1、FORD MANUFACTURING STANDARDS ES20 DISCONNECTS AND OPERATING MECHANISMS ES20 SEPTEMBER 1995 AND SAFETY SWITCHES Page 1 1. SCOPE: 1.1 1.2 1.2.1 1.2.2 1.2.3 1.2.4 1.2.5 1.3 1.3.1 This Standard applies to disconnects and operating mechanisms used in combination motor starters and industrial equipment en
2、closures at 600 Vat and below. It also applies to separately mounted safety switches used for service disconnects and on auxiliary equipment. DEFINITIONS APPLICABLE TO THIS STANDARD: The DISCONNECT is any disconnect switch, circuit breaker, fusible molded case switch (FMCS), or safety switch applied
3、 as the means of disconnecting the industrial equipment from the electrical power source(s). The OPERATING MECHANISM includes the external handle, linkage, and yoke or other coupling to the disconnect. The EXTERNAL HANDLE is that portion of the operating mechanism mounted on the enclosure flange or
4、to the right side of the enclosure for safety switches. The LINKAGE is the mechanical connection between the external handle and the yoke or coupling. The YOKE or COUPLING is the device which operates the disconnect. REFERENCE STANDARDS: Devices furnished under this standard shall conform with the l
5、atest revisions of the following standards, except where differences exist this standard shall.take precedence. Ford Manufacturing Standard EKl and EK3 ANSI/NFPA 70, “National Electrical Code“, (N.E.C.) National Electrical Manufacturers Association (NEMA) AB-1, “Molded Case Circuit Breakers and Swit
6、ches.“ Nema KS-l, “Enclosed Switches,“ (Type HD) HEAVY DUTY. Underwriters Laboratories (UL) 98, “Enclosed and Dead-Front Switches.“ UL 489, “Molded Case Circuit Breakers and . Circuit-Breaker Enclosures.“ UL 508, “Industrial Control Equipment.“ UL 1087, “Molded Case Switches.“ All disconnects shall
7、be UL listed for use in USA and/or CSA certified for use in Canada in accordance with the above standards and shall bear the mark(s) of these agencies. FORD MANUFACTURING STANDARDS - ES20 DISCONNECTS AND OPERATING MECHANISMS SEPTEMBER 1995 AND SAFETY SWITCHES ES20 Page 2 2.3.1 2.3.2 1.4 2. 2.1 2.2 2
8、.3 MANDATORY AND PREFERRED ITEMS: Mandatory requirements of this Standard are characterized by the use of the word “shall.“ Preferred items are characterized by the use of the word “should.“ ROTARY DISCONNECT OPERATORS ARE NOT ACCEPTABLE, unless they conform with all the requirements of this standar
9、d. EXCEPTION: Switches which are an integral part of Ford-approved, UL listed transformer/disconnect assemblies up to 3.0 KVA are excepted, (refer to Ford Standard EW3). Rotary disconnects having permanently affixed handles operating through either a gasketed hole in the enclosure door or through th
10、e side of the enclosure shall not be used, unless they conform to this standard and Ford Standard EKl, and have been accepted in writing by Ford Controls Engineering and Safety Engineering as part of the bid submitted by the equipment seller. LOCKOUT OF MOTION OR OTHER HAZARDS: Transformer/disconnec
11、t assemblies shall not be used as power sources for equipment motions or other hazards - unless these hazards are capable of being de-energized and locked out with other disconnects meeting this standard - in strict accordance with Ford Energy Control and Power Lockout (ECPL) policies and procedures
12、. NOTE: The plug on cord-and-plug connected equipment is considered a disconnect if it is capable of being removed from its receptacle to isolate the equipment from its power source and the plug can be locked out. Other equipment may require its own knife-blade safety switch. SUPPLEMENTAL REQUIREMEN
13、TS FOR OFF-THE-SHELF EQUIPMENT: Where commercially available, “off-the-shelf“ equipment, which involves no custom engineering, cannot practicably be furnished with flange- mounted disconnects, it shall be equipped with a disconnect which fully conforms to this standard and Standard Exl. This will ty
14、pically be a NEMA 12, knife-blade safety switch mounted to the outside of the main electrical enclosure. This primary disconnect shall be installed between the power source and the line side of whatever disconnecting means is furnished within the electrical enclosure of the equipment. ECPL placards
15、and required labels shall identify this primary safety switch or disconnect as the “Main Electrical Disconnect (El)“ while the disconnecting means furnished within the enclosure of the equipment shall be designated as “(E2).“ FORD MANUFACTURING STANDARDS ES20 DISCONNECTS AND OPERATING MECHANISMS ES2
16、0 SEPTEMBER 1995 AND SAFETY SWITCHES Page 3 2.4 2.5 3. 3.1 In all cases, the disconnecting means furnished inside the enclosure of the “off-the-shelf“ equipment shall provide the mechanical door-to-disconnect interlock required under this standard and Ford Standard EXl. Self-enclosed, rotary switche
17、s are not acceptable as substitutes for Ford-approved, knife-blade safety switches which conform to this standard. PREFERRED DISCONNECTS: Unless otherwise specified by the requisitioning activity, a fusible disconnect switch is preferred where the total load is less than 200 Amps. For loads of 200 A
18、mps and more a circuit breaker or (FMCS) is preferred. Circuit breakers shall be selected and applied so their UL listed interrupting rating exceeds the short-circuit current available at their line terminals at the supply voltage. Circuit breakers fed directly from substations will generally requir
19、e higher interrupting ratings than those fed from fusible switches or busplugs containing Ford-approved, current-limiting power fuses. 4. DISCONNECT REQUIREMENTS: 4.1 Switches shall have knife blades or movable contacts which provide readily visible, positive indication of being open in the OFF posi
20、tion. 4.2 Switches shall be rated in.both Amperes and horsepower. 4.3 Circuit breakers or (FMCS) shall have a position indicator which cannot indicate OFF until all contacts are actually open with an adequate isolating distance between the contacts in conformance with NRMA and NFPA 70 requirements f
21、or the maximum voltage rating involved. 4.4 Safety switches shall have NEMA 12 enclosures unless otherwise required by their operating environment. Types without knockouts should be specified. 4.4.1 Auxiliary Contacts: UL listed, N.O./N.C. electrical interlock kits shall be available for safety swit
22、ches from approved manufacturers. These interlocks shall open their contact(s) slightly before the safety switch opens. FOR0 MANUFACTURING STANDARDS ES20 DISCONNECTS AND OPERATING MECHANISMS SEPTEMBER 1995 AND SAFETY SWITCHES ES20 Page 4 4.5 OPERATING HANDLE PERMANENTLY AFFIXED: The operating handle
23、 shall be permanently affixed to the disconnecting means. The linkage shall be a solid rod or bar and SHALL BE SUCH THAT THE OPERATING HANDLE IS IN CONTROL OF THE DISCONNECT AT ALL TIMES, including when the door(s) is/are open. 5. GENERAL REQUIREMENTS: 5.1 CONDUCTOR TERMINATION: 5.1.1 Protection: Th
24、ere shall be no exposed live parts in the OFF (open) position. An insulating cover or shield or other means shall be provided by the disconnect manufacturer as a component part of their UL listed assembly to guard against inadvertent contact with the line terminals. Where provided, test prod access
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- FORDES201995DISCONNECTSANDOPERATINGMECHANISMSANDSAFETYSWITCHES 断开 操作 机制 安全 开关 PDF

链接地址:http://www.mydoc123.com/p-744820.html