NAVY MIL-PRF-24775 A-2005 AIR CONDITIONING FAN COIL UNITS HORIZONTAL AND VERTICAL TYPES NAVAL SHIPBOARD《海军军舰上用水平的和垂直型空气调节鼓风机盘绕系统》.pdf
《NAVY MIL-PRF-24775 A-2005 AIR CONDITIONING FAN COIL UNITS HORIZONTAL AND VERTICAL TYPES NAVAL SHIPBOARD《海军军舰上用水平的和垂直型空气调节鼓风机盘绕系统》.pdf》由会员分享,可在线阅读,更多相关《NAVY MIL-PRF-24775 A-2005 AIR CONDITIONING FAN COIL UNITS HORIZONTAL AND VERTICAL TYPES NAVAL SHIPBOARD《海军军舰上用水平的和垂直型空气调节鼓风机盘绕系统》.pdf(26页珍藏版)》请在麦多课文档分享上搜索。
1、 INCH-POUND MIL-PRF-24775A(SH) 31 January 2005 SUPERSEDING MIL-A-24775(SH) 13 July 1992 PERFORMANCE SPECIFICATION AIR CONDITIONING FAN COIL UNITS, HORIZONTAL AND VERTICAL TYPES, NAVAL SHIPBOARD This specification is approved for use by the Department of the Navy and is available for use by all Depar
2、tments and Agencies of the Department of Defense. 1. SCOPE 1.1 Scope. This specification covers horizontal and vertical type air conditioning fan-coil units for use in heating and air conditioning applications aboard Naval ships. 1.2 Classification. The air conditioning fan-coil units are of the fol
3、lowing classifications (see 6.2): 1.2.1 Types. The types of air conditioning fan units are as follows: Type H - Horizontal, overhead mounting Type V - Vertical, bulkhead mounting Type NMH - Nonmagnetic construction, horizontal, overhead mounting Type NMV - Nonmagnetic construction, vertical, bulkhea
4、d mounting 1.2.2 Sizes. The sizes of air conditioning fan units are as follows: Sizes 1-8 - Capacity in British thermal units per hour in thousands (MBH) as specified in Table I 1.2.3 Classes. The classes of air conditioning fan units are as follows: Heater kW - Heating in Kilowatt (kW) as specified
5、 in Table I Class RH - Right Hand - type DW chilled water coil Class LH - Left Hand - type DW chilled water coil 1.2.4 Grades. The grades of air conditioning fan units are as follows: HI Shock - HI shock unit Type X - Non-HI shock unit Comments, suggestions, or questions on this document should be a
6、ddressed to: Commander, Naval Sea Systems Command, ATTN: SEA 05Q, 1333 Isaac Hull Avenue, SE, Stop 5160, Washington Navy Yard DC 20376-5160 or emailed to commandstandardsnavsea.navy.mil, with the subject line “Document Comment”. Since contact information can change, you may want to verify the curren
7、cy of this address information using the ASSIST Online database at http:/assist.daps.dla.mil. AMSC N/A FSC 4120 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-PRF-24775A(SH) 1.2.5 Heater requirement. The heater requirements of air conditioning f
8、an units are as follows: Item A1 - Cooling unit with low voltage heater Item A2 - Cooling unit with medium voltage heater Item A3 - Cooling unit with high voltage heater 1.2.6 Motor protection. The motor protections of air conditioning fan units are as follows: Motor Protection LVP - Low voltage pro
9、tection Motor Protection LVR - Low voltage release 1.3 Part or identifying number (PIN). PINs to be used for horizontal and vertical type air conditioning fan-coil units acquired to this specification are created as follows: M 24775 - X X XX X X X Prefix for Military Specification Specification Numb
10、er Type (see code below) Size (see code below) Class (see code below) Grade (see code below) Heater requirement (see code below) Motor protection (see code below) Type Code Size Code Class Code Grade Code Heater Requirement Code Motor Protection Code Type Code Size Code Class Code Grade Code Heater
11、Code Motor protect. Code H A 1 1 RH RH HI shock 1 A1 A LVP 1 V B 2 2 LH LH Type X 2 A2 B LVR 2 NMH C 3 3 A3 C NMV D 4 4 5 5 6 6 7 7 8 8 Examples: M24775-A2RH1A2 M24775-B8LH2B1 2. APPLICABLE DOCUMENTS 2.1 General. The documents listed in this section are specified in sections 3, 4, or 5 of this speci
