NAVY MIL-C-19794 B-1962 CASTABLE MIX REFRACTORY THERMAL INSULATING《绝热型难熔铸块混合》.pdf
《NAVY MIL-C-19794 B-1962 CASTABLE MIX REFRACTORY THERMAL INSULATING《绝热型难熔铸块混合》.pdf》由会员分享,可在线阅读,更多相关《NAVY MIL-C-19794 B-1962 CASTABLE MIX REFRACTORY THERMAL INSULATING《绝热型难熔铸块混合》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、*c- - -_ -, -_ I_ - _- - - _- - MIL-C-17774B 73 m 997770b OLL7LIL7 7 - %- MIL-C-l9794B(SHIPS) 11 December 1962 SUPERSEDING 27 October 1959 MIL-C- 19?94A(SHIPS) MILITARY SPECIFICATION CASTABLE MM, REFRACTORY, THERMAL INSULATING 1. SCOPE 1.1 This specification covers thermal insulating refractory cast
2、able mix for use as a back-up insula- tion for refractory furnace linings of boilers. 2. APPLICABLE DOCUMENTS 2.1 The following documents, of the issue in effect on date of invitation for bids or request for pro- posal, form a part of this specification to the extent specified herein: SPECIFICATIONS
3、 FEDERAL UU-S-48 - Sacks, Paper, Shipping. PPP-B-35 - Bags: Textile, Shipping, Burlap, Cotton and Waterproof Laminated. STANDARDS MILITARY MIL-STD-105 - Sampling Procedures and Tables for Inspection by Attributes. MIL-STD-129 - Marking for Shipment and Storage. (Copies of specifications, standards,
4、drawings, and publications required by suppliers in connection with specific procurement functions should be obtained from the procuring activity or as directed by the contracting officer.) 2.2 Other publications. - The following document forms a part of this specification to the extent specified he
5、rein. Unless otherwise indicated, the issue in effect on date of invitation for bids or request for proposal shall apply: OFFICIAL CLASSIFICATION COMMITTEE Uniform Freight Classification Rules. (Application for copies should be addressed to the Official Classification Committee, 1 Park Avenue at 33r
6、d Street, New York 16, N.Y.) 3. REQUIREMENTS 3.1 Material. - The castable refractory shall be composed of a mixture of heat-resistant materials and a bond material. It shall mix readily with water and shall be of such consistency when mixed with water that it can be cast into a sound wall reasonably
7、 free of voids. 3.2 Time for air set. - The length of time for air setting shall not be greater than 24 hours. At the end of this period, the mix shall support its own weight and maintain its originally cast shape (see 4.4. i). 3.3. Density. - The density of the castable refractory shall not exceed
8、45 pounds per cubic foot after being heat soaked at 2,000“F. for 5 hours (see 4.4.2). 3.4 Permanent linear change. - The permanent linear change shall not exceed 3. O percent shrinkage after being heat soaked at 2,000“F. for 5 hours (see 4.4.3). fusion or softening upon completion of the test specif
9、ied in 4.4.4 and shall retain its cast shape without crumbling when removed from the panel assembly. 3.5 Refractoriness. - The castable refractory shall be in satisfactory condition without evidence of I FSC 9350 I THIS DOCUMENT CONTAINS y PAGES. - - - Provided by IHSNot for ResaleNo reproduction or
10、 networking permitted without license from IHS-,-,-MIL-C-l9794B(SHPS) 3.6 T-aI conductance. - The thermal conductance of the mix shali be such that the temperature drop through and block cast from the mix shall be not less than 1,800F. when the hot face of the block is maintained at 2,500F. (see 4.4
11、.4). 3.7 Workmanship. - Workmanship shall be first class in every respect. 4. QUALITY ASSURANCE PROVISIONS 4.1 Responsibility for inspection. - Unless otherwise specified in the contract or purchase order, the supplier is responsible for the performance of all inspection requirements as specified he
12、rein. Except as otherwise specified, the supplier may utilize his own facilities or any commercial laboratory satisfac- tory to the Government. The Government reserves the right to perform any of the inspections set forth in the specification where such inspections are deemed necessary to assure sup
13、plies and services conform to prescribed requirements. 4.2 SampIing for quality conformance inspection. - Sampling for inspection shall be performed in ac- cordancewe provisions set forth in MIL-STD-105, except where otherwise indicated. For purposes of sampIing, an inspection lot for quality confor
14、mance inspection shall consist of all material offered for delivery at one time. 4.3 inspection of the castable mix. - 4.3.1 Examination of the castable mix. - Examination of the castable mix shall be made in accordance with the classification of defects, inspection levels and acceptable quality lev
15、els (AQLs) set forth below. The lot size, for purpose of determining the sample size in accordance with MIL-STD-105, shall be ex- pressed in units of filled containers of castable refractory mix for examination in 4.3.1.1, 4.3.1.2 and 4.3.1.3. 4.3.1.1 Examination of castable mix container for defect
16、s in appearance, workmanship, closures and markings.- The sample unit for this examination shall be one filled container. Examine Defect Appearance and workmanship Not type or size specified. Evidence of sifting or leaking of contents. Bag laminations not as specified. Scuff marks, torn or punctured
17、. End closure not as specified. Omitted, illegible, incorrect, incomplete or not in accordance with contract requirements. Closures Markings 4.3.1.2 Examination of castable mix container for defects in appearance of refractory castable mix. - The sample unit for this examination shall be one filled
18、container. Examine Defect Appearance Material not as specified. Presence of foreign material. Presence of large particles, lumps or caked material. 4.3.1.3 Examination of castable mix for defects in net contents. The sample unit for this examination shall be one filled container. The average net con
19、tents shall be not less than the specified or indicated quantity. No less than five sample units shall be drawn for this examination. 4.3.1.4 inspection levels and acceptable quality levels (AQLs) for examinations. - The inspection levels for determining the sample size and acceptable quality levels
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILC19794B1962CASTABLEMIXREFRACTORYTHERMALINSULATING 绝热 熔铸 混合 PDF

链接地址:http://www.mydoc123.com/p-977469.html