《ICEA S-76-474-2011 NEUTRAL-SUPPORTED POWER CABLE ASSEMBLIES WITH WEATHER-RESISTANT EXTRUDED INSULATION RATED 600 VOLTS《中性线支撑的额定值600伏特的抗风化挤制绝缘电力电缆组件》.pdf》由会员分享,可在线阅读,更多相关《ICEA S-76-474-2011 NEUTRAL-SUPPORTED POWER CABLE ASSEMBLIES WITH WEATHER-RESISTANT EXTRUDED INSULATION RATED 600 VOLTS《中性线支撑的额定值600伏特的抗风化挤制绝缘电力电缆组件》.pdf(33页珍藏版)》请在麦多课文档分享上搜索。
1、ANSljlCEA S-76-4 7 4-2011 I -I I (j) II . ,.I STANDARD FOR NEUTRAL-SUPPORTED POWER CABLE ASSEMBLIES WITH WEATHER-RESISTANT EXTRUDED INSULATION RATED 600 VOLTS Approved by AMERICAN NATIONAL STANDARDS INSTITUTE July 15, 2011 Publication # ANSI/ICEA S-76-474-2011 I I I I I I I I I I I I I I 2011 by I I
2、I INSULATED CABLE ENGINEERS ASSOCIATION, Inc. I II I II I II I II I II I II I II I II I I I I I I I I Approved as an American National Standard ANS! Approval Date: July 16. 2011 ANSI/ICEA Publication S-76-474 - 2011 Standard For Neutral-Supported Power Cable Assemblies With Weather-Resistant Extrude
3、d Insulation Rated 600 Volts Developed and Published By Insulated Cable Engineers Association, Inc. Post Office Box 1568 1“ _ . 11+,. “ .,i. “ln1-t., I 1. 5-76-474-2011 Pageiv ICEA publications are adopted in the public intai6st and SiG designed to eliminate misunderstanding between the manufacturer
4、 and user and to assist the user in selecting and obtaining proper products for his particular need El(istenc.e of an !CE.I. pubHc.!tion does not in any respect preclude the manufacture or use of products not conforming to the publication. The user of this publication is cautioned to observe any app
5、licable heaHh or safety regulations and rules relative to the manufacture and use of cable made in conformity with this publication. This publication hereafter assumes that manufacture, testing, installation and maintenance of cables defined by this publication will be performed only by properly tra
6、ined personnel using suitable equipment. Questions of interpretation of !CE.I. publications can only be accepted in writing at Headquarters by the Secretary, and the reply shall be provided in writing. Suggestions for improvements in this publication are welcome, and should be sent to ICEA at the ad
7、dress below. Copyrighted by the ICEA Contents may not be reproduced in any form without permission of the INSULATED CABLE ENGINEERS ASSOCIATION, INC. Post Office Box 1568 Carrollton, Georgia 30112, USA Telephone: (770) 830-0369 2011 by the Insulated Cable Engineers Association, Incorporated Section
8、1 GENERAL 1.1 SCOPE ICEA S-76-474-2011 Page 1 This staiidaid applies to the matenals, constructions, and tasting of assemblies of extruded dielectric insulated electric current carrying phase conductors and bare or covered neutral electrical conductors used as weather-resistant wires and cables susp
9、ended from supporting structures for the overhead distribution of electrical energy. This standard is intended to apply to the following multiplexed wire and cable constructions: Neutrai Supported Service Drop Cabies, ami Neutral Supported Secondari Cistrib;1ion Cables. The use of these service drop
10、 and secondary distribution cables is limited to Circuits not exceeding 600 volts phase-to-phase. or 480 volts phase-to-ground. and to a normal service conductor temperature rating of 75C or goc. When reference is made in this publication to an industry standard. that reference is to the standard wi
11、th . _ .t.il.I _ .1_JAIOlIl03 UV“UfCCIl LlIIW 1 . “Iun IIIQI“ “I LlII,wo standard and those of a referenced standard, the requirements of this standard shall apply. In this standard, units are most often expressed in the English System. To convert from an English unit to the appropriate metric unit,
12、 multiply the value of the English unit by the appropriate number from Appendix B. The recommended bending radii for phase conductors and cable assemblies is given in Appendix C. U.S. customary units, except for temperature, are specified throughout this standard. Approximate International System of
