NAVY MIL-T-16315 D-1994 TRANSFORMERS POWER STEP-DOWN (MISCELLANEOUS NAVAL SHIPBOARD USE)《降压强力变换器(混合海军舰用)》.pdf
《NAVY MIL-T-16315 D-1994 TRANSFORMERS POWER STEP-DOWN (MISCELLANEOUS NAVAL SHIPBOARD USE)《降压强力变换器(混合海军舰用)》.pdf》由会员分享,可在线阅读,更多相关《NAVY MIL-T-16315 D-1994 TRANSFORMERS POWER STEP-DOWN (MISCELLANEOUS NAVAL SHIPBOARD USE)《降压强力变换器(混合海军舰用)》.pdf(18页珍藏版)》请在麦多课文档分享上搜索。
1、(INCH-PO$D- MIL-T-16 1 D(SH) 24 May 1994 SUPERSEDING .I MIL-T-l6315C(NAVY) 24 January 1955 (See 6.7) MILITARY SPECIFICATION TRANSFORMERS, POWER, STEP-DOWN (MISCELLANEOUS, NAVAL SHIPBOARD USE) This specification is approved for use by the Naval Sea Systems Command, Department of the Navy, and is avai
2、lable for use by all Departments and Agencies of the Department of Defense. 1. SCOPE 1.1 Scope. This specification covers small, dry type, step-down, power transformers for use on Naval ships. 1.2 Classification. Transformers shall be of the following types, as specified (see 6.2): IL (Indicator lig
3、ht). (3.14) CC (Control circuit). (3.15) SL (Sight light). (3.16) GF (Gun and torpedo firing). (3.17) PR (Power rectifier). (3.18) TF (Torpedo firing). (3.19) SA (Special applications). (3.20) 2. APPLICABLE DOCUMENTS 2.1 Government documents. 2.1.1 SDecifications. standards. and handbooks. The follo
4、wing specifi- cations, standards, and handbooks form a part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those listed in the issue of the Department of Defense Index of Specifications and Standards (DODISS) and supplement thereto, cit
5、ed in the solicitation (see 6.2). Beneficial comments (recommendations, additions, deletions) and any pertinent data which may be of use in improving this document should be addressed to: Commander, Naval Sea Systems Command, SEA 03442, 2531 Jefferson Davis Hwy., Arlington, VA 22242-5160 by using th
6、e Standardization Document Improvement Proposal (DD Form 1426) appearing at the end of this document or by letter. 1 1 AMSC N/A DISTRIBUTION STATEMENT A. Approved for public release; distribution is unlimited. FSC 5950 Provided by IHSNot for ResaleNo reproduction or networking permitted without lice
7、nse from IHS-,-,-MIL-T-l6315D(SH) SPECIFICATIONS FEDERAL PPP-F-320 Fiberboard; Corrugated and Solid Sheet J-W-1177 - Wire, Magnet, Electrical. Stock (Container Grade) and Cut Shapes. MILITARY MIL- S - 901 - Shock Tests, HI (High Impact) Shipboard Machinery, Equipment, and Systems, Requirements for.
