NAVY A-A-59319-2003 DISPOSABLE AIR FILTERS FOR ENVIRONMENTAL CONTROL SYSTEMS《环境控制系统可任意使用的空气过滤器》.pdf
《NAVY A-A-59319-2003 DISPOSABLE AIR FILTERS FOR ENVIRONMENTAL CONTROL SYSTEMS《环境控制系统可任意使用的空气过滤器》.pdf》由会员分享,可在线阅读,更多相关《NAVY A-A-59319-2003 DISPOSABLE AIR FILTERS FOR ENVIRONMENTAL CONTROL SYSTEMS《环境控制系统可任意使用的空气过滤器》.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、 INCH-POUND A-A-59319 31 July 2003 COMMERCIAL ITEM DESCRIPTION DISPOSABLE AIR FILTERS FOR ENVIRONMENTAL CONTROL SYSTEMS The General Services Administration has authorized the use of this commercial item description as a replacement for U.S. Navy standard cleanable impingement filters described in MI
2、L-PRF-16552, except those filters used prior to flame arrestors. 1. SCOPE. This commercial item description (CID) describes disposable filter media that is used for air filtration purposes in shipboard heating, ventilating and air conditioning (HVAC) systems. 2. CLASSIFICATION. Disposable air filter
3、s shall conform to the following types and sizes: 2.1 Types. Disposable air filters shall be of the following types and efficiencies: Type I: Filter Pads (to be inserted into a reusable filter frame) Type II: Filter Panels (internal frames-inserted directly into filter housings) Medium Efficiency Hi
4、gh Efficiency Type III: Filter Panel Links (filter panels linked together) Medium Efficiency High Efficiency Type IV: Filter Sleeves (filter material constructed to fit over an internal frame) Medium Efficiency High Efficiency Type V: Filter Cubes (internal frames-inserted directly into filter housi
5、ngs) Medium Efficiency High Efficiency Beneficial comments, recommendations, additions, deletions, clarifications, etc. and any data, that may improve this document should be sent to: Commander, Naval Sea Systems Command, ATTN: SEA 05Q, 1333 Isaac Hull Avenue, SE, Stop 5160, Washington Navy Yard DC
6、20376-5160 or emailed to commandstandardsnavsea.navy.mil, with the subject line “Document Comment”. Since contact information can change, you may want to verify the currency of this address information using the ASSIST Online database at www.dodssp.daps.mil. FSC 4130 Provided by IHSNot for ResaleNo
7、reproduction or networking permitted without license from IHS-,-,-A-A-59319 2.2 Sizes. Each type of filter shall come in the following sizes: 2.2.1 Type I filter pads. Type I filter pads shall be sized to fit within filter holding frames that are sized in accordance with the standard Navy filter dim
8、ensions of MIL-PRF-16552 and with commercial filters on Navy ships. Filter pad sizes shall be in accordance with Table I. TABLE I. Type I filter sizes. Standard Navy Filter or Commercial Size Designation Type I Filters (Length x Width) (inches) +1/8 10AF 7-3/4 x 7-3/4 11AF 13 x 8-1/2 12AF 15 x 10-1/
9、2 13AF 10-1/2 x 22-1/2 14AF 16 x 2515AF 20 x 2016AF 20 x 30Com20x25 20 x 252.2.2 Type II filter panels. Type II filter panels shall be designed to fit into standard Navy filter housings and other common filter housings found on Navy ships. The filter material shall be sealed to fit snugly around the
10、 internal frame. The internal frame size shall be in accordance with Table II. TABLE II. Type II filter internal frame sizes. Standard Navy Filter or Commercial Size Designation Type II Filters Internal Frame Size (inch) +1/8 10AF 7-1/8 x 7 1/8 11AF 12-3/8 x 7-7/8 12AF 14-3/8 x 9-7/8 13AF 9-7/8 x 21
11、-7/814AF 15-3/8 x 24-3/8 15AF 19-3/8 x 19-3/8 16AF 19-3/8 x 29-3/8 Com20x25 19-3/8 x 24-3/8 2 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-A-A-59319 2.2.3 Type III filter panel links. Type III filter panel links are the same size as Type II filter
12、 panels but the filter panels shall be linked together by the filter material so that multiple panels can be installed and removed as a single unit. The filters shall be linked along either the length or width dimensions. Filter panels shall be designated in accordance with Table III. TABLE III. Typ