13、 Units (SI) equivalents are included for information only. 1.2 ASSEMBLIES Multiplexed cable assemblies are composed of one or more phase conductors assembled with a neutral conductor. The neiJ“tral conductor may be bare Oi covered with an extruded Weather-resistant loo-v/linaar 10:; UI lilt: UIIIUt:
14、1 t,;UVt:IIIIY, WIlt:1I U:it:U, 0)1IC111 LIt: lIIt:ts:tUICU III cn . AJIUClIllil: WIlli IvlJ“ T-27-581INEMA WC 53. The minimum thickness at any point of the covering shall not be less than the app!ic.ab!e va!ue in Tab!e 31. 2011 by the Insulated Cable Engineers Association. Incorporated 3.4 SEPARATO
15、R Table 3 1 MINIMUM THICKNESS OF THE BINDER COVERING Binder Size AWG 10 Thickness. mils(mm) LOPE I LLOPE I MOPE 27 (0.69) HOPE 14 (0.36) ICEA 5-76-474-2011 Page 13 A separator may be used between a solid or stranded conductor and the insulation or covering. If a separator is used. it shall be opaque
16、 or colored. A clear separator is not permitted. 3.5 ELECTRICAL REQUIREMENTS 3.5.1 Voltage Tests When tested in accordance with ICEA T-27-581INEMA WC 53. each phase conductor of each manufacturing or finished length shall successfully withstand either of the following tests: 3.5.1.1 After the cable
17、is immersed in water for 30 minutes. an ac voltage of 3000 volts shaii be applied for one minute between the phase conductor(s) and the water. 3.5.1.2 A spark test of 8.5 kV ac or 13.0 kV de voltage shall be applied. The test shall be c.onducted on the finished assembly of conductors with the neutra
18、l isolated from the applied voltage. Where an assembly is subject to the direct current spark test. the individual phase conductors shall be similarly tested prior to assembly. 3.6 INSULATION OR NEUTRAL COVERiNG REQUiREMENTS 3.6.1 Thickness Requirements 3.6.1.1 Insulation Thickness When measured in
19、accordance with ICEA T-27-581/NEMA WC 53. the minimum thickness at any point of the insulation shall not be less than the applicable value in Table 3-2. 3.6.1.2 Neutral Covering Thickness ,AJhsn measured in accordance with !CE.-A T-27-581!NE.A.,.t AJC 53. the minimum thickness at any point of the ne
20、utral covering shall not be less than the applicable value in Table 3-3. 3.6.2 Physical Requirements 3.6.2.1 Insulation Physical Requirements The insulation shall meet the requirements in Table 3-4. 2011 by the Insulated Cable Engineers Association. Incorporated ICEA 5-76-474-2011 Page 14 3.6.2.2 Ne
21、utral Covering Physical Requirements The neutral covering shall meet the requirements in Table 3-4. Conductor Size AWGorkcmii 8-2 1 - 4/0 250 - 477 Table 3-2 MINIMUM THICKNESS OF INSULATION Minimum Thickness Mils (mm) 41 (1.0) 54 (1.4) 72 (1.8) Nominal Thickness Miis(mmi 45 (1.1) 60 (1.5) 80 (2.0) T
22、he nominal insulation thicknesses are not requirements. They are included for information purposes only. iabie 3-3 MINIMUM THICKNESS OF NEUTRAL COVERING Conductor Size AWGorkcmil Minimum Thickness Mils (mm) Nominal * Thickness Mils (mm) 8 - 4 27 (0.69) 30 (0.76) 2-1 41(1.0) I 45(1.1) 35-7 ! g : ! g
23、:l The nominal insulation thicknesses are not requirements. They are included for information purposes on!y. 2011 by the Insulated Cable Engineers Association, Incorporated Property Density (gm/cm1 t Initial Tensile, min. psi. (MPa) Initial Elongation at Rupture, Minimum, perc-ent (See 6.1) After Ag
24、ing in air oven, Hours Temperature, C 1C Tensile Strength and Elongation at rupture: OL ,f I InClI“IM /aliIA IV l:f . . (See 6.1) Heat Distortion Temperature, C 1C Maximum percentage of Originai thickness (a) 266.8 kcmil and smaller (b) Larger than 266.8 kcmil (See 6.2) Hot Creep Temperature, C 2C E
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ICEAS764742011NEUTRALSUPPORTEDPOWERCABLEASSEMBLIESWITHWEATHERRESISTANTEXTRUDEDINSULATIONRATED600VOLTS

链接地址:http://www.mydoc123.com/p-783238.html