NAVY MIL-PRF-18953 C-2005 FANS VANEAXIAL AND TUBEAXIAL VENTILATION AND AIR CONDITIONING NAVAL SHIPBOARD《海军舷侧透气和通风管装式轴流和叶片轴流式扇风机》.pdf
《NAVY MIL-PRF-18953 C-2005 FANS VANEAXIAL AND TUBEAXIAL VENTILATION AND AIR CONDITIONING NAVAL SHIPBOARD《海军舷侧透气和通风管装式轴流和叶片轴流式扇风机》.pdf》由会员分享,可在线阅读,更多相关《NAVY MIL-PRF-18953 C-2005 FANS VANEAXIAL AND TUBEAXIAL VENTILATION AND AIR CONDITIONING NAVAL SHIPBOARD《海军舷侧透气和通风管装式轴流和叶片轴流式扇风机》.pdf(25页珍藏版)》请在麦多课文档分享上搜索。
1、 INCH-POUND MIL-PRF-18953C(SH) 14 February 2005 SUPERSEDING MIL-F-18953B(SH) 22 October 1990 PERFORMANCE SPECIFICATION FANS, VANEAXIAL AND TUBEAXIAL, VENTILATION AND AIR CONDITIONING, NAVAL SHIPBOARD This specification is approved for use by the Department of the Navy and is available for use by all
2、 Departments and Agencies of the Department of Defense. 1. SCOPE 1.1 Scope. This specification covers fixed vaneaxial and tubeaxial fans for Naval shipboard use in ventilation and air conditioning systems. 1.2 Classification. Fans are of the following types, sizes, current, voltage and phase, enclos
3、ures, maximum ambient temperature, structure, thermal protection, and quiet bearings as specified (see 6.2): 1.2.1 Types. Types PIN Code A Vaneaxial, fixed, Navy Standard (HI Shock) AA L Tubeaxial, fixed, Navy Standard (HI Shock) LL X-A Vaneaxial, fixed, Navy Standard (Non-Shock, commercial marine m
4、otor) XA X-L Tubeaxial, fixed, Navy Standard (Non-Shock, commercial marine motor) XL Comments, suggestions, or questions on this document should be addressed to: Commander, Naval Sea Systems Command, ATTN: SEA 05Q, 1333 Isaac Hull Avenue, SE, Stop 5160, Washington Navy Yard DC 20376-5160 or emailed
5、to commandstandardsnavsea.navy.mil, with the subject line “Document Comment”. Since contact information can change, you may want to verify the currency of this address information using the ASSIST Online database at http:/assist.daps.dla.mil. AMSC N/A FSC 4140 Provided by IHSNot for ResaleNo reprodu
6、ction or networking permitted without license from IHS-,-,-MIL-PRF-18953C(SH) 1.2.2 Sizes. Types A and X-A vaneaxial fans Types L and X-L tubeaxial fans Fan Size Volume (ft3/min) Fan Total Pressure (inches, wg) PIN Code Fan Size Volume (ft3/min) Fan Total Pressure (inches, wg) PIN Code 250 2.5 00Q1/
7、 450 0.75 00H 660 2.5 00H2/1 1,000 0.50 01W 1 1,030 2.65 01W3/2 1,900 0.58 02W 1 1,500 3.0 01H 3 2,250 0.70 03W 2 2,000 3.4 02W 2 2,600 3.4 02H 3 3,200 3.4 03W 3 3,750 3.5 03H 4 3,220 7.0 04H 5 4,200 3.75 05W 6 6,300 3.65 06W 7 5,200 7.0 07W 8 7,300 3.3 08W 10 8,500 4.2 10W 11 8,700 5.5 11W 12 10,25
8、0 5.0 12W 16 13,200 4.75 16W 17 12,300 6.2 17W 20 18,000 4.85 20W 25 22,000 3.95 25W 28 18,750 6.4 28W 30 25,000 4.2 30W 1/“Q” denotes the fraction “”. 2/“H” denotes the fraction “”. 3/“W” denotes a whole number. 2 Provided by IHSNot for ResaleNo reproduction or networking permitted without license
9、from IHS-,-,-MIL-PRF-18953C(SH) 1.2.3 Current. Type of Current PIN Code Alternating current (a.c.) A Not applicable N 1.2.4 Voltage. Voltage and Phase (frequency of a.c. is 60 Hz) PIN Code 115-volt, single phase a.c. 1 220-volt, 3-phase a.c. 2 440-volt, 3-phase a.c. 4 1.2.5 Enclosures. Enclosures PI
10、N Code Spraytight W Explosion-proof X 1.2.6 Maximum ambient temperature. Ambient Temperature PIN Code 65 C 6 80 C 8 1.2.7 Structure. Structure PIN Code Non-magnetic structure of fan and motor NM Not applicable NA 1.2.8 Thermal protection. Thermal Protection PIN Code Thermal protection is applied TP
11、Not applicable NA 1.2.9 Quiet bearing. Quiet Bearing PIN Code Quiet bearing that meets MIL-B-18731 QB Not applicable NA 3 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-PRF-18953C(SH) 1.3 Part or identifying number (PIN). PINs to be used for fix
