EN 50522-2010 en Earthing of power installations exceeding 1 kV a c .pdf
《EN 50522-2010 en Earthing of power installations exceeding 1 kV a c .pdf》由会员分享,可在线阅读,更多相关《EN 50522-2010 en Earthing of power installations exceeding 1 kV a c .pdf(104页珍藏版)》请在麦多课文档分享上搜索。
1、raising standards worldwideNO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBSI Standards PublicationEarthing of power installations exceeding 1 kV a.c.BS EN 50522:2010Incorporating corrigendum September 2012BS EN 50522:2010National forewordThis British Standard is the UK implem
2、entation of EN 50522:2010.Together with BS EN 61936-1:2010, it partially supersedes BS 7354:1990. Where conflict exists between BS EN 50522:2010 and BS 7354:1990 the provisions of BS EN 50522:2010 take precedence.The UK participation in its preparation was entrusted to Technical Committee PEL/99, Er
3、ection and operation of power installations. Preparation of this National Foreword and the National Annexes was entrusted to both PEL/99 and Technical Committee GEL/600, Earthing. A list of organizations represented on these committees can be obtained on request to their secretaries.NOTE To ensure w
4、ide participation in the process, GEL/600, in particular, has strengthened its membership to include more representation from the UK Electricity Supply industry (TSOs and DNOs) and an earthing test equipment manu-facturer. Furthermore, detailed consultation has been carried out with The Energy Netwo
5、rks Association (ENA) through its Earthing Co-ordination Group.National Annexes NA, NB and NC have been appended to this standard.Background and developments to IEC/CENELEC documentsIn recent years, two documents have existed side-by-side covering, among other things, the earthing of high voltage in
6、stallations. The first was HD 637 S1, Power installations exceeding 1kV, published in 1999 while the other was IEC 61936-1, of the same title, published in 2002. These docu-ments were produced by working groups of the committees CENELEC TC/99X and IEC TC/99, respectively. As these documents were not
7、 published at the same time and the composition of the working groups was to some extent different, a situation arose such that significant discrepancies existed between these two documents, notably, concerning the fundamental safety criterion of allowable human body current and body impedance value
8、s under step and touch voltage conditions. This situation was not ideal, and an initiative was taken to develop a revision to IEC 61936-1 under maintenance team IEC TC/99 MT4 and to release it as a European standard. At the same time, a working group CENELEC TC/99X WG1 was formed to extract the eart
9、hing content of HD 637 S1 and bring to publication a new European standard on earthing (EN 50522). Parallel voting of EN 61936-1 and EN 50522 was arranged, in order to achieve harmonization of the adopted electrocution safety criteria and both documents were published in 2010.Background and developm
10、ent of UK earthing design standardsOver a similar period, within the UK, there were three important concurrent documents concerning the earthing of HV power installations. The first, BS 7354:1990, Code of practice for design of high-voltage open-terminal stations, prepared by Technical Committee PEL
11、/92, covered similar topics to IEC 61936-1, with Section 7 devoted to earthing. The other two documents, exclusively concerning earthing, were published by the Energy Networks Association, and can be considered as a set. These are Technical Specification 41/24 Issue 1 1992, Guidelines for the instal
12、lation, testing and maintenance of main earthing systems in sub-stations and Engineering Recommendation S34, Amendment 2 1988, A guide for assessing the rise of earth potential at substation sites.BRITISH STANDARDIn the period of the preparation of EN 61936-1 and EN 50522, the BSI committees GEL/600
13、 and PEL/99 coordinated activities with the aim to:a) achieve pro-active representation of UK interests on CENELEC TC/99X and IEC TC/99 working groups; and b) bring about a harmonization of the criteria for station earthing design in the UK. From this work, the following important aspects of the Nat
14、ional Annexes in this document that differ from the EN 50522 are worth highlighting.1) Recognition of the probabilistic nature of electrical system safety There has been a reaffirmation in BS EN 61936-1:2010 of the explicit recognition that the parameters involved in assessing safety are probabilist
15、ic in nature, with regard to the fault current magnitude and duration, as well as the probability of the fault occurrence, and the pres-ence probability of a human being. This has led to the introduction of a new additional approach to earthing system design in the UK based on probabilistic methods,
16、 which is outlined in National Annex NA using a design flow chart and developed with case studies in National Annex NB.2) Deviations of UK safety limits compared to IEC/CENELEC limits The release of DD IEC/TS 60479-1:2005, Effects of current on human beings and livestock Part 1: General aspects, pro
17、vided new data on human electrocution safety parameters; specifically new and lower values of human body impedances. The CENELEC and IEC working groups were concerned that this would result in lower maximum tolerable values of touch voltages, and as a result, proposed a modified method for calculati
18、ng such voltagesbased on an average of different shock scenarios and based on bodyimpedances not exceeded for 50% of the population (note, the first editionof IEC 61936-1 was based on left-hand to feet body impedances notexceeded for 5% of the population). However, as a result of adviceobtained from
19、 the UK Health and Safety Executive (HSE), consensuswas reached between PEL/99 and GEL/600 that UK HV earthing systemshave to be designed according to tolerable voltages based on bodyimpedances not exceeded for 5% of the population, as given inDD IEC/TS 60479-1:2005, Table 1 (Column 2) rather than t
20、he 50% values(Column 3). Also worth noting has been the consensus among PEL/99and GEL/600 to move away from using the tolerable body current curvec1 to curve c2 from DD IEC/TS 60479-1:2005, again, based onadvice from the UK HSE. This marks a departure from the very strict deterministic limits observ
21、ed previously under ENATS 41-24. However,the reduction in values of IEC published body impedances means thatthe resultant values of tolerable voltages are not greatly affected and certainly not reduced.Accordingly, the UK obtained a variation to the new CENELEC and IEC standards which has been recog
22、nized in the foreword of BS EN 61936-1:2010 and BS EN 50522:2010, Annex Q (A-Deviations). Hence, these documents specify the required difference in approach to earthing design in the UK, based on the 5% body impedance values. This variation affects the fundamental design parameters and in National A
23、nnex NA, a revised set of tolerable voltage curves has been produced to replace EN 50522:2010, Figure 4 (Section 5.4.3) and Figure B.2 (Annex B). The new UK tolerable touch voltage figures are given in National Annex NA.3) Additional guidance on assessing fault current distribution, earth potential
24、rise, design and testing of earthing systems Differences in the UK approach to earthing designBS EN 50522:2010BS EN 61936-1:2010 partially supersedes BS 7354:1990, and in particular it supersedes the earthing section of BS 7354. However, EN 50522:2010 does not provide sufficient detailed guidance on
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- EN505222010ENEARTHINGOFPOWERINSTALLATIONSEXCEEDING1KVACPDF

链接地址:http://www.mydoc123.com/p-717228.html