1、Electrical Guide forControl CentersApproved 28 June 1978ISARP60.81978RECOMMENDED PRACTICEISA The Instrumentation,Systems, andAutomation Society TMCopyright 1978by the Instrument Society of America. All rights reserved. Printed in the UnitedStates of America. No part of this publication may be reprod
2、uced, stored in a retrieval system, ortransmitted in any form or by any means (electronic, mechanical, photocopying, recording, orotherwise), without the prior written permission of the publisher.ISA67 Alexander DriveP.O. Box 12277Research Triangle Park, North Carolina 27709ISARP60.81978, Electrical
3、 Guide for Control CentersISBN 0-87664-444-2ISA-RP60.8-1978 3PrefaceThis Preface is included for information purposes and is not part of ISA-RP60.8-1978.This Standard has been prepared as a part of the service of ISA toward a goal of uniformity in the field of instrumentation. To be of real value, t
4、his document should not be static, but should be subject to periodic review. Toward this end, the Society welcomes all comments and criticisms, and asks that they be addressed to the Secretary, Standards and Practices Board, ISA, 67 Alexander Drive, P.O. Box 12277, Research Triangle Park, North Caro
5、lina 27709, Telephone (919) 549-8411, e-mail: standardsisa.org.The ISA Standards and Practices Department is aware of the growing need for attention to the metric system of units in general, and the International System of Units (SI) in particular, in the preparation of instrumentation standards. Th
6、e Department is further aware of the benefits to USA users of ISA Standards of incorporating suitable references to the SI (and the metric system) in their business and professional dealings with other countries. Towards this end this Department will endeavor to introduce SI and SI-acceptable metric
7、 units in all new and revised standards to the greatest extent possible. The Metric Practice Guide, which has been published by the American Society for Testing and Materials as ANSI designation Z210.1 (ASTM E380-76, IEEE Std. 268-1975), and future revisions, will be the reference guide for definiti
8、ons, symbols, abbreviations, and conversion factors. ISA S60 is an overall set of recommended practices being compiled by the ISA Control Centers Committee. RP60.8 is the first of this series to be issued.SECTION TITLERP60.1 Control Center (C.C.) FacilitiesRP60.2 C.C. Design Guide and TerminologyRP6
9、0.3 Human Engineering for Control CentersRP60.4 Documentation for Control CentersRP60.5 Control Center Graphic DisplaysRP60.6 Nameplates, Labels, Tags and Terminal IdentificationRP60.7 Control Center ConstructionsRP60.8 Electrical Guide for Control CentersRP60.9 Piping Guide for Control CentersRP60.
10、10 Control Center Inspection and TestingRP60.11 Crating, Shipping and Handling for C.C.The persons listed below served as active members of the ISA Control Centers Committee for the major share of its working period.NAME COMPANYH. R. Solk, Chairman Comsip Customline Corp.C. S. Lisser Oak Ridge Natio
11、nal LabR. W. Borut M. W. Kellogg Co.J. M. Fertitta, Secretary The Foxboro Co.A. R. Alworth Shell Oil Co.M. Arevalo Fischer it is also intended to comply with the provisions of the National Electrical Code. What follows are the practices normally used by architects, engineers, user organizations and
12、control center manufacturers. Special considerations which may apply to particular devices or circuits are not taken into account in this section.2 General2.1 ApplicationThis Section of ISA-RP60 applies to the inter-connection wiring between devices within a control center, or between control center
13、s. It does not apply to the internal wiring of an instrument or device, nor to the wiring between the control center and field-mounted instruments.2.2 ComplianceAll wiring recommendations in this Standard are intended to comply with the National Electrical Code. Compliance with other applicable loca
14、l or industry codes requires specific reference in the control center specification. General references to these codes should be avoided.2.3 Wiring2.3.1 Power wiringEach device requiring control center power shall be wired so that when wires are removed from any one device, power will not be disrupt
15、ed to any other device. It is recommended that no voltages greater than 125 Vdc or 120 Vac be used. If higher voltages are required, refer to color coding below. Provisions should be made for power wire segregation and identification to insure personnel safety.The recommended minimum size for power
16、wiring up to 15 A is #14 stranded copper conductor, 600 V, 60 C with thermo-plastic insulation. Different insulation material should be considered if the insulation has to be self-extinguishing or nontoxic. Refer to Table 310-13 “Conductor Application and Insulations“ of the National Electrical Code
17、, latest revision for particular provisions. Where power is 150 W or less and run to each instrument through a separate fuse or circuit breaker, the wire size can be reduced to #16 or #18. Refer to Article 310 “Conductors for General Wiring“ in the National Electrical Code, latest revision for curre
18、nts greater than 15A.2.3.1.1 Color coding of ac power wiring1) 120 Vac, 2 wire, single phase: Phase1 or L1, black NeutralN or L2, white2) 120/240 Vac or 120/208 Vac, 3 wire, single phase with neutral:Phase 11 or L1, black10 ISA-RP60.8-1978Phase 22 or L2, redNeutralN, white3) 240 Vac, 2 wire, single
19、phase: 1 or L1, black2 or L2, red4) Any 3-phase circuit regardless of voltage: Phase 11 or L1, black Phase 22 or L2, red Phase 33 or L3, blue Neutral in 4-wire systemN, white5) Interlock control circuits wired from an external power source:yellow6) Case ground wire, if insulatedgreen or green with o
20、ne or more yellow stripes.2.3.1.2 Color coding of dc power wiringDue to numerous voltage levels and existing standards, it is recommended that distinctive colors be used which do not conflict with other colors being used.2.3.1.3 Circuit protectionIn addition to circuit protection requirements of the
21、 National Electrical Code, special circuit considerations must be given. In particular, the solution to the problem of the failure of any device in a system which will cause loss of power for that system or other systems.2.3.2 GroundingEach device requiring power should be grounded to the control ce
22、nter by mounting to effect a conducting path or by a ground wire. Ground wire size should be no less than the supply conductor wire size. To determine wire size for grounding of control center to earth ground, refer to Table 250-95 “Size of Equipment Grounding Conductors for Grounding Raceway and Eq
23、uipment“ of the National Electrical Code, latest revision.2.3.3 Control wiringControl wiring is considered distinct from power or signal wiring. This type involves wiring of push buttons, pilot lights, selector switches, relay logic, timers and programming devices. Recommendations for wire sizes, fu
24、sing and color codes may be found in the Joint Industrial Council Electrical Standards for General Purpose Machine Tools EGP-1-67.2.3.4 Signal wiringNormal usage for signal wiring is #18 AWG stranded copper conductor. The recommended minimum wire size is #24 AWG, which should be used in a multicondu
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ISARP6081978ELECTRICALGUIDEFORCONTROLCENTERS 控制中心 用电 指南 PDF

链接地址:http://www.mydoc123.com/p-789919.html