1、b 4 i MIL-STD-2202A 999991L 0474991 777 - (NOT MEASUREMENTI I SENSXTLVE I MIL-STD-2202A l!LhLEM SUPERSEDING MIL-STD-2202 29 May 1987 MILITARY STANDARD ENERGY MONITORING AND CONTROL SYSTEMS, FACTORY TESTS AMSC N6988 AREA ATTS DISTRIBUTION STATEMENT A : APPROVED FOR PUBLIC RELEASE; DISTRIBUTION IS UNL
2、IMITED. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-STD-2202A = 99999LL 0474992 b03 MIL-STD-2202A FOREWORD 1. This military standard is approved for use by all Departments and Agencies of the Department of Defense. 2. Beneficial comments (rec
3、ommendations, additions, deletions) and any pertinent data which may be of use in improving this document should be addressed to: Commanding Officer (Code 156), Naval Construction Battalion Center, Port Hueneme, CA 93043-4301, by using the Standardization Document Improvement Proposal (DD Form 1426)
4、 appearing at the end of this document or by letter. ii Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-STD-2202A m 99999311 0474993 54T = CONTENTS Page Paragraph 1 . SCOPE 1 2 . APPLICABLE DOCUMENTS 2 3 . DEFINITIONS . 3 4 . GENERAL REQUIREMENTS
5、 15 4.1 4.2 4.2.1 4.3 4.3.1 f! . 4 4.4.1 4.5 General . 15 Test plans . 15 Data requirements for test plans 15 Test procedures . 15 Data requirements for test procedures 16 Testreports 16 Data requirements for test reports . 16 Test equipment and set up 16 5 . DETAILED REQUIREMENTS 17 5.1 General . 1
6、7 5.2 Factory tests 17 Test Number Title 1A 2A 3A Initial System Equipment Verification 18 System Startup . 19 System Accuracy and Resolution . 20 Surge Protection Tests: 4A 5A 6A Overvoltage Test: 7A Power Line Surge Protection . 21 Sensor and Control Wiring Surge Protection . 22 Communication Link
7、s Surge Protection 23 Data Communication Links Overvoltage Protection 24 FID/MUX or RCU/ACU Hardware and Software: 8A 9A 10A 11A 12A 13A FID or RTU Memory and FID/MUX or RCU/ACU Spare I/O Capacity 25 FID or RTU startup and Functions 26 FID or RTU RTC and RAM Battery Backup 28 FID/MUX or RCU/ACU Batt
8、ery Backup 29 FID/MUX or RCU/ACU Portable Tester . 30 FID or RTU Test Set . 32 iii Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-CONTENTS Analog/Digital 1/0 Functions: Page 14A 15A Analog and Digital 1/0 Functions 33 (Common Mode) . 35 Analog Input
9、 Function Noise Protection Analog/Digital 1/0 Functions: (Continued) 16A 17A Analog Input Function Noise Protection Digital Input a non-volatile semiconductor memory. 3.109 Real time. Real time is a situation in which a computer monitors, evaluates, reaches decisions, and effects controls within the
10、 response time of the fastest phenomenon. 3.110 Real time clock (RTC). A real time clock is a device which maintains accurate time of day, day of week, and date information for the computer. The RTC may be updated by hardware. 10 Provided by IHSNot for ResaleNo reproduction or networking permitted w
11、ithout license from IHS-,-,-MIL-STD-2202A m 99999LL 0475007 732 m MIL-STD-2202A 3.111 Register. A register is a digital device capable of retaining information. 3.112 Reinitialization. Refer to initialization. 3.113 Remote control unit (RCU). The RCU is an intelligent hardware device containing soft
12、ware which implements the distribution process aspects of operating with the central computer as well as maintaining effective control of field control loops. 3.114 Remote operator station (ROS) Identical to a COS except remotely located. 3.115 Resistance temperature detector (RTD). An RTD is a devi
13、ce where resistance changes linearly as a function of temperature. 3.116 Selective generation. Selective generation is where the management of input/output is restricted to selected peripherals. 3.117 Sensors. Sensors are devices used to detect or measure physical phenomena. 3.118 Sinple steDDing. S
14、ingle stepping is the procedure by which the next statement in a memory resident program is executed by depressing a switch, 3.119 SnaDshot. A snapshot is a picture of the instantaneous status and state of a system. 3.120 Software. Software is a term used to describe all programs whether in machine,
15、 assembly, or high-level language. 3.121 Source code. Source code is a term used to describe assembler and high-level programmer developed code. 3.122 Stand-alone. Stand-alone is a term used to designate a device or system which can perform its function totally independent of any other device or sys
16、tem. 3.123 Standard panel. A control panel developed by the U.S. Army Corps of Engineers to control heating, ventilating, and air conditioning equipment. 3.124 Supervisory control. Supervisory control is a separate (and usually remote) control and monitoring of local control loops. control. ) (See D
17、irect digital 3.125 System normal heavy. System normal heavy load conditions are defined as the occurrence throughout the system of a total of three status changes, three digital alarms, three analog high or low limit alarms, and three analog quantity changes within the high and low limits during a
18、single 1-second interval. This number of similar occurrences shall repeat on a continuous basis during successive 1 second intervals for up to 30 seconds. The system normal heavy load conditions shall have 50 percent of the changes and alarms, including no less than one of each type, occurring at a
19、single FID or RTU or MUX or ACU with the remaining changes and alarms distributed among the Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-STD-2202A 9999911 O475008 b79 = MIL-STD-2202A remaining FID/MUX or RCU/ACU. No DTM link shall be more than
20、 65 percent loaded during this normal heavy load condition and the alarm printer shall continue to print out all occurrences. 3.126 ThrouehDut. - Throughput is the total capability of equipment to process or transmit data during a specified time period. 3.127 Time base generator (TBG). See Clock. 3.
21、128 Time tag. A time tag is the date and time of occurrence of an event. 3.129 True digital. A true digital is a representation of any value by symmetric digits, used to form fixed length words. 3.130 Unitarv control unit (UCU). UCU is a microprocessor based, dedicated purpose device designed and pr
22、ogrammed to control air distribution system mixing boxes, terminal units or variable air volume (VAV) boxes. 3.131 Utilitv control system (UCS). A computer based system for monitoring A typical system would include a COS, DTM and and controlling utility systems. RTUc/ACUs . 3.132 Utilitv monitoring
23、and control systems (UMCS). A computer based A system for monitoring and controlling utility systems and energy usage. typical system would include COSs, DTM, and RCUs/ACUs. 3.133 Volatile memorv. the stored digital data is lost when power is removed. A volatile memory is a semiconductor device in w
24、hich 3.134 Word. A word is a set of binary bits handled by the computer as the primary unit of information. 3.135 m. A zone is an area composed of a building, a portion of a building, or a group of buildings affected by a single device or piece of equipment. 3.136 Definitions of acronyms used in thi
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILSTD2202A1994ENERGYMONITORINGANDCONTROLSYSTEMSFACTORYTESTS 工厂 测试 能源 监测 控制系统 PDF

链接地址:http://www.mydoc123.com/p-982416.html