Drains2.1.13 Fire Department Connections2.1.14 Tank Mounted Air Compressor2.2 BURIED WATER PIPING SYSTEMS2.2.1 Pipe and Fittings2.2.2 Valves2.2.3 Post Indicator Valves2.2.4
6、Valve Boxes2.2.5 Buried Utility Warning and Identification Tape2.3 PIPE SLEEVES2.4 ESCUTCHEON PLATES2.5 DETECTION DEVICES2.5.1 Spot Heat Detectors2.5.2 Smoke Detectors2.5.3 Control Panel2.5.4 Secondary Power Supply2.5.5 Wiring2.5.6 Supervision2.5.7 Manual Remote Release Stations2.6 ALARMS2.6.1 Water
7、 Motor Alarms2.6.2 Local Alarm2.6.3 Fire AlarmPART 3 EXECUTION3.1 INSTALLATION3.1.1 Electrical Work3.1.2 Disinfection3.1.3 Connections to Existing Water Supply Systems3.1.4 Buried Piping System3.2 FIELD QUALITY CONTROL3.2.1 Preliminary Tests3.2.2 Formal Tests and Inspections3.3 FIELD PAINTING3.3.1 S
8、ystems in Finished Areas3.3.2 Systems in Unfinished Areas3.4 SCHEDULE- End of Section Table of Contents -SECTION 21 13 19.00 20 Page 2Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-*USACE / NAVFAC / AFCESA / NASA UFGS-21 13 19.00 20 (November 2009)-
9、Preparing Activity: NAVFAC SupersedingUFGS-21 13 19.00 20 (April 2006)UFGS-13945N (September 1999)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated October 2009*SECTION 21 13 19.00 20DELUGE PREACTION FIRE SPRINKLER SYSTEMS11/09*NOTE: This guide specification covers t
10、he requirements for automatic deluge and preaction fire extinguishing sprinkler systems.Edit this guide specification for project specific requirements by adding, deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information.Remove information and requ
11、irements not required in respective project, whether or not brackets are present.Comments and suggestions on this guide specification are welcome and should be directed to the technical proponent of the specification. A listing of technical proponents, including their organization designation and te
12、lephone number, is on the Internet.Recommended changes to a UFGS should be submitted as a Criteria Change Request (CCR).*NOTE: Use deluge systems for high hazard occupancies and as required by Unified Facilities Criteria (UFC) 3-600-01 Design: Fire Protection Engineering for Facilities or applicable
13、 NFPA standards. Use preaction systems in lieu of wet pipe systems where extraordinary precautions against accidental water discharge is warranted. For NAVFAC users, system requirements shall conform to UFC 3-600-01 and NFPA 13, “Installation of Sprinkler Systems.“*NOTE: If there are questions conce
14、rning system design, consult with the Engineering Field Division, Naval Facilities Engineering Command, Fire SECTION 21 13 19.00 20 Page 3Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-Protection Engineer.*NOTE: Following information shall be shown
15、on project drawings:1. Location and detail of each sprinkler system supply riser, deluge or preaction valve, water motor alarm, fire department inlet connection, control panel, air compressor, fused disconnect switch, and associated electrical connections.2. Location where each sprinkler system begi
16、ns including connection to water distribution system piping.3. Location of sprinkler system control valves, post indicator valves, or wall indicator valves.4. Area of sprinkler system coverage when system is protecting partial areas.5. Details of anchoring piping, including pipe clamps and tie rods,
17、 or mechanical retainer glands.6. Indicate existing sprinkler piping layout and sprinkler heads on project drawings only if existing sprinkler system is being modified and such layout is necessary for clarity.7. Do not show detector placement, conduit runs, or number of conductors.*PART 1 GENERAL1.1
18、 REFERENCES*NOTE: This paragraph is used to list the publications cited in the text of the guide specification. The publications are referred to in the text by basic designation only and listed in this paragraph by organization, designation, date, and title.Use the Reference Wizards Check Reference
19、feature when you add a RID outside of the Sections Reference Article to automatically place the reference in the Reference Article. Also use the Reference Wizards Check Reference feature to update the issue dates.References not used in the text will automatically be deleted from this section of the
20、project specification when you choose to reconcile references in the publish print process.*SECTION 21 13 19.00 20 Page 4Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-The publications listed below form a part of this specification to the extent ref
21、erenced. The publications are referred to within the text by the basic designation only.AMERICAN WATER WORKS ASSOCIATION (AWWA)AWWA C651 (2005; Errata 2005) Standard for Disinfecting Water MainsASME INTERNATIONAL (ASME)ASME A17.1 (2007; Addenda 2008) Safety Code for Elevators and EscalatorsFM GLOBAL
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYUFGS21131900202009DELUGEPREACTIONFIRESPRINKLERSYSTEMS 雨淋预动式 喷洒 灭火 系统 PDF

链接地址:http://www.mydoc123.com/p-984785.html