FORD EFX-1994 POWER FACTOR CORRECTION《功率因数校正》.pdf
《FORD EFX-1994 POWER FACTOR CORRECTION《功率因数校正》.pdf》由会员分享,可在线阅读,更多相关《FORD EFX-1994 POWER FACTOR CORRECTION《功率因数校正》.pdf(9页珍藏版)》请在麦多课文档分享上搜索。
1、FORD MANUFACTURING STANDARDS = EFX POWER FACTOR CORRECTION EFX JUNE 1994 Page 1 = 1. SCOPE: 1.1 This Standard prescribes the application of power factor correction capacitors to individual as well as groups of electric motors used on production machines and equipment. 1.2 Capacitors, enclosures, wir
2、ing, and installation shall conform as applicable to this Standard and the following: A. Ford Manufacturing Standard, EXl, “Electrical Standard for Mass Production Equipment“. B. Ford Manufacturing Standard, EMl, “AC Electric Motors, Totally -Enclosed Type“. C. Ford Manufacturing Standard, EMlX, “AC
3、 Electric Motors, Totally- Enclosed Design and Reference Data“. D. ANSI/NFPA 70, “National Electrical Cadet (NEC), Article 460, Section A, as it pertains to capacitors rated under 600 VAC nominal. 1 E. NEMA CP-1, “Shunt CapacitorsI. 2. APPLICATION: 2.1 2.2 2.3 2.4 2.4.1 The correction specified in T
4、able 1 applies only to totally enclosed, U frame, NEMA design B (normal slip) and NEMA design D (5 - 8 percent slip) motors used on 480 V, three phase, 60 Hertz applications. NEMA design D motors below 75 HP should be corrected the same as design B motors. For more detailed motor specifications see
5、Standards EM1 and EMlX. For other types of motors consult the motor manufacturer for power factor correction requirements. Power factor correction capacitors shall be included as described in this Standard when specified on the Electrical Equipment Data Form (Form 2630). The word “shall“ as used in
6、this Standard is understood as a requirement; the word “should“ as a preference. DEFINITIONS: For purposes of this Standard the following definitions shall apply: Capacitor Cell - A capacitor cell is a single three phase capacitor. FORD MANUFACTURING STANDARDS = EFX POWER FACTOR CORRECTION EFX JUNE
7、1994 Page 2 = 2.4.2 Capacitor Assembly - A capacitor assembly is a single cell or two capacitor cells connected in parallel to make up the total required KVAR and housed in a NEMA I2 enclosure. 2.4.3 Multiple Capacitor Assembly - Two or more capacitor assemblies housed in a common NEMA 12 enclosure
8、and wired independently for two or more separate motor circuits. 3. CAPACITOR REQUIREMENTS: 3.1 Capacitor cells shall be Industrial Grade, rated 480 RMS VAC, three phase, 60 hertz. Three discharge resistors of not more than .47 megohms each and rated not less than one watt, shall be connected to the
9、 capacitor terminals in a closed delta configuration. The resistors shall discharge the capacitor to 50 volts or less within one minute after the capacitor source of supply is disconnected. Capacitor losses shall not exceed 0.5 watts per RvAR. 3.1.1 Capacitor cells utilizing pressure interrupter met
10、al casing, shall disconnect all three phases of power. 3.2 In order to minimize power losses, dielectric materials should include polypropylene or similar film materials. 3.2.1 Capacitor cells shall contain no polychlorinated biphenyls (PCB). 3.3 3.4 Capacitor cells shall be equipped with threaded s
11、tuds and nuts for termination of conductors with ring type connectors. Soldered connections and quick disconnect tab lug terminals are not acceptable. Each capacitor assembly shall have a nameplate which includes all data as specified in NEC, paragraph 460.12. Separate llCAUTION“ tags shall be affix
12、ed to each capacitor listing the name of the liquid dielectric material and the recommended disposal method, and a lCautionlt . Before Opening, Disconnect Main Power . Wait One Minute For Capacitor Discharge. The nameplate and CAUTION tags shall be readable on exterior of capacitor enclosure. FORD M
13、ANUFACTURING STANDARDS = EFX POWER FACTOR CORRECTION EFX JUNE 1994 Page 3 = 4. SELECTION AND APPLICATION: 4.1 GENERAL: 4.1.1 Power factor correction shall not be applied to production machines and equipment where: a) The total motor load is less than 7.5 HP. b) The application uses a single motor fo
14、r: reversing, plugging, jogging, inching, or two-speed operation. c) A clutch, brake, solid state rectifier, or DC voltage is connected to the load side of a motor starter in a single motor application. This exception does not apply when the motor is one of a group of motors being corrected as descr
15、ibed in 4.3.2. d) Motors. regardless of HP rating, are used only for adjustment purposes on an intermittent basis. An example of such limited duty is the slide adjustment motors on a press. e) Motor(s) that are controlled by solid state drives, unless authorized by requesting activity. 4.1.2 Conduct
16、or sizes for capacitor wiring shall be selected from Table 2. 4.2 SINGLE MOTOR APPLICATIONS: 4.2.1 On single motor applications rated 7.5 HP or more, the KVAR correction for NEMA Design B or D motors shall be selected from Table 1. The capacitor(s) shall be connected to the load side of the motor st
17、arter, between the contactor and the overload relay assembly as illustrated in Figure 1. The capacitor connections to the starter shall not restrict ready access to the overload heater elements or reset button. 4.2.2 Wiring between a single starter and the related capacitor(s) shall be identified wi
18、th wrap type adhesive bands marked lC1, lC2, lC3. The numbers shall correspond to the motor terminals to which the capacitor is connected (e.g., 1Cl to lT1, lC2 to lT2, lC3 to lT3). Refer to Figure 1 for an example of proper lead identification. FORD MANUFACTURING STANDARDS -_-_- -_- EFX POWER FACTO
19、R CORRECTION EFX JUNE 1994 Page 4 -_-_- -_- 4.3 MULTIPLE MOTOR APPLICATIONS: 4.3.1 Where a multiple motor application includes a single motor, 60 HP or larger, and one or more other motors with a total of less then 7.5 HP, the installation shall be treated as a single motor application as described
20、in 4.2.1. Example: A punch press with a 150 HP drive motor NEMA Design D, a 3 HP oil pump, and a l/2 HP lubrication pump. The small motors total less then 7.5 HP and are therefore not included. Since the press motor is a NEMA design D. 150 HP, a 45 KVAR capacitor assembly is selected from Table 1. T
21、he capacitor is connected to the starter as shown in Single Motor Applications Figure 1. 4.3.2 4.3.3 In multiple motor applications, KVAR correction shall be determined as follows: a) Each motor 60 HP or larger shall be considered as a single motor application described in 4.2.1. b) The horsepower o
22、f all remaining motors less than 60 HP shall be totalled. The KVAR correction shall be derived from the formula: KVAR = (total horsepower)/3 The capacitor value used shall be selected from Table 1. In all cases the exact or closest lower KVAR value shall be used. See Figure 2 for a typical applicati
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- FORDEFX1994POWERFACTORCORRECTION 功率因数 校正 PDF
