ITU-T K 8-1988 SEPARATION IN THE SOIL BETWEEN TELECOMMUNICATION CABLES AND EARTHING SYSTEM OF POWER FACILITIES《土壤中通信电缆与电力装置接地系统间的隔距-抗干扰防护(研究组5)5页》.pdf
《ITU-T K 8-1988 SEPARATION IN THE SOIL BETWEEN TELECOMMUNICATION CABLES AND EARTHING SYSTEM OF POWER FACILITIES《土壤中通信电缆与电力装置接地系统间的隔距-抗干扰防护(研究组5)5页》.pdf》由会员分享,可在线阅读,更多相关《ITU-T K 8-1988 SEPARATION IN THE SOIL BETWEEN TELECOMMUNICATION CABLES AND EARTHING SYSTEM OF POWER FACILITIES《土壤中通信电缆与电力装置接地系统间的隔距-抗干扰防护(研究组5)5页》.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、INTERNATIONAL TELECOMMUNICATION UNION)45G134 + TELECOMMUNICATIONSTANDARDIZATION SECTOROF ITU02/4%#4)/.G0G0!).34G0G0).4%2 modified at Melbourne, 1988)IntroductionIf a buried telecommunication cable without an insulating layer around the metal sheath is located in thevicinity of a high voltage earthin
2、g system, part of the earth potential rise (EPR) in the event of an earth fault in the highvoltage system can transfer to the telecommunication system through resistive coupling.According to CCITT and CIGRE1)documents 1-3, EPR from high voltage power installations is recognizedas a source of dangero
3、us disturbance to telecommunication systems and a hazard to service personnel.It is possible to calculate EPR near power installations following the methods given in the Directives 1 (seeVolumes II and III), and this is especially recommended for dealing with switchyard earthing systems.The object o
4、f the present Recommendation is to give practical guidelines in determining safe distances betweenburied telecommunication cables and earthing systems of power facilities in the absence of local measurements orcalculated values of EPR.1 ScopeEarth fault in a power system causes earth currents which
5、raise the earth potential where the fault current leavesand enters the earth. The magnitude and extension of the EPR depends on the fault current level, the earthingresistance, the soil resistivity and the layout of the earthing arrangement. The duration of an earth fault depends on thetype of power
6、 network.This Recommendation gives information about:a) locations where EPR may occur;b) duration of EPR in different types of power networks;c) “safe distance” between telecommunication cables and power installations;d) measures to be taken if the safe distance is not achieved.2 General considerati
7、onsThe minimum separation in soil to be recommended between an earthing system of a power installation andtelecommunication cables depends on a number of factors: type of power network; fault current level; power earthing system; soil resistivity; local conditions.3 Type of power networkPower networ
8、ks are classified according to how the neutral point is connected to earth. The earthing systemaffects both the level and duration of the fault current, and hence the EPR._1)CIGRE International Conference on Large High-Tension Electric Systems.2 Volume IX - Rec. K.83.1 Networks with the neutral poin
9、t earthed directly or through a low impedanceThe level of an earth-fault current is high. A relay system will clear the fault in a short time.3.2 Networks with the neutral point earthed through an arc suppression coilThe level of an earth-fault current is small, usually not exceeding 100 amperes for
10、 each coil. The duration of anearth fault is relatively short.Such networks may be equipped with delayed tripping to clear permanent earth faults.3.3 Networks with the neutral point isolated from earthThe level of an earth-fault current is normally low, but the fault duration might be very long. Net
11、works of largeextent may give rise to large capacitive fault currents.If such networks are equipped with devices for automatic fault clearing, the fault duration is short to medium.4 Locations where earth potential rise may occur4.1 Power stations and sub-stationsPower stations and sub-stations are
12、most likely to experience EPR. The size of the station, the number andconstruction of power lines attached to the station, and the earthing arrangement are factors influencing the level andstation, and the earthing arrangement are factors influencing the level and zone of EPR. As given in reference
13、4 thelayout and structure of the earthing arrangement depends on regulations, size, age, purpose and location. If the powerlines entering the station are provided with earth wires, they will be connected to the earthing system in the station.4.2 Power line towersPower line towers with footing electr
14、odes are subjected to EPR due to earth-fault current in the power system,and currents from lightning strikes. If the power line is equipped with earth wires, these will normally be connected tothe tower electrodes. The probability of high EPR decreases when a power line is equipped with earth wires.
15、5 Magnitude of earth potential riseThe magnitude of the EPR depends on the power system voltage, the power line construction, the fault currentlevel and the earthing resistance.6 Zone of earth potential riseEPR is measured as the earth potential referred to a distant neutral earth. The zone of EPR,
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ITUTK81988SEPARATIONINTHESOILBETWEENTELECOMMUNICATIONCABLESANDEARTHINGSYSTEMOFPOWERFACILITIES 土壤 通信 电缆

链接地址:http://www.mydoc123.com/p-799320.html