1、FORD MANUFACTURING STANDARD - -_I_- - m-v EEl CONDUIT FITTINGS EEZ DECEMBER 1992 ,. * Page 1 1. SCOPE: 1.1 This standard provides the requirements for conduit fittings used throughout Ford Motor Company to connect conduit to conduit, enclosures, panels or boxes. 2. REFERENCES: 2.1 ANSI/ASME B1.20.1,
2、 “Pipe Threads, General Purpose“ A.NSI/NEMA FBl, “Fittings, Cast Metal Boxes, and Conduit Bodies for Conduit and Cable Assemblies“ ANSI/NFPA 70, “National Electric Code“ - Articles 110, 346 and 370 ASTM A 47, “Standard Specification for Ferritic Malleable Iron Castings“ ASTM A 536, “Standard Specifi
3、cation for Ductile Iron Castings“ ASTM B 117, “Standard Method of Salt Spray (Fog) Testing“ UL 514B, “Fittings for Conduit and Outlet Boxes“ 3. GENERAL 3.1 Conduit fittings shall be made of malleable or ductile cast iron. Gray iron is not acceptable. Dimensions, wall thicknesses and materials shall
4、be in compliance with the standards referenced in item 2.1. All fittings and covers shall be be durably and legibly marked with the manufacturers name or trademark, and any applicable testing agency symbols, listing and certification numbers. 3.2 Conduit fittings, covers and gaskets shall be UL List
5、ed and CSA Certified as may be required for conformance to the National Electric Code, OSHA and other local electrical codes. 3.3 Conduit fitting threads shall be tapered and conform to ANSI/ASME B1.20.1 3.4 Fittings and fitting covers shall be sufficiently plated to with- stand a 100 hour salt spra
6、y test conducted in accordance with ASTM B 117. 3.5 Covers used on fittings may be sheet steel, but shall not be less than 1.8 mm (0.07 in) thick. 3.6 Retaining screws and gaskets used on fitting covers shall be captive to the cover when not assembled to the fitting. 3.7 Gaskets and “0“ rings shall
7、use an oil resistant synthetic material. Paper and cork cover gaskets are not acceptable. Cover gaskets shall be 1.6 mm (l/16 in) thick minimum. FORD MANUFACTURING STANDARD EEl DECEMBER 1992 . . . CONDUIT FITTINGS EEl Page 2 -i ! ;.: 4. RIGID CONDUIT FITTINGS 4.1 Rigid conduit fittings are used to c
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- FORDEE11992CONDUITFITTINGS 导管 配件 PDF