12、fication. This section does not include documents cited in other sections of this specification or recommended for additional information or as examples. While every effort has been made to ensure the completeness of this list, document users are cautioned that they must meet all specified requireme
13、nts of documents cited in sections 3, 4, or 5 of this specification, whether or not they are listed. 2 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-PRF-24775A(SH) 2.2 Government documents. 2.2.1 Specifications, standards, and handbooks. The fo
14、llowing specifications, standards, and handbooks form a part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those cited in the solicitation or contract. DEPARTMENT OF DEFENSE SPECIFICATIONS MIL-S-901 - Shock Test, H.I. (High-Impact) Shi
15、pboard Machinery, Equipment, and Systems, Requirements for MIL-PRF-16552 - Filters, Air Environmental Control System, Cleanable, Impingement (High Velocity Type) MIL-B-17931 - Bearings, Ball, Annular, for Quiet Operation DEPARTMENT OF DEFENSE STANDARDS MIL-STD-167-1 - Mechanical Vibrations of Shipbo
16、ard Equipment (Type I - Environmental and Type II - Internally Excited) MIL-STD-889 - Dissimilar Metals MIL-STD-1399-300 - Interface Standard for Shipboard Systems, Electric Power, Alternating Current (Metric) MIL-STD-1474 - Noise Limits MIL-STD-2031 - Fire and Toxicity Test Methods and Qualificatio
17、n Procedure for Composite Material Systems Used in Hull, Machinery, and Structural Applications Inside Naval Submarines MIL-STD-2142 - Magnetic Silencing Characteristics, Measurement of (Metric) (Copies of these documents are available online at http:/assist.daps.dla.mil/quicksearch/ or http:/assist
18、.daps.dla.mil or from the Standardization Document Order Desk, 700 Robbins Avenue, Building 4D, Philadelphia, PA 19111-5094.) 2.2.2 Other Government documents, drawings, and publications. The following other Government documents, drawings, and publications form a part of this document to the extent
19、specified herein. Unless otherwise specified, the issues of these documents are those cited in the solicitation or contract. NAVSEA TECHNICAL PUBLICATION S9074-AR-GIB-010/278 - Requirements for Fabrication, Welding and Inspection, Casting Inspection and Repair for Machinery, Piping and Pressure Vess
20、els (Copies of this document are available from Naval Inventory Control Point, 700 Robbins Avenue, Attn: Code 0862 (Cash Sales), Philadelphia, PA 19111 or online at www.nll.navsup.navy.mil.) 2.3 Non-Government publications. The following documents form a part of this document to the extent specified
21、 herein. Unless otherwise specified, the issues of these documents are those cited in the solicitation or contract. AIR CONDITIONING AND REFRIGERATION INSTITUTE (ARI) ARI 410 - Forced-Circulation Air-Cooling and Air-Heating Coils (Copies of this document are available from the Air Conditioning and R
22、efrigeration Institute, 1501 Wilson Boulevard, Suite 600, Arlington, VA 22209-2403, Attn: Publications Department, or online at www.ari.org.) 3 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-PRF-24775A(SH) AIR MOVEMENT AND CONTROL ASSOCIATION, I
23、NC. (AMCA) AMCA 111 - Laboratory Accreditation Program (DoD adopted) AMCA 300 - Reverberant Room Method for Sound Testing of Fans (DoD adopted) (Copies of these documents are available from the Air Movement and Control Association, Inc., 30 West University Drive, Arlington Heights, IL 60004 or onlin
24、e at www.amca.org.) AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)/AMERICAN BEARING MANUFACTURERS ASSOCIATION (ABMA) ANSI/ABMA STD-4 - Tolerance Definitions and Gaging Practices for Ball and Roller Bearings ANSI/ABMA STD-9 - Load Ratings and Fatigue Life for Ball Bearings ANSI/ABMA STD-13 - Rolling Be
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILPRF24775A2005AIRCONDITIONINGFANCOILUNITSHORIZONTALANDVERTICALTYPESNAVALSHIPBOARD 海军 军舰 水平 垂直 空气调节

链接地址:http://www.mydoc123.com/p-980955.html