ITU-T SERIES L SUPP 12-2014 ITU-T L 1300 C Supplement on experimental studies on plates and ducts installed at equipment inlets and outlets (Study Group 5)《ITU-T L 1300 补充对安装在设备的进口.pdf
《ITU-T SERIES L SUPP 12-2014 ITU-T L 1300 C Supplement on experimental studies on plates and ducts installed at equipment inlets and outlets (Study Group 5)《ITU-T L 1300 补充对安装在设备的进口.pdf》由会员分享,可在线阅读,更多相关《ITU-T SERIES L SUPP 12-2014 ITU-T L 1300 C Supplement on experimental studies on plates and ducts installed at equipment inlets and outlets (Study Group 5)《ITU-T L 1300 补充对安装在设备的进口.pdf(18页珍藏版)》请在麦多课文档分享上搜索。
1、 I n t e r n a t i o n a l T e l e c o m m u n i c a t i o n U n i o n ITU-T Series L TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Supplement 12 (12/2014) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF CABLES AND OTHER ELEMENTS OF OUTSIDE PLANT ITU-T L.1300 Supplement on experimental stud
2、ies on plates and ducts installed at equipment inlets and outlets ITU-T L-series Recommendations Supplement 12 L series Supplement 12 (12/2014) i Supplement 12 to ITU-T L-series Recommendations ITU-T L.1300 Supplement on experimental studies on plates and ducts installed at equipment inlets and outl
3、ets Summary Supplement 12 to ITU-T L-series Recommendations describes experimental studies on plates and ducts installed at equipment inlets and outlets based on Recommendation ITU-T L.1300. More precisely, this Supplement provides a problem description of practical solutions for correcting airflow
4、direction for equipment, highlighting, at the same time, examples of practical solutions as well as experimental results. History Edition Recommendation Approval Study Group Unique ID* 1.0 ITU-T L Suppl. 12 2014-12-19 5 11.1002/1000/12440 Keywords Best practice, data centre, energy efficient, inform
5、ation and communication technology and climate change (ICT examples of practical solutions; and experimental results. 2 Definitions None. 3 Abbreviations and acronyms This Supplement uses the following abbreviations and acronyms: BT Bottom-to-Top CRAC Computer Room Air Conditioner PDU Power Distribu
6、tion Unit RL Right-to-Left VAV Variable Air Volume 4 Problem description of practical solutions for correcting airflow direction for equipment This clause describes examples of practical solutions for airflow correction. It will enable the recognition of the practical solutions to be taken for equip
7、ment in which airflow correction is necessary. 5 Examples of practical solutions The installation of a plate or duct at the inlet and outlet of the equipment is a practical solution to correct the airflow direction of the equipment. An example of ducts installed in equipment with bottom-to-top (BT)
8、airflow direction is shown in Figure 1. Installation of such ducts corrects the airflow direction to front-to-rear and separates the intake air and the exhaust air. Such separation prevents the equipment from sucking in the exhaust air of adjacent equipment and prevents increases in its temperature.
9、 Experimental studies on plates and ducts installed at the inlets and outlets of equipment with bottom-to-top airflow direction and with right-to-left (RL) airflow direction are shown below. 2 L series Supplement 12 (12/2014) Figure 1 Examples of types of rack mount equipment in which airflow correc
10、tion is necessary An example of a duct installed at the inlet of equipment that is small in depth is shown in Figures 2 and 3. Such a duct directs the cold air in front of the rack to the inlet of the equipment and enables cold air to be supplied to the equipment sufficiently. Figure 2 Example of du
11、ct installation in equipment with bottom-to-top airflow direction L series Supplement 12 (12/2014) 3 Figure 3 Example of duct installation in equipment that is small in depth An example of the description given in an installation manual is shown in Figure 4. 4 L series Supplement 12 (12/2014) Figure
12、 4 Example of a description given in an installation manual 6 Experimental results The purpose of the experimental studies was to evaluate the effectiveness of the plates and ducts installed at the inlets and outlets of equipment with different airflow direction from the data centre airflow design.
13、L series Supplement 12 (12/2014) 5 6.1 Outline of experiment The layout of the experiment room, and equipment used for the experiment are illustrated in Figures 5 and 6 respectively. Four types of equipment and power distribution units (PDUs) were mounted on two open racks. A plate or a duct was ins
14、talled at the inlet and the outlet of two types of rack mount equipment, whose airflow direction was bottom-to-top (Type BT) and right-to-left (Type RL). The temperature was measured at 100, 500, 1000, 1500, and 2100 mm above floor level, at the front and the rear of the rack. It was also measured i
15、nside the raised floor, at the inlet and the outlet of the adjacent equipment. The room temperature setting and the outlet temperature setting of the computer room air conditioning (CRAC) were 24C and 19C, respectively. The CRAC was set to keep the air supply temperature constant and to operate in v
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ITUTSERIESLSUPP122014ITUTL1300CSUPPLEMENTONEXPERIMENTALSTUDIESONPLATESANDDUCTSINSTALLEDATEQUIPMENTINLETSANDOUTLETSSTUDYGROUP5ITUTL1300

链接地址:http://www.mydoc123.com/p-803333.html