8、ments for (Naval Shipboard Use). Equipment. Light Housings, and Indicator Light Lenses, General Specifications For. LH93. Style LH94. Equipment. MIL-E-917 - Electric Power Equipment, Basic Require- MIL-E-2036 - Enclosures for Electric and Electronic MIL-L-3661 - Lampholder, Indicator Lights, Indicat
9、or MIL-L-3661/60- Lampholder, Transformer, Light Indicator, Style MIL-L-3661/61- Lampholder, Light, Indicator (Housing), MIL-P-15024 - Plates, Tags and Bands for Identification of MIL-L-19140 - Lumber and Plywood, Fire-Retardant Treated. MIL-E-24142 - Enclosure for Electrical Fittings and Fixtures,
10、General Specifications For. MIL-E-24142/6- Enclosure, Submersible (15-Foot), Sizes 8 by 10 through 14 by 26. MIL-1-24718 - Insulating Resins Solventless, Vacuum-Pressure Impregnating, General Specification For. MIL-T-55164 - Terminal Boards, Molded, Barrier, Screw and Stud Types, and Associated Acce
11、ssories, General Specification for. STANDARDS MILITARY MIL-STD-195 - Marking of Connections for Electrical Assemblies. MIL-STD-45662- Calibration Systems Requirements. (Unless otherwise indicated, copies of federal and military specifications, and standards are available from the Navy Publishing and
12、 Printing Service Office, Bldg. 4D, 700 Robbins Avenue, Philadelphia, PA 19111-5094.) 2.1.2 Other Government documents. drawings. and Dublications. The following other Government documents, drawings, and publications form a part of this document to the extent specified herein. Unless otherwise speci
13、fied, the issues are those cited in the solicitation. DRAWING NAVAL SEA SYSTEMS COMMAND (NAVSEA) NAVSHIPS S6202-73731 - Enclosure (SPT), for Gunfiring Transformers, Type GF. (Application for copies should be addressed to Commander, Portsmouth Naval Shipyard, Naval Engineering Drawing Support Activit
14、y, Code 202.2, Portsmouth, NH 03804-5000,) 2 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-2.2 Order of precedence. In the event of a conflict between the text of this document and the references cited herein, the text of this document shall take p
15、recedence. Nothing in this document, however, supersedes applicable laws and regulations unless a specific exemption has been obtained. 3. REQUIREMENTS 3.1 First article. When specified (see 6.2), a sample shall be subjected to first article inspection (see 6.4) in accordance with 4.3. 3.2 General d
16、esign features. Transformers shall be of the dry type. Transformer cores shall be made of separate laminations of nonaging steel, insulated from each other when assembled. 3.2.1 Electrostatic shielding. When specified, (see 6.2), an electrostatic shield, either an aluminum or copper sheet, shall be
17、wound between the primary and secondary windings, and insulated from them. The ends of the shield shall be insulated from each other and a lead brought out from one end. 3.3 Basic requirements. Except as otherwise specified herein, transformers shall conform to MIL-E-917 and shall be of the followin
18、g insulation classifica- tion: Class 105, 130, 155, 180, 200, 220, 240, 3.3.1 Load test. Transformers shall withstand being operated at full load for 100 hours, at rated duty, under the conditions of nominal voltage, frequency and ambient temperature. 3.4 Magnet wire. Round or rectangular wire shall
19、 be in accordance with J- W-1177. 3.5 Preparation of electrical windings and core. The complete transformer shall be impregnated with a solventless resin per requirements of MIL-1-24718. The vacuum-pressure impregnation (VPI) method shall be used. After VPI process, the transformer shall receive an
20、additional varnish treatment to provide a smooth finished surface. Impregnation shall be in accordance with MIL-E-917. 3.6 Temuerature rise. The average winding temperature rise above an ambient temperature of 50 degrees C, when measured by the change of resistance method, shall not exceed the follo
21、wing values: See 4.7.3. The hot temperature rise shall be by the embedded detector method of MIL-E-917. Average winding Hot-Spot winding Insulation system temperature rises temperature rise temperature degrees C degrees C degrees C 105 130 155 180 200 220 240 45 50 75 100 120 140 160 55 80 105 130 1
22、50 170 190 3 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-T-16315D 9979906 L984725 T20 3.7 Dielectric strength. - and induced voltage tests. Dielectric strength, and induced voltage tests shall consist of the following: 3.7.1 Applied potential
23、 test. The applied potential test shall be made by applying between each winding and all other windings connected to ground a voltage from an external source in accordance with the below values when tested in accordance with 4.7.7.1. The test voltages apply to all types of transformers except the ty
24、pe PR. See 3.18.3. Applied Potential Test Voltages Nameplate voltage rating, volts O - 125 Above 125 Test potential, volts, minimum 1000 1500 3.7.2 Induced voltage test. The induced voltage test shall be made by applying between the terminals of one winding a voltage of twice the normal voltage deve
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILT16315D1994TRANSFORMERSPOWERSTEPDOWNMISCELLANEOUSNAVALSHIPBOARDUSE 降压 强力 变换器 混合 海军 PDF

链接地址:http://www.mydoc123.com/p-982506.html