12、ed vaneaxial and tubeaxial fans acquired to this specification are created as follows (see 1.2.1 through 1.2.9): M 18953 - XX XXX X X X X XX XX XX Prefix for Military Specification Specification Number Type Size Current Voltage and Phase Enclosures Ambient Temp. Structure Thermal Protection Quiet Be
13、aring 2. APPLICABLE DOCUMENTS 2.1 General. The documents listed in this section are specified in sections 3, 4, or 5 of this specification. This section does not include documents cited in other sections of this specification or recommended for additional information or as examples. While every effo
14、rt has been made to ensure the completeness of this list, document users are cautioned that they must meet all specified requirements of documents cited in sections 3, 4, or 5 of this specification, whether or not they are listed. 2.2 Government documents. 2.2.1 Specifications, standards, and handbo
15、oks. The following specifications, standards, and handbooks form a part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those cited in the solicitation or contract. DEPARTMENT OF DEFENSE SPECIFICATIONS MIL-S-90l Shock Tests, H.I. (High-I
16、mpact) Shipboard Machinery, Equipment, and Systems, Requirements for MIL-M-17059 Motors, 60-Cycle, Alternating-Current, Fractional H.P. (Shipboard Use) MIL-M-17060 Motors, 60-Hertz, Alternating Current, Integral-Horsepower, Shipboard Use MIL-B-17931 Bearings, Ball, Annular, for Quiet Operation DEPAR
17、TMENT OF DEFENSE STANDARDS MIL-STD-l67-1 Mechanical Vibrations of Shipboard Equipment (Type I - Environmental and Type II - Internally Excited) MIL-STD-1399-300 Interface Standard for Shipboard Systems, Electric Power, Alternating Current (Metric) MIL-STD-2142 Magnetic Silencing Characteristics, Mea
18、surement of (Metric) (Copies of these documents are available online at http:/assist.daps.dla.mil/quicksearch/ or http:/assist.daps.dla.mil or from the Standardization Document Order Desk, 700 Robbins Avenue, Building 4D, Philadelphia, PA 19111-5094.) 2.2.2 Other Government documents, drawings, and
19、publications. The following other Government documents, drawings, and publications form a part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those cited in the solicitation contract. NAVSEA TECHNICAL PUBLICATION S9074-AR-GIB-010/278 Re
20、quirements for Fabrication, Welding and Inspection, Casting Inspection and Repair for Machinery, Piping and Pressure Vessels (Copies of this document are available from Naval Inventory Control Point, 700 Robbins Avenue, Attn: Code 0862 (Cash Sales), Philadelphia, PA 19111 or online at www.nll.navsup
21、.navy.mil.) 4 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-PRF-18953C(SH) 2.3 Non-Government publications. The following documents form a part of this document to the extent specified herein. Unless otherwise specified, the issues of these doc
22、uments are those cited in the solicitation or contract. AIR MOVEMENT AND CONTROL ASSOCIATION (AMCA) INTERNATIONAL, INC. AMCA 99-0401 Classification for Spark Resistant Construction AMCA 111 Laboratory Accreditation Program AMCA 210 Laboratory Methods for Testing Fans for Aerodynamic Performance Rati
23、ng (DoD adopted) AMCA 300 Reverberant Room Method for Sound Testing of Fans (DoD adopted) (Copies of these documents are available from the Air Movement and Control Association International, Inc., 30 West University Drive, Arlington Heights, IL 60004 or online at www.amca.org.) AMERICAN NATIONAL ST
24、ANDARDS INSTITUTE (ANSI)/AMERICAN BEARING MANUFACTURERS ASSOCIATION (ABMA) ANSI/ABMA STD-4 Tolerance Definitions and Gaging Practices for Ball and Roller Bearings ANSI/ABMA STD-9 Load Ratings and Fatigue Life For Ball Bearings ANSI/ABMA STD-13 Rolling Bearing Vibration and Noise (Methods of Measurin
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILPRF18953C2005FANSVANEAXIALANDTUBEAXIALVENTILATIONANDAIRCONDITIONINGNAVALSHIPBOARD 海军 透气 通风管 轴流

链接地址:http://www.mydoc123.com/p-980906.html