13、e III filter panel link designation. Standard Navy or Commercial Filter Size Designation Type III Filters Internal Frame Size (inch) + 1/8 Joined on Side S=Short L=Long X=Square No. of Links 10AF 7-1/8 x 7-1/8 X AR* 11AF 12-3/8 x 7-7/8 S AR 11AF 12-3/8 x 7-7/8 L AR 12AF 14-3/8 x 9-7/8 S AR 12AF 14-3
14、/8 x 9-7/8 L AR 13AF 9-7/8 x 21-7/8 S AR 13AF 9-7/8 x 21-7/8 L AR14AF 15-3/8 x 24-3/8 S AR 14AF 15-3/8 x 24-3/8 L AR 15AF 19-3/8 x 19-3/8 X AR 16AF 19-3/8 x 29-3/8 S AR 16AF 19-3/8 x 29-3/8 L AR Com20x25 19-3/8 x 24-3/8 S AR Com20x25 19-3/8 x 24-3/8 L AR * As Required 2.2.4 Type IV filter sleeves. T
15、ype IV filter sleeves shall be open at one end so that an internal frame, of length and width dimensions as shown in Table II, can be inserted into the sleeve. The filter frame and sleeve shall fit into the standard Navy filter housings and other common filter housings found on Navy ships. Type IV f
16、ilter sleeves shall be sized in accordance with Table IV. TABLE IV. Type IV filter sleeves. Standard Navy Filter Size Designation Type IV Filters (Sleeves) Min Opening if on Short Side (inch)Type IV Filters (Sleeves) Min Opening if on Long Side (inch) 10AF 7- 7- 11AF 8 12-12AF 10 14-13AF 10 2214AF 1
17、5- 24- 15AF 19- 19-16AF 19- 29-Com20x25 19- 24- 3 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-A-A-59319 2.2.5 Type V filter cubes. Type V filter cubes shall be extended surface filters of a basic bag shape and have an internal frame with exterior
18、 dimensions as shown in Table V. The filters shall be 15 inches deep and tapered in the direction of airflow. TABLE V. Type V filter cubes. Standard Navy Filter Size Designation Type V Filters (Cubes) Internal Frame Size (inches) + 1/16 Depth (inches) 10AF N/A N/A 11AF 12-1/2 x 8 15 12AF 14-1/2 x 10
19、 15 13AF 10 x 22 1514AF 15-5/8 x 24-5/8 15 15AF 19-5/8 x 19-5/8 15 16AF 19-5/8 x 29-5/8 15 Com20x25 19-5/8 x 24-5/8 15 3. SALIENT CHARACTERISTICS. 3.1 Description. The filters shall be used to remove dirt particles from the air in ventilation supply and air conditioning recirculation systems to prot
20、ect HVAC equipment and to provide a clean environment. Air velocity will be up to a maximum of 900 feet per minute. The filter shall perform in accordance with requirements herein under ambient temperatures between -10 and +120 F. 3.2 Construction requirements. 3.2.1 General requirements. 3.2.1.1 Fi
21、lter material. The filter material shall be constructed of synthetic non-woven fibers. When a multiple ply or progressive density material is used, the fibers on the air inlet side shall be of heavier weight (more open) than the fibers on the air outlet (downstream) side. 3.2.1.2 Tackifiers. A non-m
22、igratory tackifier may be used throughout the material or on the air outlet side. Tackifiers shall not run at a temperature of less than 150 F. 3.2.1.3 Marking. If the filter is unidirectional, the downstream side of the filter material shall be colored, tackified, or printed with the words “DOWNSTR
23、EAM”, “AIR LEAVING SIDE” or other information. The inlet side shall not be labeled. 3.2.2 Filter pads (type I). 3.2.2.1 Material thickness. The filter material shall be a minimum of 0.75 inch and a maximum of 2 inches thick. 3.2.3 Internal frames for filter panels (type II), filter panel links (type
24、 III) and filter cubes (type V). 3.2.3.1 Construction. The internal frame shall be constructed of galvanized or stainless steel, or other material satisfying the requirements of UL 900 Class 1. 4 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-A-A-59
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYAA593192003DISPOSABLEAIRFILTERSFORENVIRONMENTALCONTROLSYSTEMS 环境 控制系统 任意 使用 空气 过滤器 PDF

链接地址:http://www.mydoc123.com/p-976399.html